# Chapter 3: Means of Egress

3.1
scope
The provisions of this Section shall control the design, construction and arrangement of
building components to provide a reasonably safe means of egress. Any repair or
alteration works within a building shall be prohibited unless the existing means of egress
and fire protection system are continuously maintained or a continuous alternative exits
and protection measures are taken to provide an equivalent degree of safety for the
occupant and the workers for the total duration of such project.
3.2
Components of Means of Egress
3.2.1
A means of egress is an evacuation system with the provisions of reentry for
rescuers and fire fighters where a continuous and unobstructed way of exit travel shall be
provided from any point within a building to a designated area of refuge for allowable
delayed evacuation and ended up with the exit termination by reaching a street abutting
building or plot or an safe area which is open to air and designated assemblies for
evacuees.
The way of exit travel within a building form any point thereof along a means of egress
shall consist of three parts: (1) the exit access, (2) the exit, and (3) the exit discharge
(a)
A way or path of evacuation from any point of an area affected due to fire
incident leads to a protected entry to another separated area of a building
shall be termed as exit access. Straight line distance between the remotest
point of an area of incident and the entrance point of a separated area shall be
measured and termed as a travel distance.
(b)
The exit is a component or a group of components start with a protected
opening to evacuate an area of fire incidence and provides a safe entry to a
separated area which is component of means of egress and subsequently leads
to the exit discharge.
(c)
The outer edges or peripheral points of a building from where occupants shall
evacuate the building envelope termed as Exit discharges which shall lead
evacuees to the terminal points at a safe distance from thereof.
An area or any plot abutting street which is open to air and designated for systematic
assemblies of evacuees to complete the process of egress system shall be termed as exit
termination.

3.2.2
The parts of the means of egress consist of any of the following exit
components:
(a)
A doorway, separated or refuge area like smoke and fire proof enclosure,
compartment, corridor, passage, ramp, balcony, an exterior or open or interior
fire stair, or any combination of these, leads orderly to the exit discharge
which offer safety from fire or smoke from the area of incidence.
(b)
Horizontal exit shall provide a delayed egress by relocating the occupants
from their initial location due to a fire incident to a separated area at same
level of a same building or at the same level of adjoining or detached
buildings connected through a fire door or a vestibule or a passage or
corridors for relocation of evacuees. Receiving areas are capable to
accommodate expected evacuees for certain time period, free from heat,
smoke and aggressive fire, from the area of incidence and shall lead to exit
discharges without returning the evacuees to their initial locations.
3.2.3
Generally lifts, escalators and moving walks shall not be regarded as
components of means of egress. When they are designed and installed for safe operation
during fire shall be included as components of means of egress.
3.2.4
Means of Escape: A way out of a building or structure that does not conform to
the formation of means of egress but does provide a safe way out.
3.3
General Requirements
3.3.1
Design considerations or assumptions:
(a)
Fire initiated from only one source in single space shall aggravate within a
building or adjacent structures over a time period.
(b)
More than one space or source of fire at the same time shall not be
considered.
(c)
All Construction Materials by qualities and quantities including surface
finish, utilities, fabrications of movables and immovable, stored materials
shall be approved types as per provisions of this Code.
(d)
Stability of structural elements or building itself shall be as per provisions of
this Code.
(e)
Occupants, Rescuers and fire fighters life safety shall be the prime
consideration thus egress system including relocation and fight in place or
evacuation and reentry provisions shall be as per provisions of this Code.

(f)
Fire suppression and extinguishment arrangement for life safety and
minimize property damages shall be performance based as per provisions of
this Code.
(g)
Provisions of this Part shall be the minimum standard,  in excess of these
provisions shall not be prevented to design a egress system or to install
advance and higher standard of detection and extinguishment equipment or
both which shall be approved by the authorities having jurisdiction.
3.3.2
All buildings constructed for human occupancy or control areas or storages shall
be provided with adequate exit facilities to permit safe and quick unaided egress of the
occupants in the event of fire or other emergency.
3.3.3
Exits shall not be used for any other purpose at any time that would obstruct the
intended use of those components during emergency.
3.3.4
Where corridors or passages are components of exits shall not be designed or
used as components to supply or return air.
3.3.5
Preferences of levels of walking surfaces in the means of egress shall be more
than 1 in 20. Ramps or stairway shall be used in case of changes in elevations of walking
surfaces.
(a)
Abrupt changes not exceeding 130 mm but exceeding 60 mm shall be
beveled 1 in 2.
(b)
Changes in elevation exceeding 130 mm shall be considered as a change in
level.
(c)
A stairway in walking surface of the means of egress shall consist of
minimum two steps and all of them shall be identical and shall have tread
depth not less than 330 mm and height of risers shall not be exceeded more
than 230 mm but shall comply tread and riser combination as per provision of
this Code.
(d)
Changes in levels 530 mm or more in walking surfaces of the means of
egress shall be achieved either by a ramp or by a stairway.
(e)
Presence and location of such steps or ramps in the walkways shall be readily
apparent.
(f)
Other than ramp, a slope of walking surfaces along the direction of travel
shall not be steeper than 1 in 20 and slope perpendicular to the travel
direction shall not be exceeded 1 in 48.
(g)
Slope of ramps shall be complied with the accessibility where required as per
provisions of this Code.

3.3.6
From the exit access all exits shall be clearly visible. Corridors and passages
leading to the exit discharge shall be marked and signposted to guide the evacuees as per
provisions of this Code. A space used in darkness having more than one exits shall be
illuminated exits sign as per provision of this Code.
3.3.7
The owner or lessee of all new and existing buildings shall be responsible to
provide the safety provisions for all occupants and rescuers and firefighters. If in any
existing building, the exit facilities are deemed inadequate in view of the requirements of
this Code, the authority having jurisdiction may order to comply with the provisions of
this Code.
3.4
General Provisions of Exits
3.4.1
All exits shall be easily discernible and accessible from the areas served by
them.
3.4.2
Exit from any room or space shall not open into an adjoining or intervening
room or area except where such adjoining room or area is an accessory to the area served,
is not a hazardous occupancy. If hazardous or a control area, provide a direct exit to the
outside of a building envelope or directly connect with the components of egress system.
3.4.3
No portion of Exits shall pass through a room that may be subject to lock with
detachable key or be intervened by a door that may have detachable key operated lock
and the door is locked when the building is occupied.
3.4.4
All entry points to the assembly occupancy shall serve as Exits and shall have
the total capacity for at least one-half of the total occupant load. Provisions of exits other
than entries shall have capacity to evacuate at least two-thirds of occupant from each
level of assembly occupancy.
3.4.5
All exits shall be so located and arranged that they shall provide continuous and
unobstructed means of egress up to the exit discharge.
3.5
Occupant Load
Total occupant load means summation of all occupants of only one level at the pick hour
occupancy where maximum occupants are present.
Occupant load shall be considered as per provisions of this Code to design each and
every component of means of egress system shall be termed as design occupant load.

