# Appendices A-W

> Electrical, acoustics, lifts/escalators, water supply, drainage, and gas supply forms and design tables.

## Appendix A: Maximum Demand and Diversity

Some information on the determination of the maximum demand for an electrical installation are provided in this appendix. It also includes some notes on the application of allowances for diversity. It is impossible however, to specify the appropriate allowances for diversity for every type of installation since determination of such allowances calls for special knowledge and experience. The figures shown in Table A1 are therefore, intended to act as guideline. The current demand of a final circuit is determined by summing the current demands of all points of utilization and equipment in the circuit. Typical values to be used for this summation are given in Table A2. For blocks of residential dwellings, large hotels, and industrial and large commercial premises, allowances are to be assigned by a competent engineer.

The current demand of a circuit supplying a number of final circuits may be assessed by applying the allowances for diversity given in Table A1 to the total current demand of all the equipment supplied by that circuit. In the table, the allowances are appraised either as percentages of the current demand or, where followed by the letters f.l., as percentages of the rated full load current of the current using equipment. After the design currents for all the circuits have been determined, enabling the conductor sizes to be chosen, it is necessary to check that the limitation on voltage drop is met.

**Table A1: Allowances for Diversity**

| Purpose of final circuit fed from conductors or switchgear to which diversity applies | Individual household installations, including dwellings of a block                                                                  | Small shops, stores, offices and business premises                                                    | Small hotels, boarding houses, guest houses, etc.                                                     |
| ------------------------------------------------------------------------------------- | ----------------------------------------------------------------------------------------------------------------------------------- | ----------------------------------------------------------------------------------------------------- | ----------------------------------------------------------------------------------------------------- |
| 1. Lighting                                                                           | 66% of total current demand                                                                                                         | 90% of total current demand                                                                           | 75% of total current demand                                                                           |
| 2. Cooking appliances                                                                 | 10 amperes + 30% f.l. of connected cooking appliances in excess of 10 amperes + 5 amperes if socket outlet is incorporated in unit. | 100% f.l. of largest appliance + 80% f.l. of 2nd largest appliance + 60% f.l. of remaining appliances | 100% f.l. of largest appliance + 80% f.l. of 2nd largest appliance + 60% f.l. of remaining appliances |
| 3. Motors (other than lift motors which are subject to special consideration)         | —                                                                                                                                   | 100% f.l. of largest motor + 80% f.l. of 2nd largest motor + 60% f.l. of remaining motors             | 100% f.l. of largest motor + 50% f.l. of remaining motors.                                            |
| 4. Water heater (thermostatically controlled)                                         | No diversity allowable                                                                                                              | No diversity allowable                                                                                | No diversity allowable                                                                                |

**Table A2: Current Demand to be Assumed for Points of Utilization and Current using Equipment**

| Point of Utilization or Current-using Equipment | Current Demand to be Assumed                                                                                                                     |
| ----------------------------------------------- | ------------------------------------------------------------------------------------------------------------------------------------------------ |
| Socket outlets other than 5A socket outlets     | Rated current                                                                                                                                    |
| 5A socket outlets                               | At least 0.5A                                                                                                                                    |
| Lighting outlet                                 | Current equivalent to the connected load, with a minimum of 100W per lamp holder                                                                 |
| House hold cooking appliance                    | The first 10A of the rated current plus 30% of the remainder of the rated current plus 5A if a socket outlet is incorporated in the control unit |
| All other stationary equipment                  | Standard rated current or nominal current.                                                                                                       |

## Appendix B: Useful Tables Relating to Conductor Sizes

**Table B1: Number of Single-core Wire of Different Sizes for Various Sizes of Metal Conduits**

| Conductor Cross-sectional Area (mm²) | 19 mm | 25.4 mm | 31.8 mm | 38 mm | 51 mm | 63.5 mm |
| ------------------------------------ | ----- | ------- | ------- | ----- | ----- | ------- |
| 1.5                                  | 5     | 10      | 14      | -     | -     | -       |
| 2.5                                  | 5     | 8       | 12      | -     | -     | -       |
| 4.0                                  | 3     | 6       | 10      | -     | -     | -       |
| 6.0                                  | 2     | 5       | 8       | -     | -     | -       |
| 10.0                                 | -     | 3       | 5       | 6     | -     | -       |
| 16.0                                 | -     | -       | 3       | 6     | -     | -       |
| 25.0                                 | -     | -       | 2       | 4     | 6     | 7       |
| 35.0                                 | -     | -       | -       | 3     | 5     | 6       |
| 50.0                                 | -     | -       | -       | -     | 4     | 5       |

*Values are number of wires that can be drawn through the conduit diameter shown.*

**Table B2: Number of Single-core Wires of Different Sizes for Various Sizes of PVC Conduits**

| Conductor Cross-sectional Area (mm²) | 19 mm | 25 mm | 32 mm | 38 mm | 51 mm |
| ------------------------------------ | ----- | ----- | ----- | ----- | ----- |
| 1.5                                  | 6     | 10    | 14    | -     | -     |
| 2.5                                  | 5     | 10    | 14    | -     | -     |
| 4.0                                  | 3     | 6     | 10    | 14    | -     |
| 6.0                                  | 2     | 5     | 8     | 11    | -     |
| 10.0                                 | -     | 4     | 7     | 9     | -     |
| 16.0                                 | -     | 2     | 4     | 5     | 12    |
| 25.0                                 | -     | -     | 2     | 2     | 6     |
| 35.0                                 | -     | -     | 2     | 2     | 5     |
| 50.0                                 | -     | -     | -     | 2     | 3     |

*Values are number of wires that can be drawn through the conduit diameter shown.*