3.5.1
Design Occupant Load
The design occupant load for which the component of means of egress is to be provided
shall be the highest number computed as per the provisions of (a), (b) and (c) as stated
below:
(a)
The actual number of occupants for whom the area served by the exits is
designed;
(b)
Number of occupants shall be computed as prescribed in Table 4.3.1.
(c)
The number of occupants in any area shall be computed as per provisions of
(a) or (b) as stated above and in all cases the higher value shall govern the
design.
(d)
The computation of design occupant load shall be the summation of
occupants of a space and the evacuees of other spaces whose are using the
said space as for waiting or passing through in case of emergency to gain an
access to a component of means of egress.
Table 4.3.1: Occupant Load Factor
Occupancy
Unit of Floor Area in m2 per
Occupant\*
A      Residential
18 gross
B      Educational:
Class room
Preschool

2 net

### 3.5 net

C      Institutional
12 gross
D      Health Care:
In patient areas
Out-patient areas

15 gross
10 gross
I

Assembly:
with fixed seats
with movable seats
standing space only
with table and chairs
Passengers that can be unloaded
simultaneously to a terminal or a
platform

Number of seats designed.

### 0.93 net

### 0.37 net

### 1.5 net

### 0.15 net

E      Business: Office Space
3 gross

Occupancy
Unit of Floor Area in m2 per
Occupant\*
F

Mercantile:
Retail sales Area, Ground  floor
or Basement
All other floor

### 2.3 net

### 4.6 net

G      Industrial
10 gross
H      Storage
20 net
K      Garages and open parking structures
23 net
L      Utility
Actual occupant load
M     Miscellaneous Building
Actual occupant load

* As per Sec 3.5.1(b) of this Chapter, design occupant load shall be calculated and any
  fraction shall be rounded to next higher integer value. Width of all components of
  egress system shall satisfy requirements of specified in the Table 4.3.2
  3.5.2
  Fixed Seats
  The occupant load for an assembly or educational area having fixed seats shall be
  determined by the seating capacity of the area. For fixed seats without dividing arms, the
  capacity shall be taken as one person for every 500 mm of seat.
  3.5.3
  Maximum Occupant Load
  The design occupant load, need not to be calculated more than one person per 0.3 m2 of
  usable floor space.
  3.5.4
  Mezzanine Floors
  The occupants of a mezzanine floor evacuating through other floors the occupant load
  shall be added to the receiving floors.
  3.5.5
  Roofs
  A Roof, an open air space used as assembly or refuge area, educational or other types of
  human occupancy shall be provided with exit facilities as per provisions of this Code.
  3.6
  Capacity of Exit Components
  3.6.1
  The capacity of egress components shall be complied with the occupant load of
  the area served. The required width of each component shall be computed on the basis of
  the allotted width per occupant prescribed in Table 4.3.2, subject to the minimum widths

of such components specified in Sections 3.7 to 3.12 and the travel distances of such
components as per provision of this Code.
Table 4.3.2: Required Width per Occupant

Occupancy
Buildings without Sprinkler
System (mm per person)
Buildings thoroughly
Sprinkled (mm per person)
Stairways
Ramps &
Corridors
Doors Stairways Ramps &
Corridors
Doors
A
B
E
F1, F2
G
H
Residential
Educational
Business
Mercantile
Industrial
Storage

C1, C2
Institutional
C3, C4, C5  Institutional
D
Health Care
I
F3
Assembly
Mercantile
J
Hazardous
K,  L, M

Note:  width of the components of egress shall be divided by value specified in this
table to determine the maximum allowable occupant load served by them.
3.7
Corridors and Passageways
3.7.1
Occupants commencing exit travel along a corridor or a passageway shall be
lead to an exit discharge. Length of dead end corridors and passageways and branches
thereof shall not be exceeded as per Sec 3.15.4 of this Chapter.
3.7.2
The required width of corridors and passageways shall be calculated on the basis
of the occupant load in accordance with the provisions of this Code and shall not be less
than as per Sec 3.15.4 of this Chapter.
3.7.3
The minimum ceiling height of the corridors and passageways used as a means
of egress shall not be less than 2.4 m.

| Occupancy                                     | Col2                                                                                     | Buildings without Sprinkler<br />System (mm per person) | Col4                           | Col5           | Buildings thoroughly<br />Sprinkled (mm per person) | Col7                           | Col8       |
| --------------------------------------------- | ---------------------------------------------------------------------------------------- | ------------------------------------------------------- | ------------------------------ | -------------- | --------------------------------------------------- | ------------------------------ | ---------- |
| **Occupancy**                                 | **Occupancy**                                                                            | **Stairways**                                           | **Ramps &**<br />**Corridors** | \*\*Doors \*\* | \*\*Stairways \*\*                                  | **Ramps &**<br />**Corridors** | **Doors**  |
| A <br />B <br />E <br />F1, F2<br />G <br />H | Residential<br />Educational<br />Business<br />Mercantile <br />Industrial<br />Storage | 8                                                       | 5                              | 4              | 5                                                   | 4                              | 4          |
| C1, C2                                        | Institutional                                                                            | 8                                                       | 5                              | 4              | 5                                                   | 5                              | 4          |
| C3, C4, C5                                    | Institutional                                                                            | 10                                                      | 5                              | 4              | 8                                                   | 5                              | 4          |
| D                                             | Health Care                                                                              | 25                                                      | 18                             | 10             | 15                                                  | 12                             | 10         |
| I <br />F3                                    | Assembly<br />Mercantile                                                                 | 10                                                      | 7                              | 5              | 7                                                   | 5                              | 5          |
| J                                             | Hazardous                                                                                | 8                                                       | 5                              | 4              | 8                                                   | 5                              | \*\*4 \*\* |
| K,  L, M                                      |                                                                                          | 8                                                       | 5                              | 4              | 5                                                   | 4                              | 4          |

3.7.4
All exit corridors or passages shall have a fire resistance rating of 1 hour or
more as per provisions of this Code.
3.7.5
Protective opening leads to an exit shall be fire doors or fire windows or a fire
assembly having a fire resistance rating of at least 20 minutes or more as per provisions
of this Code.
(a)
Certified Fire resistance rating of Doors shall be in accordance with ASTM
E152 without the hose stream test.
(b)
Fire resistance rating of the fire door assembly has to perform as required 20,
30, 60, 90, 180 minutes or more shall be leveled A, B, C, D, E and F
respectively.
(c)
Fire door assembly of any approved materials shall qualify through ASTM
E152 without the hose stream test.
3.8
Assembly Seating and Waiting
(a)
Assembly buildings primarily meant for theatrical, operatic performances or
cinematic projection shall have the seats securely fastened to the floor with
exceptions as permitted in this Code. All seats in balconies and galleries shall
be securely fastened to the floor except boxes with level floor and less than
14 seats.
(b)
Seats not fixed to the floor shall be permitted in restaurants and such other
places provided that 1.25 m2 of floor space is allotted for every seat
excluding dancing floor and stage. Adequate aisles shall be maintained at all
times to reach exits without obstruction when such occupancies are in use.
3.8.1
Assembly buildings which contain seats, tables, equipment or exhibitions or
displays shall be provided with aisles, free of obstructions, leading to the exit.
3.8.2
Minimum clear widths of steeped aisles and other means of egress serving
assembly seating shall be calculated on the basis of number of seats and in accordance
with Table 4.3.3. Interpolation shall be permitted between the specific values shown
thereof. The minimum clear width of steeped aisles as found by above calculation shall
be modified in accordance with the conditions stated below:
(i)
If risers exceed 178 mm in height for steeped aisles the width of the steeped
aisles as shown  in the table shall be multiplied by factor a,

Where,        = 1 +

ℎ



(4.3.1)
(ii)
In the Table 4.3.3 values of steeped aisles not having a handrail within a
760 mm horizontal distance shall be 25 percent wider.

(iii)
In Table 4.3.3 values of width of ramps used for ascending and steeper than
1 in 10 slope shall be increased by 10 percent.
Table 4.3.3: Capacity Factors for Assembly Seating
Number of seats within a
single assembly space.
Clear Width per Seat Served
Steeped aisles (mm)
Passageways, Ramps
and Doorways(mm)
≤ 2,000

### 7.6  a

5.6
5,000

### 5.1  a

3.8
10,000

### 3.3  a

2.5
15,000

### 2.4  a

1.8
20,000

### 1.9  a

1.4
≥25,000

### 1.5 a

1.1
3.8.3
The minimum width of level or ramped aisles shall be as specified below:

Seats on both sides of the aisle

### 1.0 m

Seats on one side of the aisle

### 0.9 m

3.8.4
The minimum width of stepped aisles shall be as specified below:

Seats on both sides of the aisle

### 1.2 m

Seats on one side of the aisle

### 1.0 m

3.8.5
The minimum clear gap between rows, measured as the clear horizontal distance
between the back of the row ahead and the nearest projection of the row behind shall be
300 mm. For chairs having automatic or self-rising seats, the measurement shall be made
with the seats in the raised position, for non-automatic seats the measurement shall be
taken with the seats in the down position.
3.8.6
For rows of seating served by an aisle or doorway at only one end of the row,
the path of travel shall not exceed 10 m from any seat to the aisle or doorway. The
minimum clear gap between rows shall be increased beyond 300 mm specified in Sec

#### 3.8.6 by 15 mm for each seat in excess of 7, but the clear gap need not exceed 550 mm.

3.8.7
In any assembly occupancy spectators are allowed to wait in the lobby or similar
space within the building until seats are available. Exits shall be provided for the waiting
spaces on the basis of 0.28 m2 areas per person waiting space and one wheel chair space

| Number of seats within a<br />single assembly space.                | Clear Width per Seat Served                                                         | Col3                                             |
| ------------------------------------------------------------------- | ----------------------------------------------------------------------------------- | ------------------------------------------------ |
| **Number of seats within a**<br />**single assembly space.**        | **Steeped aisles (mm)**                                                             | **Passageways, Ramps**<br />**and Doorways(mm)** |
| ≤ 2,000<br />5,000<br />10,000<br />15,000<br />20,000<br />≥25,000 | 7.6\_a\_ <br />5.1\_a\_ <br />3.3\_a\_ <br />2.4\_a\_ <br />1.9\_a\_ <br />1.5\_a\_ | 5.6<br />3.8<br />2.5<br />1.8<br />1.4<br />1.1 |

for every 100 occupant. Such waiting occupant load shall be added with main assembly
load for calculating exit size for the assembly as per provisions of this Code.
3.9
Doorways
One surface of a door leaf which is exposed to a fire incident is the terminal point of exit
access and other surface of that said door which is unexposed to that fire incident is the
starting point of an exit. A door or an opening protective assembly is an obstruction for
occupants to pass through from exit accesses to exits until and unless it is installed as per
provisions of this Code.
3.9.1
Each occupant of a room or space shall have access to at least one exit door or
exit access assembly. The occupant load per exit door and the travel distance up to that
door shall not exceed the values specified in Table 4.3.4.
3.9.2
Where either the occupant load or the travel distance exceeds the values
specified in Table 4.3.4 shall have multiple exit doors to comply the both.
3.9.3
The width of a door shall not be less than 1 m and the height shall be not less
than 2 m. Exit doors shall be side swing or pivoted of side hinge type.
3.9.4
No sliding or hanging door shall be used as a means of exit. In pressurized areas
and when occupant load is less than 10, restriction of Sec 3.9.3 may be exempted.
3.9.5
All exit access doors shall be of a side-swinging type. When the occupant load
exceeds 50 or in a hazardous occupancy, the doors shall swing outward from the room or
towards the direction of travel. Swinging of the door shall not constrict the width of the
corridor narrower than 0.9 m measured at the most critical position.
3.9.6
Exit doorways shall not open directly on a flight of stairway. A clear area which
more than the width of the door leaf as specified in the above Sec 3.9.5 shall be
maintained immediately outside the doorway. The floor levels shall be same in the
direction of travel as per provisions of this Code.
Table 4.3.4:  Maximum Occupant Load and Travel Distance for Spaces with One
Exit Door
Occupancy
Maximum Design
Occupant  Load
Maximum Travel
Distance (m)
A
Residential
C
Institutional
D
Health Care

B
Educational
I
Assembly
E                Business
F                Mercantile
G
Industrial

| Exit Door                                                                                                                                    | Col2                                       | Col3                                     |
| -------------------------------------------------------------------------------------------------------------------------------------------- | ------------------------------------------ | ---------------------------------------- |
| **Occupancy**                                                                                                                                | **Maximum Design**<br />**Occupant  Load** | **Maximum Travel**<br />**Distance (m)** |
| A<br />    Residential<br />C<br />    Institutional<br />D<br />    Health Care                                                             | 12                                         | 23                                       |
| B<br />    Educational<br />I <br />    Assembly<br />E                Business<br />F                Mercantile<br />G<br />     Industrial | 50                                         | 23                                       |

H
Storage
J
Hazardous
3.9.7
Revolving doors shall not be used as a means of exit in assembly, educational or
institutional buildings or in spaces with an occupant load of 200 or more. In all other
cases revolving doors shall not constitute more than half of the total required exit door
width and each revolving door with least diameter of 2.7 m shall be credited not more
than 50 persons. Exit doors shall be installed in the same wall within proximity of 3m of
Revolving doors and shall comply with the following:

##### 3.9.7.1 Revolving doors shall be positioned with a dispersal area at a distance of 3m or

more from the foot or top of stairway or escalators or moving walks or lift lobbies.