**Table B3: Wire Gauges**

| AWG | SWG | Diameter (mm) | Cross-sectional Area (mm²) | Weight of Copper (kg/km) | Weight of Aluminium (kg/km) |
| --- | --- | ------------- | -------------------------- | ------------------------ | --------------------------- |
| 6/0 | -   | 14.73         | 170.46                     | 1515.4                   | 460.4                       |
| 5/0 | -   | 13.11         | 134.92                     | 1199.4                   | 365.0                       |
| -   | 7/0 | 12.70         | 126.68                     | 1126.2                   | 342.1                       |
| -   | 6/0 | 11.79         | 109.09                     | 969.8                    | 294.6                       |
| 4/0 | -   | 11.68         | 107.22                     | 953.2                    | 289.4                       |
| -   | 5/0 | 10.97         | 94.56                      | 840.7                    | 255.4                       |
| 3/0 | -   | 10.41         | 85.16                      | 757.2                    | 229.6                       |
| -   | 4/0 | 10.16         | 81.70                      | 720.7                    | 219.6                       |
| -   | 3/0 | 9.449         | 70.12                      | 623.4                    | 189.4                       |
| 2/0 | -   | 9.271         | 67.51                      | 600.1                    | 182.1                       |
| -   | 2/0 | 8.839         | 61.36                      | 545.5                    | 165.7                       |
| 0   | -   | 8.255         | 53.52                      | 475.8                    | 144.4                       |
| -   | 0   | 8.230         | 53.19                      | 472.9                    | 143.6                       |
| -   | 1   | 7.620         | 45.60                      | 405.4                    | 123.1                       |
| 1   | -   | 7.341         | 42.22                      | 376.2                    | 114.5                       |
| -   | 2   | 7.010         | 38.60                      | 343.1                    | 104.2                       |
| 2   | -   | 6.553         | 33.94                      | 299.8                    | 90.80                       |
| -   | 3   | 6.401         | 32.18                      | 286.1                    | 86.89                       |
| -   | 4   | 5.893         | 27.27                      | 242.5                    | 73.63                       |
| 3   | -   | 5.817         | 26.57                      | 236.2                    | 72.01                       |
| -   | 5   | 5.385         | 22.77                      | 202.5                    | 61.51                       |

**Table B3 (Contd.): Wire Gauges**

| AWG | SWG | Diameter (mm) | Cross-sectional Area (mm²) | Weight of Copper (kg/km) | Weight of Aluminium (kg/km) |
| --- | --- | ------------- | -------------------------- | ------------------------ | --------------------------- |
| 4   | -   | 5.182         | 21.09                      | 187.5                    | 57.11                       |
| -   | 6   | 4.877         | 18.68                      | 166.1                    | 50.44                       |
| 5   | -   | 4.623         | 16.78                      | 149.2                    | 45.25                       |
| -   | 7   | 4.470         | 15.70                      | 139.5                    | 42.39                       |
| 6   | -   | 4.115         | 13.30                      | 118.2                    | 35.91                       |
| -   | 8   | 4.065         | 12.97                      | 115.3                    | 35.02                       |
| 7   | 9   | 3.658         | 10.507                     | 93.41                    | 28.49                       |
| 8   | 10  | 3.251         | 8.302                      | 73.80                    | 22.59                       |
| -   | 11  | 2.948         | 6.818                      | 60.61                    | 18.41                       |
| 9   | -   | 2.896         | 6.585                      | 58.54                    | 17.91                       |
| -   | 12  | 2.642         | 5.480                      | 48.72                    | 14.80                       |
| 10  | -   | 2.591         | 5.272                      | 46.87                    | 14.21                       |
| -   | 13  | 2.337         | 4.284                      | 38.08                    | 11.58                       |
| 11  | -   | 2.311         | 4.196                      | 37.30                    | 11.26                       |
| 12  | -   | 2.057         | 3.325                      | 29.55                    | 8.934                       |
| -   | 14  | 2.032         | 3.243                      | 28.83                    | 8.756                       |
| 13  | 15  | 1.828         | 2.627                      | 23.35                    | 7.093                       |
| 14  | 16  | 1.626         | 2.075                      | 18.45                    | 5.621                       |
| 15  | -   | 1.448         | 1.646                      | 14.64                    | 4.460                       |
| -   | 17  | 1.422         | 1.589                      | 14.13                    | 4.290                       |
| 16  | -   | 1.295         | 1.318                      | 11.72                    | 3.532                       |
| -   | 18  | 1.291         | 1.168                      | 10.38                    | 3.154                       |
| 17  | -   | 1.143         | 1.026                      | 9.122                    | 2.808                       |
| 18  | 19  | 1.016         | 0.8107                     | 7.207                    | 2.223                       |
| 19  | 20  | 0.9144        | 0.6567                     | 5.838                    | 1.773                       |
| 20  | 21  | 0.8128        | 0.5189                     | 4.613                    | 1.401                       |
| 21  | -   | 0.7239        | 0.4156                     | 3.695                    | 1.111                       |
| -   | 22  | 0.7112        | 0.3973                     | 3.532                    | 1.073                       |
| 22  | -   | 0.6428        | 0.3243                     | 2.883                    | 0.8756                      |
| -   | 23  | 0.6096        | 0.2919                     | 2.595                    | 0.7881                      |
| 23  | -   | 0.5733        | 0.2588                     | 2.301                    | 0.6990                      |
| -   | 24  | 0.5588        | 0.2453                     | 2.181                    | 0.6620                      |
| 24  | -   | 0.5105        | 0.2047                     | 1.820                    | 0.5527                      |
| -   | 25  | 0.5086        | 0.2021                     | 1.797                    | 0.5473                      |

## Appendix C: Completion Certificate Form (Electrical Works)

I/we certify that the installation detailed below has been installed by me/us and tested and that to the best of my/our knowledge and belief, it complies with the requirements of Bangladesh National Building Code and the Electricity Act of Bangladesh (as modified up to 1987).

**Header fields:** Electrical Installation at \_\_\_\_\_\_; Voltage and system of supply \_\_\_\_\_\_

**Particulars of Works:**

a) Internal Electrical Installation — for each item below, the form provides columns for No., Total load, and Type or system of wiring:
i) Light point
ii) Fan point
iii) Plug point — 3-pin 5 A; 3-pin 15 A

b) Others — for each item below, the form provides columns for Description, hp/kW, and Type of starting:

1. Motors: i), ii), iii)
2. Other plants

c) If the work involves installations of overhead line and/or underground cable:

1. i) Type and description of overhead line; ii) Total length and number of spans; iii) Number of street lights and its description
2. i) Total length and size of underground cable; ii) Number of joints — End joint, Tee joint, Straight through joint

d) Earthing:
i) Description of earthing electrode
ii) Number of earth electrodes
iii) Size of main earth lead

**Test Results:**

a) Insulation Resistance
i) Insulation resistance of the whole system of conductors to earth \_\_\_\_\_\_ mega ohms
ii) Insulation resistance between the phase conductor and neutral — Between phase R and neutral \_\_\_\_\_\_ mega ohms; Between phase Y and neutral \_\_\_\_\_\_ mega ohms; Between phase B and neutral \_\_\_\_\_\_ mega ohms
iii) Insulation resistance between the phase conductors in case of polyphase supply — Between phase R and phase Y \_\_\_\_\_\_ mega ohms; Between phase Y and phase B \_\_\_\_\_\_ mega ohms; Between phase B and phase R \_\_\_\_\_\_ mega ohms

b) Polarity test — Polarity of nonlinked single pole branch switches

c) Earth continuity test — Maximum resistance between any point in the earth continuity conductor including metal conduits and main earthing lead \_\_\_\_\_\_ ohms

d) Earth electrode resistance — Resistance of each earth electrode: i) \_\_\_\_\_\_ ohms; ii) \_\_\_\_\_\_ ohms; iii) \_\_\_\_\_\_ ohms; iv) \_\_\_\_\_\_ ohms

e) Lightning protective system — Resistance of the whole of lightning protective system to earth before any bonding is effected with earth electrode and metal in/on the structure \_\_\_\_\_\_ ohms.

**Signatures:** Signature of Supervisor, Name and Address \_\_\_\_\_\_ — Signature of Contractor, Name and Address \_\_\_\_\_\_

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-c-completion-certificate-electrical.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=c26906495a1ea36dde2d463868df7b92" alt="Appendix C: Completion Certificate Form (Electrical Works)" width="858" height="1189" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-c-completion-certificate-electrical.png" />
</Frame>

## Appendix D: Relationship of Weighting Curves for Sound Levels

The standardized weighting curves for sound level meters together with the more recent E and SI curves are shown in the figure below.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-d-weighting-curves.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=232dcca15222a94ba21cbfe727a84f0b" alt="Fig. D1: Relationship of Weighting Curve for Sound Levels" width="1698" height="700" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-d-weighting-curves.png" />
</Frame>

Fig. D1: Relationship of Weighting Curve for Sound Levels — chart plots Relative Response (dB) from -70 to +20 against Frequency (Hz) from 10 to 2×10⁴, showing curves labelled A, B, C, D, E, SI, and (B+C).

## Appendix E: Recommended Optimum Reverberation Time for Assembly Buildings

The recommended optimum reverberation times for various uses of Assembly buildings are given in the figure below.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-e-reverberation-time.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=cdfe536253932042d2556d44c110e8a7" alt="Fig. E1: Recommended Optimum Reverberation Time for Various Uses" width="1706" height="870" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-e-reverberation-time.png" />
</Frame>

Fig. E1: Recommended Optimum Reverberation Time for Various Uses — chart plots Reverberation Time (Seconds, at 125 Hz on the left axis and at 500-2000 Hz on the right axis) against Volume of Room (m³, from 10³ to 10⁵), with lines labelled Organ, Orchestra, Vocal Music, Opera, Chamber Music, Multi-purpose, Theatre, Cinema, and Speech.

## Appendix F: STC Ratings of Walls and Floors

STC ratings of some commonly used walls, floors and structural elements are given in the following Table.

**Walls**

| Walls                                                                              | STC |
| ---------------------------------------------------------------------------------- | --- |
| 100 mm brick with 13 mm plaster both side                                          | 40  |
| 114 mm brick with 13 mm plaster both side                                          | 42  |
| 230 mm brick with 13 mm plaster both side                                          | 52  |
| 305 mm brick                                                                       | 54  |
| 305 mm brick wall, both side plaster with 50 mm cavity                             | 54  |
| 460 mm brick wall, both side 13 mm plaster, 25 mm wood wall slab and 152 mm cavity | 62  |
| 610 mm stone wall, both side 13 mm plaster                                         | 56  |
| 150 mm concrete wall with 13 mm plaster both side                                  | 52  |

**Floors**

| Floors                                                                          | STC |
| ------------------------------------------------------------------------------- | --- |
| 100 mm concrete slab                                                            | 44  |
| 125 mm concrete slab with 32 mm cork and plywood subfloor                       | 48  |
| 150 mm concrete slab with 19 mm plaster on both side                            | 47  |
| 150 mm concrete slab with cork pad, wood floor and sleeper (total 235 mm thick) | 53  |

## Appendix G: Air Traffic Noise Levels

For traffic noise levels produced from the aircrafts, control measures shall be initiated from the investigation of the following characteristic features of aircraft noise:

a) i) Noise characteristics of different aircraft vary with different power conditions.
ii) Noise created by jet aircraft are different from those generated by propeller aircraft with piston engines.
iii) Jet noise originates from different parts of the engine, such as the jet, the compressor and the turbine.
iv) The typical roar of a flying jet is generated by the violent mixing of the hot exhaust gases with the surrounding air, particularly noticeable during take off and climb.

b) After take off the noise level on the ground shall not exceed certain maximum values, for each direction of each runway. These noise levels are higher during the day than at night.

c) An angle of 3° or less with the horizontal should be adopted for landing.

d) Very long corridor shall be left free of buildings for descending the aircraft before they reach the runway threshold. Airports with runways which continue over water (lake or sea) can follow the noise control requirements much more easily and with added safety.

Approximate noise levels due to various types of aircrafts, measured on ground (when the aircraft fly overhead at a height of 450 m) shows that boeing 707 records a maximum noise level of 111 PNdB, followed by Boeing 737 (107 PNdB), Boeing 747 (103 PNdB) and Airbus A 300 (101 PNdB).

The flyover noise level for Concorde SST at 450 m with take off thrust is recorded at 114 PNdB, the highest noise level among the commercial aircrafts.

## Appendix H: Frequency Values and Noise Levels of Some Common Sources

High frequency values have short wavelengths, and are heard as notes of high pitch. Conversely, low frequency sounds have a long wavelength, and are heard as notes of low pitch.

A healthy young person is capable of hearing sound from about 20 to 20,000 Hz. Prolonged exposure to intense sound can also cause permanent hearing damage. Short term exposure can cause temporarily losses.

Some typical frequencies are mentioned below (in round numbers):

| Source                   | Frequency    |
| ------------------------ | ------------ |
| Male voice, vowel sounds | 100 Hz       |
| Male voice, sibilants    | 3,000 Hz     |
| Bass singer, bottom note | 100 Hz       |
| Piano, bottom note       | 25 Hz        |
| Piano, middle C          | 260 Hz       |
| Piano, top note          | 4,200 Hz     |
| Piccolo, top note        | 4,600 Hz     |
| Orchestral range         | 45-4,500 Hz  |
| Audible range            | 20-20,000 Hz |