##### 3.9.7.2 Revolving doors shall stop rotating and stand still in a book-fold position at a

force not more than 800 N or when a force is applied not more than 578 N to a wing
within 760 mm of outer edge or due to sudden power failure catch automatically released
and ready to manual revaluation and that provide a path which shall have aggregate width
minimum 910 mm.

##### 3.9.7.3 A manual control switch shall be installed in an approved location.

##### 3.9.7.4 Speed of revolving door shall not exceed the revolution per minute shown

below:
Speed of Revolving Door
Inside Diameter (m)
Manual-mode Speed
limit (rpm)
Power-mode Speed
limit (rpm)
2.1
2.3
2.4
2.6
2.7
2.9

##### 3.9.7.5 All exit doors shall be operable without the using a detachable key from the side

they serve to evacuate.
3.10
Stairways
Change in level in elevations achieved by steps combination of identical risers and treads
as per provisions of this Code shall be termed as Stairway irrespective of their locations.
Stairways within an envelope shall be termed as Staircase. Exception: stepped aisles with
in an assembly.
Width of Stairways shall be a length perpendicular to the direction of travel, a clear
distance measured between inner edges of handrails or a clear distance between inner
edges of a handrail of exposed side to its opposite and parallel surface measured at a
height of inner edge of cross section of that handrail. In case of variation in width
measurement the smallest value shall represent the width of a stairway. Required
combination of dimensions for risers and treads given in Table 4.3.5.
Required guards and handrails shall continue for the full length of each flight
of stairways. Inner turns of handrail of flights shall be at the landings and grasp ability of
handrails shall be smooth and continuous, Handrail Brackets or balusters attached to the
bottom surface of handrail shall not be considered to be obstructions to grasp ability. Gap
between any surface and handrail shall be not less than 63.5 mm.
Stairways serving more than three storey building having capacity more than 10
occupants shall have visual enclosures to avoid any impediments to stair use by persons
having fear of height, any arrangement intended to meet this requirement shall be at least
1070 mm in height.
3.10.1
The required width of exit stairways shall be computed in accordance with the
provisions of Sec 3.6, but it shall not be less than the minimum widths specified in Tables

#### 4.3.6 and 4.3.7

3.10.2
The least dimension of landings or platforms in exit stairways shall not be less
than the required width of stairway and shall be leveled, except that the landing between
two stair flights in a straight run shall not be required to be wider than 1.2 m in the
direction of travel.
When two stair flights are not straight or nonparallel to each other, a turning in the path
of travel direction occurred which is other than U turn. Landing width shall be the

required width of stairway and length of the common landing between such flights shall
be one tread depth more lengthen when measured from both edges of stairway from both
the flights.
Table 4.3.5: Combination of Risers and Treads
Gradients
Step Dimensions

Available
Headroom
Clearance of
Flight
Handrail
or
Guard
Height
Maximum
Number
of Flights
Grade
Angle of Flight
Tread
Depths
Risers
(%)
Deg
(mins)
(mm)
(mm)
(mm)
(mm)

31.25
33.87
37.28
41.07
44.44
Unlimited
48.07
53.06
57.44
63.63
69.04
81.57
88.88
97.05
103.02
107.07
112.5

| Gradients | Col2                | Col3                | Step Dimensions           | Col5       | Available<br />Headroom<br />Clearance of<br />Flight | Handrail<br />or<br />Guard<br />Height | Maximum<br />Number<br />of Flights |
| --------- | ------------------- | ------------------- | ------------------------- | ---------- | ----------------------------------------------------- | --------------------------------------- | ----------------------------------- |
| **Grade** | **Angle of Flight** | **Angle of Flight** | **Tread**<br />**Depths** | **Risers** | **Risers**                                            | **Risers**                              | **Risers**                          |
| **(%)**   | **Deg**             | **(mins)**          | **(mm)**                  | **(mm)**   | **(mm)**                                              | **(mm)**                                |                                     |
| 31.25     | 17                  | 21                  | 406                       | 127        | 2159                                                  | 851                                     | 6                                   |
| 33.87     | 18                  | 43                  | 394                       | 133        | 2184                                                  | 2184                                    | 2184                                |
| 37.28     | 20                  | 27                  | 375                       | 140        | 140                                                   | 140                                     | 140                                 |
| 41.07     | 22                  | 20                  | 356                       | 146        | 146                                                   | 146                                     | 146                                 |
| 44.44     | 23                  | 58                  | 343                       | 152        | 2210                                                  | 838                                     | Unlimited                           |
| 48.07     | 25                  | 40                  | 330                       | 159        | 159                                                   | 159                                     | 159                                 |
| 53.06     | 27                  | 57                  | 311                       | 165        | 2235                                                  | 2235                                    | 2235                                |
| 57.44     | 29                  | 52                  | 324                       | 171        | 171                                                   | 171                                     | 171                                 |
| 63.63     | 32                  | 28                  | 279                       | 178        | 2261                                                  | 2261                                    | 2261                                |
| 69.04     | 34                  | 37                  | 267                       | 184        | 2286                                                  | 2286                                    | 2286                                |
| 75        | 36                  | 52                  | 254                       | 190        | 2311                                                  | 2311                                    | 2311                                |
| 81.57     | 39                  | 12                  | 241                       | 197        | 2362                                                  | 851                                     | 851                                 |
| 88.88     | 41                  | 38                  | 229                       | 203        | 2388                                                  | 2388                                    | 2388                                |
| 97.05     | 44                  | 9                   | 216                       | 210        | 2438                                                  | 2438                                    | 2438                                |
| 103.02    | 45                  | 51                  | 210                       | 216        | 2464                                                  | 2464                                    | 2464                                |
| 107.07    | 46                  | 57                  | 206                       | 222        | 2489                                                  | 864                                     | 10                                  |
| 112.5     | 48                  | 22                  | 203                       | 229        | 2515                                                  | 2515                                    | 2515                                |