The following are examples of familiar sounds expressed in dB:

| Description                                                                                                                   | Subjective Evaluation | Decibels (dB) |
| ----------------------------------------------------------------------------------------------------------------------------- | --------------------- | ------------- |
| Near jet engine                                                                                                               | Deafening             | 140           |
| Threshold of pain                                                                                                             | Deafening             | 130           |
| Threshold of feeling hard rock band                                                                                           | Deafening             | 120           |
| Accelerating motorcycle at a few metre away (Note: 15 m from motorcycle equals noise at about 600 m from a 4-engine aircraft) | Very loud             | 110           |
| Full orchestra, loud passage                                                                                                  | Very loud             | 95            |
| Noisy urban street, noisy factory                                                                                             | Loud                  | 90            |
| School cafeteria                                                                                                              | Loud                  | 80            |
| Loud speech, 1 m distant; stenographic room                                                                                   | Moderate              | 70            |
| Near freeway auto traffic                                                                                                     | Moderate              | 60            |
| Conversational speech, 1 m distant; average office                                                                            | Faint                 | 50            |
| Attentive theatre audience, total sound. Soft radio music in apartment.                                                       | Faint                 | 40            |
| Faint whisper, 1 m distant; average residence without stereo playing                                                          | Very faint            | 30            |
| Average whisper                                                                                                               | Very faint            | 20            |
| Rustle of one program, 8 m distant                                                                                            | Very faint            | 15            |
| Rustle of leaves in wind; human breathing                                                                                     | Very faint            | 10            |
| Threshold of audibility                                                                                                       | Very faint            | 0             |

## Appendix I: Typical Noise Levels in Free-Flowing Road Traffic

Typical noise levels in free-flowing road traffic are given in the following table.

| No. of Vehicles (per 18 hour day)   | Speed   | L₁₀, 30 m from Road Edge dBA |
| ----------------------------------- | ------- | ---------------------------- |
| 5000 (10 per cent heavy vehicles)   | 50 km/h | 65                           |
| 10,000 (20 per cent heavy vehicles) | 60 km/h | 70                           |
| 10,000 (40 per cent heavy vehicles) | 80 km/h | 75                           |
| 20,000 (40 per cent heavy vehicles) | 80 km/h | 77                           |

Note: The values are applicable to free-flowing traffic without honking.

## Appendix J: Average Air-borne Sound Insulation of Common Constructions

Table J1 below indicates the airborne sound insulation, averaged over the frequency range 100 to 3150 Hz, of a number of common types of constructions. These single figure values must be taken only as a guide because insulation effectiveness depends on how the insulation varies with frequency and because differences in building construction affect the values actually obtained. It must also be remembered that the insulation achieved in practice depends not only on the insulation of the particular dividing element but also on its area in relation to the sound absorption in the rooms, and on indirect transmission. No specific allowance can be made for indirect transmission. However for elements having an insulation of 40 dB or below it will have little effect. In Table J1 the figures above 40 dB allow for the amount of indirect transmission likely to be present when the structures are used in a more or less traditional manner.

As to the effects of area and absorption, the values given have been chosen to represent as nearly as possible the achieved insulation between two normally furnished rooms of average proportions when the whole area of the wall or floor is of the specified construction. As a result of these considerations, and owing to variations in detailing and quality of workmanship, it is important to bear in mind that the figures in Table J1 are subject to wide tolerance and must be treated as estimates.

**Table J1: Average Airborne Sound Insulation of Windows, Walls, Floors etc.**

*Windows*

| Construction                                                                                                                     | Insulation (dB) |
| -------------------------------------------------------------------------------------------------------------------------------- | --------------- |
| Open window                                                                                                                      | 5-10            |
| 3 or 4 mm glass, not well sealed                                                                                                 | 15-20           |
| 3 or 4 mm glass, well sealed                                                                                                     | 23              |
| 6 mm glass, well sealed                                                                                                          | 27              |
| 4 mm glass – 200 mm gap – 4 mm glass, but each leaf partially opened (up to 100 mm opening), with openings staggered 1.5 m apart | 27              |
| 6 mm glass – 12 mm gap – 6 mm glass well sealed                                                                                  | 28              |
| 12 mm glass, well sealed                                                                                                         | 31              |
| 6 mm glass – 150 mm gap – 4 mm glass well sealed, lined reveals                                                                  | 35              |
| 12 mm glass laminated, well sealed                                                                                               | 36              |
| 4 mm glass – 200 mm gap – 4 mm glass, but not well sealed                                                                        | 36              |
| 10 mm glass – 80 mm gap – 6 mm glass well sealed, lined reveals                                                                  | 37              |
| 4 mm glass – 200 mm gap – 4 mm glass well sealed, lined reveals                                                                  | 39              |
| 10 mm glass – 200 mm gap – 6 mm glass well sealed, lined reveals                                                                 | 44              |

*Masonry walls*

| Construction                                                                                         | Insulation (dB) |
| ---------------------------------------------------------------------------------------------------- | --------------- |
| Lightweight block work, not sealed                                                                   | \< 35           |
| 63 mm hollow clay block plastered on each side to 12 mm                                              | 35              |
| 57 mm lightweight (100 kg/m²) block work, plastered both sides to 12 mm                              | 39              |
| 50 mm precast concrete units, well grouted joints                                                    | 40              |
| 200 mm lightweight concrete precast slabs (122 kg/m²) with well grouted joints                       | 40              |
| 100 mm solid brickwork, unplastered                                                                  | 42              |
| 100 mm solid brickwork, plastered                                                                    | 45              |
| 110 mm dense concrete, well sealed                                                                   | 45              |
| 150 mm dense concrete, well sealed                                                                   | 47              |
| 230 mm solid brick, unplastered                                                                      | 48              |
| 250 mm no fines concrete (1:10) plastered both sides to 12 mm                                        | 49              |
| Block work (110 kg/m²) 75 mm airspace – block work (110 kg/m²)                                       | 49              |
| 200 mm dense concrete blocks with cement-lime mortar plastered both sides to 12 mm                   | 50              |
| 230 mm solid brick work plastered or with dry lining of 12 mm plaster board on plaster dabs          | 50              |
| 250 mm cavity construction, i.e. 110 mm brick–cavity–5 mm block + 12 mm plaster, butterfly wire ties | 50              |
| 280 mm cavity brick work, butterfly wire ties, plastered one side to 12 mm                           | 52              |
| 340 mm brick work, plastered both sides to 12 mm                                                     | 53              |
| 450 mm brick or stone well pointed or plastered                                                      | 55              |

Note: These estimates refer to insulation of walls between rooms. For insulation between a room and a noise in the open air the overall insulation should be reduced by 5 dB.

**Table J1 (Contd.): Average Airborne Sound Insulation of Windows, Walls, Floors etc.**

*Floors*

| Construction                                                                                                             | Insulation (dB) |
| ------------------------------------------------------------------------------------------------------------------------ | --------------- |
| 21 mm t-and g-boards or 19 mm chipboard on floor joists, 9 mm plaster board + skim coat below                            | 35              |
| 110 mm concrete + screed (≤ 220 kg/m²)                                                                                   | 42              |
| 21 mm t-and g-boards or 19 mm chipboard on floor joists, lath and plaster (20 mm) below with 50 mm layer of sand pugging | 45-46           |
| 125 mm reinforced concrete + 50 mm screed                                                                                | 45-46           |
| 200 mm reinforced concrete + 50 mm screed                                                                                | 47-48           |
| 125 mm reinforced concrete + timber raft (i.e. 21 mm t-and-g boards or 19 mm chipboard) on glass- or mineral-fibre quilt | 47-48           |
| Precast concrete units (50 mm) + 30 mm finishing screed on deep truss with well sealed 9 mm insulation board below       | 47-48           |
| 125 mm reinforced concrete + 40-50 mm concrete screed on glass or mineral-fibre quilt                                    | 49-50           |
| 300 mm reinforced concrete + 50 mm screed                                                                                | 49-50           |
| Floated timber raft (21 mm t-and g-boards or 19 mm chipboard) on glass or mineral-fibre quilt on joists                  | 49-50           |
| 50 mm sand directly on ceiling of plaster on metal lath (20 mm)                                                          | 49-50           |
| 150 mm reinforced concrete + 100 mm floated raft on specialist mounts, free from 'bridging'                              | 55              |
| As above, with walls built near the edge of the floor to limit flanking transmission                                     | 60+             |

*Dry partitions*

| Construction                                                                                                                                                              | Insulation (dB) |
| ------------------------------------------------------------------------------------------------------------------------------------------------------------------------- | --------------- |
| 21 mm t-and g-boarding, tightly clamped                                                                                                                                   | 20              |
| 9 mm insulation board each side of 75 x 50 mm studs                                                                                                                       | 23              |
| 12 mm plaster board + skim coat on timber frame                                                                                                                           | 25              |
| 12 mm plaster board both sides of honeycomb core – 63 mm total thickness                                                                                                  | 28              |
| 6 mm ply/hard board on 50 mm timber studs, mineral-fibre quilt in cavity                                                                                                  | 30              |
| 12 mm plaster board each side of 50 mm timber studs                                                                                                                       | 30              |
| 1 mm steel panels spaced apart by 50 mm with mineral-fibre quilt fill                                                                                                     | 30              |
| 12 mm plaster board each side of 50 mm metal studs                                                                                                                        | 33              |
| 50 mm wood-wool plastered both sides to 12 mm                                                                                                                             | 35              |
| 12 mm plaster board each side of 50 mm timber studs with absorbent quilt in cavity                                                                                        | 37              |
| As above, but with metal studs                                                                                                                                            | 39              |
| 2 x 12 mm plaster board each side of 50 mm timber studs with absorbent quilt in cavity                                                                                    | 41              |
| 1 mm steel panels backed with 9 mm plasterboard, with absorbent quilt in cavity                                                                                           | 41              |
| 2 x 12 mm plaster board each side of 75 mm metal studs with absorbent quilt in cavity                                                                                     | 45              |
| 3 layers 12 mm plaster board on timber frame each side of 225 mm air gap, frames separated and area of supported panels ≤ 15% glass or mineral-fibre quilt hung in cavity | 49              |

*Doors*

| Construction                                                                    | Insulation (dB) |
| ------------------------------------------------------------------------------- | --------------- |
| Panel/hollow core door well fitted, no seals                                    | 15              |
| As above with good seals and close cut threshold                                | 20              |
| Solid core door well fitted, no seals                                           | 15              |
| As above with good seals and threshold strip seal or close cut to carpet        | 25              |
| 60 mm + solid core door with carefully detailed seals, including threshold seal | 30              |

Note: Above 30 dB, specialist doors are needed.

*Room to room insulation via suspended ceiling void* (Assuming 600 mm deep void, below concrete soffit, no undue obstructions such as large ducts, downstand beams)

| Construction                                                               | Insulation (dB) |
| -------------------------------------------------------------------------- | --------------- |
| > 10% perforated metal pan ceiling with absorbent lay-in backing           | 15-20           |
| 19 mm mineral-fibre ceiling tile (6 kg/m²) in lay-in or concealed fix grid | 25-30           |
| Solid metal pan ceiling (0-6 mm)                                           | about 30        |
| + absorbent quilt overlay                                                  | about 35        |
| Perforated metal pan + 9 mm plasterboard backing                           | 35-40           |

## Appendix K: Recommended Background Noise Criteria and NC Curves

The NC levels to specify the desirable lowest limits are given in Table K1 and Fig K1.

**Table K1: Recommended Background Noise Criteria for Rooms**

| Type of Room                       | NC Number |
| ---------------------------------- | --------- |
| Concert hall                       | 15-20     |
| Radio or recording studio          | 15-20     |
| Opera house                        | 20        |
| Theatre                            | 20-25     |
| Music room                         | 20-25     |
| Television studio                  | 20-25     |
| Executive office                   | 20-30     |
| Classroom or lecture hall          | 25        |
| Cinema studio                      | 25        |
| Conference room                    | 25-30     |
| Church                             | 25-30     |
| Courtroom                          | 25-30     |
| Assembly hall or school auditorium | 25-35     |
| Home (sleeping areas)              | 25-35     |
| Hotel or motel                     | 25-35     |
| Motion picture/Cinema hall         | 30        |
| Hospital                           | 30        |
| Semiprivate office                 | 30-35     |
| Library                            | 30-35     |
| Business office                    | 35-45     |
| Restaurant                         | 35-50     |
| Drafting room                      | 40-45     |
| Gymnasium                          | 45-50     |
| Typing or accounting office        | 45-60     |
| Coliseum                           | 50        |

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-k-nc-curves.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=8753696cbe39840e5bf95561bd69bcf3" alt="Fig. K1: Noise-Criterion Curves (NC)" width="1731" height="1550" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-k-nc-curves.png" />
</Frame>

Fig. K1: Noise-Criterion Curves (NC) — chart plots Sound Pressure Level (dB), 0 to 80+, against Frequency (Hz), 63 to 4K (with the corresponding Frequency Band ranges 20-75 through 4800-9600 Hz shown along the top axis), with curves labelled NC-20 through NC-70 (in steps of 10) and a dashed "Threshold of Audibility" curve.

## Appendix L: Particulars of Lifts, Escalators and Moving Walks

**LIFT** — particulars required:

a) Number of lifts and capacity of each lift;
b) Layout of lift well with sizes;
c) Particulars of lift well enclosures;
d) Size, position, number and type of landing doors;
e) Number of floors served by the lift;
f) Height between floor levels;
g) Provision of ventilation of lift well;
h) Total headroom clearance;
i) Location of machine room (above or below lift well), height of machine room;
j) Provision of access to machine room;
k) Provision of ventilation and, if possible, natural lighting of machine room;
l) Depth of lift pit;
m) Size and position of supporting steel work at roof levels;
n) Size and position of any footings or grillage foundations, if these are adjacent to lift pit; and
o) In the case of passenger lifts, whether the lift cage is required to carry heavy household luggage, such as refrigerator, steel almirah, etc.