Note:  Allowable length of nosing at the outer edge of tread shall not be included in the
tread depth measurement. The maximum rise of a single flight between landings
shall not be exceeded 3658 mm and in case of large assembly maximum rise of
a single flight between landings shall not be exceeded 2438 mm.
Table 4.3.6: Minimum Width of Stairways in Egress System
Occupancy
Minimum Width of Each
Stairway (mm)
A
Residential: A1, A2
A3, A4, A5
As per Table 4.3.6
B
Educational
Occupant load up to 130
Occupant load more than 130  but not more 250

D
Hospital

Patient area

Staff area

I
Assembly: I1, I2, I3, I4, I5
As per provisions of this Code.
All others
As per provisions of this Code.
Note:  The required number of stairways shall be determined by dividing the calculated
total widths of stairways as per sections 3.5, 3.6 and Table 4.3.2 of this Chapter
by applicable minimum stair width as specified in this table and any fractions
thereof shall be rounded up with the next higher integer. Unit width of stair and
multiple even numbers shall be maintained as per provisions this Code.
Table 4.3.7: Fire Escape Stairs
Element
Serving More than 10
Occupants
Serving 10 or Fewer
Occupants
Clear widths
560 mm between handrails
Minimum horizontal
dimension of any
landing or platform
560 mm
Maximum riser height
230 mm

| Table 4.3.6: Minimum Width of Stairways in Egress                                                                   | System                                                |
| ------------------------------------------------------------------------------------------------------------------- | ----------------------------------------------------- |
| **Occupancy**                                                                                                       | **Minimum Width of Each**<br />\*\*Stairway (mm) \*\* |
| A<br />Residential: A1, A2<br />A3, A4, A5                                                                          | As per Table 4.3.6<br />1120                          |
| B <br />Educational<br />               Occupant load up to 130<br /> Occupant load more than 130  but not more 250 | <br />1120<br />2235                                  |
| D <br />Hospital<br />Patient area<br />Staff area                                                                  | 2235<br />1120                                        |
| I<br />Assembly: I1, I2, I3, I4, I5                                                                                 | As per provisions of this Code.                       |
| All others                                                                                                          | As per provisions of this Code.                       |

| Element                                                           | Serving More than 10<br />Occupants | Serving 10 or Fewer<br />Occupants |
| ----------------------------------------------------------------- | ----------------------------------- | ---------------------------------- |
| Clear widths                                                      | 560 mm between handrails            | 560 mm between handrails           |
| Minimum horizontal<br />dimension of any<br />landing or platform | 560 mm                              | 560 mm                             |
| Maximum riser height                                              | 230 mm                              | 230 mm                             |

Element
Serving More than 10
Occupants
Serving 10 or Fewer
Occupants
Minimum tread,
exclusive of nosing
250 mm
Tread construction
Solid, 13 mm diameter perforation permitted
Winders
Not permitted
permitted subject to Sec 3.10.7
Spiral
Not permitted
permitted subject to Sec 3.10.7
Maximum height
between landings

### 3.70 m

Headroom, minimum

### 2.00 m

Access to protected
openings
Door or casement windows,
600 mm x 2000 mm or
double-hung windows 70 mm
x 900 mm clear opening
Window providing a clear
opening of at least 500
mm in width, 600 mm in
height, and 0.53 m2 in
area
Level of access
openings
Not over 300 mm above floor; steps if higher
Discharge to ground
Swinging stair section permitted if approved by authority
having jurisdiction
Capacity, number of
person
13 mm per person if access
by door; 25 mm per person if
access
by
climbing
over
window sill
Note: The maximum design occupant load for a Fire escape stair shall not be exceeded
50 occupants from any floor level.
3.10.3
The rise and tread dimensions in a stairway shall be identical and the headroom
requirements shall conform to the provisions of this Code.
3.10.4
Handrails height on stair shall be not less than 860 mm and not more than 960
mm above the surface of the tread, measured vertically from the top of the rail to the
outer edge of the tread. Peripheral diameter of circular cross section of a handrail shall
not be less than 32 mm and not more than 50 mm. Any other shape with perimeter
dimension of not less than 100 mm, but not more than 160 mm and with the largest cross-
sectional dimension not more than 55 mm shall be permitted provided that all edges are
rounded to provide a radius of not less than 3 mm. Handrails shall be graspable along
their entire length. Additional handrails that are lower or higher than main shall be
permitted.

| Element                                 | Serving More than 10<br />Occupants                                                                                       | Col3                                                                                                                      | Serving 10 or Fewer<br />Occupants                                                                                      |
| --------------------------------------- | ------------------------------------------------------------------------------------------------------------------------- | ------------------------------------------------------------------------------------------------------------------------- | ----------------------------------------------------------------------------------------------------------------------- |
| Minimum tread,<br />exclusive of nosing | 250 mm                                                                                                                    | 250 mm                                                                                                                    | 250 mm                                                                                                                  |
| Tread construction                      | Solid, 13 mm diameter perforation permitted                                                                               | Solid, 13 mm diameter perforation permitted                                                                               | Solid, 13 mm diameter perforation permitted                                                                             |
| Winders                                 | Not permitted                                                                                                             | permitted subject to Sec 3.10.7                                                                                           | permitted subject to Sec 3.10.7                                                                                         |
| Spiral                                  | Not permitted                                                                                                             | permitted subject to Sec 3.10.7                                                                                           | permitted subject to Sec 3.10.7                                                                                         |
| Maximum height<br />between landings    | 3.70 m                                                                                                                    | 3.70 m                                                                                                                    | 3.70 m                                                                                                                  |
| Headroom, minimum                       | 2.00 m                                                                                                                    | 2.00 m                                                                                                                    | 2.00 m                                                                                                                  |
| Access to protected<br />openings       | Door or casement windows,<br />600 mm x 2000 mm or<br />double-hung windows 70 mm<br />x 900 mm clear opening             | Door or casement windows,<br />600 mm x 2000 mm or<br />double-hung windows 70 mm<br />x 900 mm clear opening             | Window providing a clear<br />opening of at least 500<br />mm in width, 600 mm in<br />height, and 0.53 m2 in<br />area |
| Level of access<br />openings           | Not over 300 mm above floor; steps if higher                                                                              | Not over 300 mm above floor; steps if higher                                                                              | Not over 300 mm above floor; steps if higher                                                                            |
| Discharge to ground                     | Swinging stair section permitted if approved by authority<br />having jurisdiction                                        | Swinging stair section permitted if approved by authority<br />having jurisdiction                                        | Swinging stair section permitted if approved by authority<br />having jurisdiction                                      |
| Capacity, number of<br />person         | 13 mm per person if access<br />by door; 25 mm per person if<br />access<br />by<br />climbing<br />over<br />window sill | 13 mm per person if access<br />by door; 25 mm per person if<br />access<br />by<br />climbing<br />over<br />window sill | 10                                                                                                                      |

3.10.5
The height of guards shall not be less than 105 mm measured vertically from the
top of the guards from the surface of adjacent area to be served by them. When blasters
are used in the guards rail shall be used to create a pattern as such size that a sphere 100
mm in diameter shall not pass through any opening up to a height of 860 mm. Riser, tread
and the bottom rail of guards formed a triangular opening shall not be of such size that a
sphere 150 mm in diameter shall not pass through.
3.10.6
There shall be no variation in excess of 5 mm in depth of adjacent treads or in
the height of adjacent risers, and the tolerance between the largest and smallest tread or
between the largest and smallest riser is 10 mm in any flight.
3.10.7
Monumental stairs, Circular stairs, Curved stairs, Spirals and winders, stepped
and rung ladders, alternate tread devices shall be permitted as per provisions of this Code.