**ESCALATOR** — particulars required:

a) Number of escalators and capacity of each escalator;
b) Layout of escalators with dimensions of floor punches; and
c) Height between floors.

**MOVING WALK** — particulars required:

a) Number of moving walks and capacity of each moving walk;
b) Layout of moving walks with dimensions; and
c) Length and width of each unit.

## Appendix M: Format for Particulars of Lifts, Escalators and Moving Walks

This appendix is a fillable form for submitting the detailed particulars listed in Appendix L. The fields are as follows.

**LIFTS**

a) Use: Passenger/Goods/Services/Hospital
b) Number of lifts required: \_\_\_\_\_\_
c) Capacity per lift: Number of passengers \_\_\_\_\_\_ kg \_\_\_\_\_\_
d) Rated Speed: \_\_\_\_\_\_ m/s
e) Travel height: \_\_\_\_\_\_ m
f) Size and type of car doors: \_\_\_\_\_\_
g) Size and type of landing doors: \_\_\_\_\_\_
h) Size(s) and location(s) of lift well(s): \_\_\_\_\_\_
i) Number of doors: \_\_\_\_\_\_
j) Method of control(s): \_\_\_\_\_\_
k) Location of machine room: \_\_\_\_\_\_
l) Position of counter weight: \_\_\_\_\_\_
m) Size of car platform: \_\_\_\_\_\_
n) Construction, design and finish of car bodywork: \_\_\_\_\_\_
o) Construction, design and finish of car platform: \_\_\_\_\_\_
p) Particulars of ventilation of the car: \_\_\_\_\_\_
q) Particulars of control buttons in car: \_\_\_\_\_\_
r) Particulars of position indicators in car: \_\_\_\_\_\_
s) Particulars of call buttons in landing: \_\_\_\_\_\_
t) Particulars of car position indicators in landings: \_\_\_\_\_\_
u) Electric supply: Power: \_\_\_\_\_\_ volts, ac/dc, \_\_\_\_\_\_ phase, \_\_\_\_\_\_ Hz/wire system \_\_\_\_\_\_; Lighting: \_\_\_\_\_\_ Volts, ac/dc, \_\_\_\_\_\_ Hz/sec
v) Additional requirements, if any: \_\_\_\_\_\_

**ESCALATOR**

a) Number of escalators required: \_\_\_\_\_\_
b) Capacity of each escalator (No. of people/hr): \_\_\_\_\_\_
c) Rated speed \_\_\_\_\_\_ m/s
d) Travel height \_\_\_\_\_\_ m, Travel length \_\_\_\_\_\_ m
e) Width of escalator \_\_\_\_\_\_ m
f) Construction, design and finish of balustrade: \_\_\_\_\_\_
g) Details of steps: \_\_\_\_\_\_
h) Materials of landing plate: \_\_\_\_\_\_
i) Electric supply: Power: \_\_\_\_\_\_ volts, ac/dc, \_\_\_\_\_\_ phase \_\_\_\_\_\_ Hz/wire system \_\_\_\_\_\_
j) Additional requirements, if any: \_\_\_\_\_\_

**MOVING WALK**

a) Number of moving walks required: \_\_\_\_\_\_
b) Capacity of each moving walk (No. of people/hr): \_\_\_\_\_\_
c) Rated speed \_\_\_\_\_\_ m/s
d) Inclination \_\_\_\_\_\_ degrees
e) Width of moving walk \_\_\_\_\_\_ m
f) Construction, design and finish of balustrade: \_\_\_\_\_\_
g) Material of landing plate: \_\_\_\_\_\_
h) Electric supply: Power: \_\_\_\_\_\_ volts, ac/dc, \_\_\_\_\_\_ phase \_\_\_\_\_\_ Hz/wire system \_\_\_\_\_\_
i) Additional requirements, if any: \_\_\_\_\_\_

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-m-lifts-escalators-form.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=38103bc9fff6648fa41619fbfcd55f93" alt="Appendix M: Format for Particulars of Lifts, Escalators and Moving Walks (form, page 1)" width="865" height="1197" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-m-lifts-escalators-form.png" />
</Frame>

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-m-moving-walk-cont.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=462bc4e64950628050f37fd6511bcc1f" alt="Appendix M: Format for Particulars of Lifts, Escalators and Moving Walks (form, page 2 — escalator electric supply/additional requirements and moving walk fields)" width="857" height="1192" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-m-moving-walk-cont.png" />
</Frame>

## Appendix N: Application for Permit to Construct Water Supply and Distribution System

1. Building Location: \_\_\_\_\_
2. Occupancy Classification: \_\_\_\_\_
3. Number of Storeys: \_\_\_\_\_
4. Height of the Building: \_\_\_\_\_
5. This application is accompanied by all required plans, drawing and design calculations (if required) in accordance with Sec 6.3.2 and 6.3.3 of Bangladesh National Building Code.

Signature of the licensed plumber — Name and Address: \_\_\_\_\_

Signature of the Owner or his/her designated person/agent — Name and Address: \_\_\_\_\_

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-n-water-supply-permit.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=169b12a0142e7c9f1cbec5d2f6064e13" width="874" height="1204" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-n-water-supply-permit.png" />
</Frame>

## Appendix P: Sizing of Cold Water Supply and Distribution Piping

The water distribution within the building may be an upfeed or downfeed system. The design principles are the same for both systems. The principal difference in the calculation procedure is that in the upfeed system, the difference in elevation between the fixtures and the water main exerts the pressure that supplies water into the fixtures, but in the downfeed system the difference in elevation between the fixtures and the roof storage tank provides the pressure to overcome the pipe friction. The following are the recommended pipe sizing procedures:

P1 The sketch of the main lines, risers and branches serving different fixtures will have to be drawn.

P2 Determine the number and types of fixture that will be required on the basis of the Table 8.7.1 in Chapter 7.

P3 The demand weight of different fixture units may be computed in terms of water supply fixture unit (wsfu) in accordance with Table P 1.

P4 The peak demand load (or maximum probable flow) in litre per minute may be estimated with the data obtained in P3 using Fig P 1 or on the basis of the number of occupants according to their occupancy classification specified in Table 8.6.1.

P5 The equivalent length of the main lines, risers and branches will be determined. The equivalent length of different fittings may be estimated on the basis of the data presented in the Table P 2 and Fig P 2 or from manufacturer's specification. The total equivalent length is the sum of the equivalent lengths of all pipes and fittings.

P6 The pressure loss through water meter may be determined on the basis of their operating characteristics as shown in Fig P 3 (Disk type water meter). The data for other types of water meter may be obtained from the manufacturer.