##### 3.10.7.1  When the width of stairways exceeded 4475 mm termed as Monumental or

Grand Stairway shall be permitted as per provisions of this Code.

##### 3.10.7.2  Curved stairs or circular stairs shall be permitted as a component of means of

egress as per provisions of this Code provided that the depth of tread is not less than 280
mm at a point 300 mm from the narrower end of the tread and the smallest radius is not
less than twice of stair widths and shall comply with the provisions of this Code.

##### 3.10.7.3  Spiral stairways shall be permitted where occupant load shall not more than

five. For spiral stairways the following conditions shall be applicable:
(a)
The clear width of the stairs shall not be less than 660 mm.
(b)
The height of risers shall not exceed 240 mm.
(c)
Headroom shall be not less than 1980 mm.
(d)
Treads shall have a depth not less than 190 mm at a point 300 mm from the
narrower edge.
(e)
All treads shall be identical.

##### 3.10.7.4  Winders shall be permitted in stairs where occupant load shall not be more than

three.
(a)
Winders shall have a tread depth not less than 150 mm and a tread depth not
less than 280 mm at a point 300 mm from the narrowest edge.
(b)
The clear width of the stairs shall not be less than 660 mm.

##### 3.10.7.5  Stepped ladders and Rung ladders shall be installed with pitch that exceeds 75

degrees as per standards of ANSI A14.3. The lowest rung of any ladder shall not be more
than 300 mm above the level of the surface beneath it.
(a)
From towers and elevated platforms around machinery or similar spaces
subject to occupancy load not to exceed three persons.
(b)
Open structure, observation towers or railroad signals that are designed for
occupancy not more than three persons.

##### 3.10.7.6  Alternate tread device

The occupant load shall not exceed three and shall comply with the followings:
(a)
Handrail shall be provided on both sides of alternate tread device having
clear width not less than 430 mm and not more than 610 mm
(c)
Headroom shall not less than 2000 mm and angle of the device shall be
between 50 degrees and 68 degrees to horizontal.
(c)
The initial tread of the device shall begin at the same elevation as the
platform, landing, or floor surfaces and the alternating treads shall not be
laterally separated by a distance more than 50 mm.
(d)
Treads shall have projected depth not less than 150 mm and each tread
providing 240 mm of depth, including overlapping of treads.
(e)
The height of the risers shall not exceed 240 mm.
3.10.8
Stairways shall have continuous guards on both side along the direction of travel
and a continuous handrail shall be provided with inner edge guard. A stair of width more
than 1120 mm but not more than 2235 mm shall have guards and handrails on both of the
edges. Inner edge handrails shall be continuous and outer edge handrails shall be along
the flights extended up to one tread depth on both the landings.  A stair the width exceeds
2235 mm; intermediate handrails shall be installed with similar length of outer edge
handrail. Single traffic lane shall be calculated 560 mm in the stairway and two traffic
lanes shall be 1120 mm. Widths of stairs shall be multiple of two traffic lane other than
width specified in the Table 4.3.6.
3.10.9
All exit stairways shall be constructed by materials that conform to the fire
resistance requirements of the type of construction of the building, except that solid
wooden handrails shall be permitted for all types of construction.

#### 3.10.10 An exit stairway shall not be built around a lift shaft unless both of them are

located in a smoke proof enclosure and made of a material with fire resistance rating
required for the type of construction of smoke proof enclosure.

#### 3.10.11 Exterior stairways used as fire stair shall not be considered as a component of

means of egress, unless they lead directly to the ground or a refuge area, are separated
from the building interior by fire resistive assemblies or walls and are constructed by
noncombustible materials and free from smoke accumulation.
3.11
Ramps
3.11.1
Ramp is a sloping surface steeper than 1 in 20 but not steeper than 1 in 8 used by
walkers only. Slope of ramps to comply with accessibility requirement shall not be
steeper than 1 in 12.
3.11.2
The minimum width of exit ramps shall not be less than that width required for
corridors or passages.
3.11.3
The slope of an exit ramp shall not exceed 1 in 8, but for slopes steeper than 1 in
10 the ramp shall be surfaced with approved non-slip material or finished such as to
effectively prevent slipping.
3.11.4
Guards and handrails shall be provided on both sides of ramps having slope
steeper than 1 in 15.
3.11.5
Ramps shall be straight, in case of changes in the travel direction that shall be
made at the level platforms or at the landings except that ramps having a slope steeper
than 1 in 12 may be curved at any place.
3.11.6
Length of the sloping portion of ramps shall be at least 915 mm but not more
than 9150 mm long between level platforms or landings.
3.11.7
Level platforms or landings shall be at least as wide as the ramps and shall be
placed at the bottom, at intermediate levels where required, and at the top of all ramps.
Level platform shall be provided on each side of openings into or from ramps having
minimum length of 915 mm in the direction of travel and when a door swings on the
minimum length of platform or landing shall be 1525 mm.
3.11.8
Doors on ramps shall not be opened on sloping surface shall be complied with
the requirements of 3.9 of this Chapter.
3.11.9
Sloping or ramp driveway approaching basements or any parking structures
shall not be credited as an exit ramp when slope is steeper than 1 in 8 and not complied