P7 The minimum pressure required at different fixtures to produce adequate flow may be estimated on the basis of the type of fixtures or minimum size of supply pipe in accordance with Table 8.6.4.

P8 The average pressure drop in kPa per metre of equivalent pipe length may be computed as follows:

$$
F_p = \left(P \pm^{\!*} 9.807H - f\right)/L
$$

where

| Symbol | Meaning                                                                                                                                                                                                                |
| ------ | ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| $F_p$  | Average available pressure loss (kPa) per metre of equivalent length of pipe                                                                                                                                           |
| $P$    | Pressure (kPa) in the water main or zero for over head gravity storage tank.                                                                                                                                           |
| $H$    | Height (m) of the highest fixture above the water main or difference in elevation between storage tank and the fixture under consideration.                                                                            |
| $f$    | Pressure loss (kPa) through water meter or such other fittings plus pressure required to produce adequate flow through the most remote fixture in upfeed system or the fixture under consideration in downfeed system. |
| $L$    | Equivalent pipe length (m)                                                                                                                                                                                             |

\* + sign is for downfeed system and − sign is for upfeed system

P9 The pipe size may be estimated from Fig P 4 to P 7 for different types of piping materials on the basis of the expected rate of flow determined in P4 and the average pressure available for friction loss (Fp) in P7.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-sizing-cold-water-piping.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=b74b5475a3c6d867d2ca9e3f2618acb6" width="856" height="1189" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-sizing-cold-water-piping.png" />
</Frame>

### Table P 1: Water Supply Fixture Unit (wsfu) Values for Various Plumbing Fixtures

| Fixture or group     | Supply Control | wsfu — Cold | wsfu — Hot | wsfu — Total |
| -------------------- | -------------- | ----------- | ---------- | ------------ |
| Bath group           | Flush tank     | 4.5         | 3          | 6            |
| Bath group           | Flush valve    | 6           | 3          | 8            |
| Bathtub              | Faucet         | 1.5         | 1.5        | 2            |
| Bidet                | Faucet         | 1.5         | 1.5        | 2            |
| Combination          | Faucet         | 2           | 2          | 3            |
| Kitchen sink         | Faucet         | 1.5         | 1.5        | 2            |
| Laundry tray         | Faucet         | 2           | 2          | 3            |
| Laundry              | Faucet         | 1.5         | 1.5        | 2            |
| Pedestal urinal      | Flush valve    | 10          | –          | 10           |
| Restaurant sink      | Faucet         | 3           | 3          | 4            |
| Service sink         | Faucet         | 1.5         | 1.5        | 2            |
| Shower head          | Mixing Valve   | 3           | 3          | 4            |
| Stall or wall urinal | Flush tank     | 3           | –          | 3            |
| Stall or wall urinal | Flush valve    | 5           | –          | 5            |
| Water closet         | Flush tank     | 5           | –          | 5            |
| Water closet         | Flush valve    | 10          | –          | 10           |

\* Fixture with both cold and hot water supplies, the weight for maximum separate demands may be considered 75% of total wsfu.

### Table P 2: Equivalent Length of Pipe for Friction Loss in Valves and Fittings

Equivalent Length (m) of Pipes Against Diameter (mm) of Fittings

| Valves or Fittings    | 10   | 13   | 19   | 25   | 32    | 38    | 50    | 63    | 75    | 88    | 100   | 125   | 150   |
| --------------------- | ---- | ---- | ---- | ---- | ----- | ----- | ----- | ----- | ----- | ----- | ----- | ----- | ----- |
| Angle Valve           | 1.22 | 2.44 | 3.66 | 4.57 | 5.49  | 6.71  | 8.53  | 10.36 | 12.19 | 15.24 | 16.76 | 21.34 | 24.38 |
| Gate Valve            | 0.06 | 0.12 | 0.15 | 0.18 | 0.24  | 0.30  | 0.40  | 0.49  | 0.61  | 0.73  | 0.82  | 1.01  | 1.22  |
| Globe Valve           | 2.44 | 4.57 | 6.10 | 7.62 | 10.67 | 13.72 | 16.76 | 19.81 | 24.38 | 30.48 | 38.10 | 42.67 | 50.29 |
| 90° Standard Elbow    | 0.30 | 0.61 | 0.76 | 0.91 | 1.22  | 1.52  | 2.13  | 2.44  | 3.05  | 3.66  | 4.26  | 5.18  | 6.10  |
| 45° Standard Elbow    | 0.18 | 0.37 | 0.46 | 0.55 | 0.73  | 0.91  | 1.22  | 1.52  | 1.83  | 2.13  | 2.44  | 3.05  | 3.66  |
| 90° Side Tee Coupling | 0.46 | 0.91 | 1.22 | 1.52 | 1.83  | 2.13  | 3.05  | 3.66  | 4.57  | 5.49  | 6.40  | 7.62  | 9.14  |
| Straight Run of Tee   | 0.09 | 0.18 | 0.24 | 0.27 | 0.37  | 0.46  | 0.61  | 0.76  | 0.91  | 1.10  | 1.22  | 1.52  | 1.83  |

**Fig P 1 Water Supply Demand for Various Loads in Water Supply Fixture Units (wsfu)** — a chart plotting demand in litre per minute (0 to 1800, y-axis) against wsfu (0 to 3000, x-axis), showing two curves labeled "Flush Valve System" and "Flush Tank System" (the Flush Valve System curve reads consistently higher demand for the same wsfu).

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p1-water-supply-demand.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=085c66f9f225e8df62c8ac44da277562" alt="Fig P 1 Water Supply Demand for Various Loads in Water Supply Fixture Units (wsfu)" width="1626" height="1853" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p1-water-supply-demand.png" />
</Frame>

**Fig P 2 Friction Loss Through Taps and Tees** — a log-log chart of friction loss in kPa (y-axis, 0.1 to 1000) against flow in litre per minute (x-axis, 10 to 10000), with a family of parallel lines labeled by "Size of Tap or Tee (mm)": 16, 19, 25, 32, 38, 50, 75.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p2-friction-loss-taps-tees.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=923f9acfb21e9b8c3498e8a43eec624e" alt="Fig P 2 Friction Loss Through Taps and Tees" width="1612" height="1847" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p2-friction-loss-taps-tees.png" />
</Frame>

**Fig P 3 Loss of Pressure Through Disc-Type Meter in kPa** — a log-log chart of pressure loss in kPa (y-axis, 1 to 1000) against flow in litre per minute (x-axis, 10 to 10000), with a family of lines labeled by "Size of Meter (mm)": 13, 19, 25, 38, 50, 75, 100, 150.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p3-loss-pressure-disc-meter.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=62006d3226da855ff81b1c0b10426959" alt="Fig P 3 Loss of Pressure Through Disc-Type Meter in kPa" width="1630" height="1858" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p3-loss-pressure-disc-meter.png" />
</Frame>