with Sec 3.11 of this Chapter. Exits requirement of such basements shall be achieved by
stairways or fire lifts within smoke proof enclosure approached by a two doors smoke
lock vestibule.
3.12
Horizontal Exits
3.12.1
The connection between two separated areas of a building or connection
between buildings at same level which the horizontal exit serves shall be provided with at
least 2 hour fire resistance rated walls, or by an open air balcony or a bridge having
protected openings.
3.12.2
The horizontal exits shall be protected from the area of incidence by
self-closing fire door.
3.12.3
The width of a horizontal exit access door shall not be less than 1 m.
3.12.4
Changes in level in the elevation along the direction of the horizontal exit shall
not be achieved by single step but by ramps which is not stepper than 1 in 12.
3.12.5
Where the horizontal exit serves for only one side, fire door shall swing in along
the direction of travel. When horizontal exit serves both the side of separated area, the
doors shall have two leaves and each leave dedicated to satisfy direction of travel from
assigned area, or there shall be two independent doors assigned for two areas each of
them serves only one area. When the building is occupied the doors installed in
horizontal exit shall be operable at all times without the use of a detachable key.
3.12.6
Horizontal exit relocates occupants to an area which is either a public space or a
space used by other occupants and shall be termed as a refuge area. The capacity of the
refuge area shall be computed on the basis of net floor area excluding stairways, shafts
and spaces allotted to occupants of the receiving end. The required capacity of a refuge
area shall be 0.28 m2 per healthy occupant and 0.3 m2 per wheelchair or 2.8 m2 per
patients retained in bed for delayed egress or an area equivalent to a passage or a corridor
having width to comply the capacity of evacuees and connected with the components of
exits up to exit discharge.
3.13
Smoke Proof Enclosure
Any compartment or a room or a control area surrounded by barrier walls within a
building structure shall be protected from smoke penetration during a fire incident
occurred elsewhere in the building shall be termed as smoke proof enclosure.

A stairway with in an envelope shall be termed as Interior stairway or staircase. Any
exterior side having opening of 50 percent or more in such a way that there shall be no
smoke accumulation shall be termed as open stair.
3.13.1
An interior stairway conforming to Sec 3.10 and having entry from an exterior
balcony or through a ventilated vestibule conform a smoke proof enclosure provided no
direct opening or any aperture allowed on the walls of the stair from the building side.
3.13.2
All exit stairways mentioned above shall be protected by a smoke proof
enclosure when serving occupants are located in a high rise building.
3.13.3
There shall be provision to access enclosed stairways through vestibule or an
open balcony. The minimum width of a vestibule shall be equal to width of connected
passages or corridors specified in section 3.7 in this Chapter and the minimum length of a
vestibule in the direction of travel shall be 1.8 m.
3.13.4
The minimum fire resistance rating of the walls forming a smoke proof
enclosure around stairway including the vestibule thereof shall be 4 hours and separated
from the area of incidence having no openings other than a fire door for the entry to the
vestibule. For fire rating of the door see Chapter 1 Part 3.
3.13.5
All doors in smoke proof enclosure and the vestibule shall be self-closing type
or they shall be fitted with automatic closing devices actuated by the fire detection
system.
3.13.6
The vestibule shall have adequate natural ventilation. Each vestibule shall have a
minimum area of openings of 2 m2 divided into two in an exterior wall facing a
courtyard, street or public way wider than 6 m. The location of one opening measuring

### 1.5 m2 shall be as high as possible and another shall be 0.5 m2 as low as possible.

3.13.7
If the enclosed staircase is windowless, mechanical ventilation shall be installed.
If the vestibule is windowless, mechanical ventilation shall also be installed. In addition
to ventilation a positive pressure of 50 Pa shall be maintained in the vestibule. This
positive pressure must be developed within 30 seconds of the incident of fire. When the
staircase and the vestibule are windowless emergency illumination shall be provided.
3.14
Number of Exits
3.14.1
The number of exits shall be determined as per provisions of Sec 3.6, Tables
4.3.1, 4.3.2 and 4.3.8 of this Chapter and complying with maximum dead end passage or
corridors and maximum travel distance.

3.14.2
Total required widths of exits shall be calculated as per provisions of the Tables

#### 4.3.2 and 4.3.8 shall be divided and distributed at a distance not less than one-third of

diagonal distance of space and the travel distance and the width of each exit shall comply
with the provisions of this Code. The required number of exits in a space as specified
below:
Occupant load less than 50
Minimum 1 exit
Occupant load 50 to 500
Minimum 2 exits
Occupant load 501 to 1000
Minimum 3 exits
Occupant load more than 1000
Minimum 4 exits
3.14.3
High rise buildings having a floor area larger than 500 m2 on each floor used as
educational, institutional, assembly, industrial, storage or a mixed occupancy involving
any of these or hazardous occupancy, shall have a minimum of two staircases. These
staircases shall comply with the requirements as specified in Sec 3.13 of this Chapter.
3.14.4
Where two accessible means of egress are required, the exits serving such means
of egress shall be located at a distance from one another not less than one-half the length
of the maximum overall diagonal dimension of the building or area to be served.
3.15
Travel Path
3.15.1
Travel path shall be measured along the center line of a natural and unobstructed
path up to center of an exit access door opening. In case of a stairway exist in the travel
path shall be measured along an inclined straight line through the center of outer edge of
each tread of a stairway.
3.15.2
Occupant load and components of exits shall be arranged in such a manner that
the travel path from any point in the area served shall not be exceeded as listed in the
Table 4.3.8.
3.15.3
Unit width shall be 560 mm and fraction of unit width less than 280 mm shall
not be credited. Where calculation of total required width give fractional result, next
larger integral number of exit units or integral number plus one-half shall be used. Where
changes in elevation exist, one-half or less unit of width shall not be permitted.
3.15.4
Capacity of exits shall be measured in unit of width of 560 mm and the number
of occupants per unit width shall be determined by the occupancy group and type of exits
as listed in Table 4.3.8.

3.15.5
Wherever more than one exit required in a room or in any floor they shall be
placed as remote as possible from each other. As far as practicable, exits shall be
arranged in such a manner to provide a refuge area or an exit discharge to the occupants
irrespective of the direction of travel from any point in an area served.
3.16
Means of Exit Signs and Illumination
3.16.1
All required means of exit or exit access in buildings or areas requiring more
than one exit shall be signposted. The signs shall be clearly visible at all times, where
necessary supplemented by directional signs. All exit doors shall be clearly marked for
easy identification.
Exceptions: Building Occupancy type A.

##### 3.16.1.1  Location: Exit signs shall be installed at stair enclosure doors, horizontal exits

and other required exits from the storey. When two or more exits are required from a
room or area, exit signs shall be installed to clearly indicate the direction of egress.
Exceptions:
(i)
Main exterior exit doors which obviously and clearly are identifiable as exits
need not be signed when approved by the Building Official.
(ii)
Exit signs are not required for buildings of occupancies A1, A2 and
individual units of A3.
(iii) No sign is needed for exits from rooms or areas with an occupant load of less
than 50 for Occupancy type C.
Table 4.3.8: Determination of Exit and Access Requirements.
Occupancy Group/
Classification

Maximum
Travel Path
(meter)
Capacity
Number of Occupancy per unit
width of the component
Ramp, Passage ,
Corridors
Unsprinklered
Full fire resistive  or
sprinklered
Door openings
Stairs, Escalators
Ramp, Corridors, Exit
passageways,
Horizontal exit
Minimum width
(mm)
Maximum Dead End
(mm)
To outdoors at
Grade
All other Exit and
corridor doors
A1, A2
Residential
N.R.
N.R.
N.R.
N.R.
N.R.
N.R.
N.R.
N.R.
A3,
A4,A5
B
Educational

| Occupancy Group/<br />Classification         | Col2                                         | Maximum<br />Travel Path<br />(meter) | Col4                                             | Capacity<br />Number of Occupancy per unit<br />width of the component | Col6                                           | Col7                                           | Col8                                                                     | Ramp, Passage ,<br />Corridors                 | Col10                                          |
| -------------------------------------------- | -------------------------------------------- | ------------------------------------- | ------------------------------------------------ | ---------------------------------------------------------------------- | ---------------------------------------------- | ---------------------------------------------- | ------------------------------------------------------------------------ | ---------------------------------------------- | ---------------------------------------------- |
| **Occupancy Group/**<br />**Classification** | **Occupancy Group/**<br />**Classification** | **Unsprinklered**                     | **Full fire resistive  or**<br />**sprinklered** | **Door openings**                                                      | **Door openings**                              | **Stairs, Escalators**                         | **Ramp, Corridors, Exit**<br />**passageways,**<br />**Horizontal exit** | **Minimum width**<br />**(mm)**                | **Maximum Dead End**<br />**(mm)**             |
| **Occupancy Group/**<br />**Classification** | **Occupancy Group/**<br />**Classification** | **Unsprinklered**                     | **Full fire resistive  or**<br />**sprinklered** | **To outdoors at**<br />**Grade**                                      | **All other Exit and**<br />**corridor doors** | **All other Exit and**<br />**corridor doors** | **All other Exit and**<br />**corridor doors**                           | **All other Exit and**<br />**corridor doors** | **All other Exit and**<br />**corridor doors** |
| A1, A2                                       | Residential                                  | N.R.                                  | N.R.                                             | N.R.                                                                   | N.R.                                           | N.R.                                           | N.R.                                                                     | N.R.                                           | N.R.                                           |
| A3,                                          | A3,                                          | 45                                    | 60                                               | 50                                                                     | 40                                             | 30                                             | 50                                                                       | 36                                             | 12190                                          |
| A4,A5                                        | A4,A5                                        | 45                                    | 60                                               | 50                                                                     | 40                                             | 30                                             | 50                                                                       | 36                                             | 12190                                          |
| B                                            | Educational                                  | 45                                    | 60                                               | 100                                                                    | 80                                             | 60                                             | 100                                                                      | 915                                            | 12190                                          |

C1, C2
Institutional
C3, C4, C5
D
Health
E
Business
F
Mercantile
G1
Industrial
G2
H1
Storage
H2
I
Assembly
J
High Hazard
N.P.
Notes:
1\.
In Hazardous occupancy (occupancy J) Travel Path should be performance
based but shall not exceed 15240 mm.
2\.
N.P. =  Not permitted
3\.
N.R. = No requirement, (except as provided in Table 4.3.5b)

4.

Capacity of ramp shall be reduced by twenty five percent when slope is
steeper than 1 in 10.

5.

Corridors serving classroom area of an educational building. Other
corridors shall have a minimum width of 1120 mm.
6\.
Applies to corridors to patient area. Staff corridors shall have a minimum
width of 1120 mm.

##### 3.16.1.2  Graphics: The color and design of lettering, arrows and other symbols on exit

signs shall be in high contrast with their background as per NFPA 170. Words on the
signs shall be at least 150 mm high with a stroke of not less than 20 mm. For vernacular
alphabet and numeric height shall be at least 150 mm with stroke not less than 20 mm.

##### 3.16.1.3  Illumination: Signs shall be internally or externally illuminated by two electric

lamps or shall be of self-luminous type. When the luminance on the face of an exit sign is
from an external source, it shall have an intensity of not less than 53.8 lux from either
lamp. Internally illuminated signs shall provide equivalent luminance.

##### 3.16.1.4  Source of Power: Supply of power to one of the lamps for exit signs shall be

provided by the premises wiring system. Power to the other lamp shall be from an on-site
generator set which shall be installed in accordance with the provisions of this Code.

##### 3.16.1.5  Floor-level Exit Signs:  For floor-level exit signs additional approved low-level

exit signs which are externally or internally illuminated, or self-luminous, shall be
provided in all interior exit corridors serving guest rooms of hotels in Occupancy A5. The
bottom of the sign shall be 150 mm to 200 mm above the floor level. For exit doors, the

| C1, C2     | Institutional | 38 | 53  | 50  | 40 | 30 | 50  | 915  | 12190 |
| ---------- | ------------- | -- | --- | --- | -- | -- | --- | ---- | ----- |
| C3, C4, C5 | C3, C4, C5    | 38 | 53  | 30  | 30 | 15 | 30  | 2440 | 9150  |
| D          | Health        | 38 | 53  | 30  | 30 | 15 | 30  | 2440 | 9150  |
| E          | Business      | 60 | 90  | 100 | 80 | 60 | 100 | 1120 | 15240 |
| F          | Mercantile    | 45 | 60  | 100 | 80 | 60 | 100 | 915  | 15240 |
| G1         | Industrial    | 60 | 120 | 100 | 80 | 60 | 100 | 1120 | 15240 |
| G2         | G2            | 60 | 120 | 100 | 80 | 60 | 100 | 1120 | 15240 |
| H1         | Storage       | 30 | 53  | 75  | 60 | 45 | 75  | 915  | 15240 |
| H2         | H2            | 38 | 45  | 75  | 60 | 45 | 75  | 915  | 15240 |
| I          | Assembly      | 45 | 60  | 100 | 80 | 60 | 100 | 1675 | 9150  |
| J          | High Hazard   | 15 | 45  | 50  | 40 | 30 | 50  | 915  | N.P.  |

sign shall be on the door or adjacent to the door with the closest edge of the sign within
100 mm of the door frame.
3.16.2
Amusement Building Exit Marking: Approved exit direction marking and exit
signs shall be provided. Approved low-level exit signs and directional marking shall be
located not more than 200 mm above parallel the walking surface and at the exit path.
3.16.3
All exit signs shall be illuminated while in use at night, or during dark periods
within the area served, in accordance with the provisions of this Code.
3.16.4
The means of exit and exit access in buildings requiring more than one exit shall
be equipped with artificial lighting. The lighting facilities shall satisfy the provisions of
this Code.