**Fig P 4 Friction Loss in Fairly Rough Pipe** — a log-log chart of flow in litre per minute (y-axis, 1 to 100000) against friction loss in kPa per metre length (x-axis, 0.01 to 100), with a family of lines labeled by pipe "Diameter (mm)": 19, 25, 32, 38, 50, 63, 75, 100, 125, 150, 200, 250, 300.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p4-friction-loss-fairly-rough-pipe.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=33c6dedc627ed834a11fc6052e8fc737" alt="Fig P 4 Friction Loss in Fairly Rough Pipe" width="1586" height="1828" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p4-friction-loss-fairly-rough-pipe.png" />
</Frame>

**Fig P 5 Friction Loss in Rough Pipe** — same axes and diameter range as Fig P 4, for rough pipe.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p5-friction-loss-rough-pipe.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=905fb8f717cbedd8856a897da6736f43" alt="Fig P 5 Friction Loss in Rough Pipe" width="1636" height="1858" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p5-friction-loss-rough-pipe.png" />
</Frame>

**Fig P 6 Friction Loss in Fairly Smooth Pipe** — same axes and diameter range as Fig P 4, for fairly smooth pipe.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p6-friction-loss-fairly-smooth-pipe.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=637caa92a432e86bab613192d999b317" alt="Fig P 6 Friction Loss in Fairly Smooth Pipe" width="1580" height="1822" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p6-friction-loss-fairly-smooth-pipe.png" />
</Frame>

**Fig P 7 Friction Loss in Copper Pipe** — a log-log chart of flow in litre per minute (y-axis, 1 to 10000) against friction loss in kPa per metre (x-axis, 0.01 to 100), with lines for diameters 19 through 150 mm, and separate curves for copper pipe Type M, Type L and Type K at the smaller-diameter end of the chart.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p7-friction-loss-copper-pipe.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=ceff91d74dd1504da880546dbad8fef1" alt="Fig P 7 Friction Loss in Copper Pipe" width="1623" height="1853" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-p-fig-p7-friction-loss-copper-pipe.png" />
</Frame>

## Appendix Q: Completion Certificate (Water Supply Works)

Ref. No. of the Authority's permit: \_\_\_\_\_ Date: \_\_\_\_\_

This is to certify that I/We have completed the water supply and distribution system of the building and the premises at: \_\_\_\_\_

Detail description of the work: \_\_\_\_\_

This may be inspected, tested and approved.

Signature of the licensed plumber — Name and Address: \_\_\_\_\_

**The Authority's Certificate**

Certified that the above water supply and distribution system has been completed in accordance with Chapter 6 of Part 8 of the Bangladesh National Building Code. The water supply connection from water main (if any) to the service pipe will be made on \_\_\_\_\_.

Signature of the Building Official or his authorized deputy

Seal

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-q-completion-cert-water-supply.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=abccd74385abe50aacb621bea83a2dec" width="874" height="1204" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-q-completion-cert-water-supply.png" />
</Frame>

## Appendix R: Application for Permit to Construct Drainage and Sanitation System

1. Occupancy classification: \_\_\_\_\_
2. Number of storeys: \_\_\_\_\_
3. Location: \_\_\_\_\_
4. This application is accompanied by all required plans, drawings (showing details of materials, sizes, gradient and location of pipes and location of fixtures) and other details as specified in Sec 7.4.2, 7.4.3, 7.4.4 and 7.9.10 of Part 8 of Bangladesh National Building Code.

Signature of the licensed plumber — Name and Address: \_\_\_\_\_

Signature of the owner or his/her appointed person — Name and Address: \_\_\_\_\_

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-r-drainage-permit.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=8bbbdb2fa8a3fff253c31666df51233c" width="857" height="1192" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-r-drainage-permit.png" />
</Frame>

## Appendix S: One-hour Rainfall

One hour rainfall values for a 25-year return period for various locations in Bangladesh may be taken from Fig S 1. The figure shows different regions of equal rainfall intensity as well as isohyets at 5 mm intervals.

Rainfall for a particular location shall be obtained as follows:

a) When the location lies within any region (shown shaded in the map), the value marked for that region shall be taken.

b) For a location lying on any isohyet in this map, the value of that isohyet shall be taken.

c) For a location lying outside the positions (a) and (b) above, linear interpolation shall be made between the adjacent isohyets to obtain the required rainfall value.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/fig-s1-one-hour-rainfall-map.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=548bc57cb8a6688bd479d8da1788e81f" width="874" height="1203" data-path="images/bnbc2006/part-8-building-services/appendices/fig-s1-one-hour-rainfall-map.png" />
</Frame>

**Fig S 1 One-hour Rainfall (mm), Return period 25 Years** — a map of Bangladesh with district/city names, international boundaries, rivers and lakes, 25-year isohyets (labeled contour lines, e.g. 65, 70, 75, 80, 85, 90, 95, 100, 105, 110), and shaded/patterned "Rainfall Regions." Isohyet values visible on the map range from about 65 mm (southwest, Meherpur/Chuadanga/Jhenaidah area) to about 110 mm (southeast, Feni/Noakhali/Chittagong coastal belt), with a distinct closed high-value contour (up to about 115, center marked \~55 is likely a mislabeled/illegible innermost contour near Barisal/Jhalakati — see note below) around the Barisal region. Notes printed on the map (matching the appendix text above): (a) isohyet at a region boundary has the same value as that of the region; (b) rainfall for a particular location shall be obtained per the three rules (i)-(iii) reproduced in the appendix text.

<Note>
  The innermost closed contour near Barisal/Jhalakati/Patuakhali is printed with a value that reads as "55" in the original scan, which is inconsistent with the surrounding 70-100 mm contours in that area. This is likely a misprint in the original gazette.
</Note>

## Appendix T: Design Guideline of a Septic Tank

The volume of a septic tank may be computed using the following equation:

$$
V = PQt + PSy
$$

where

| Symbol | Meaning                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 |
| ------ | ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| $V$    | Volume of the septic tank (litre)                                                                                                                                                                                                                                                                                                                                                                                                                                                                       |
| $P$    | Number of persons served                                                                                                                                                                                                                                                                                                                                                                                                                                                                                |
| $Q$    | Flow, litre/capita/day (lpcd). The flow may be computed considering waste water flow 60% to 70% of the water consumption or on the basis of the plumbing fixtures discharging simultaneously into the septic tank, Sec 7.9.11.7. In absence of these data the waste water flow for the Occupancy groups A, C and D may be considered 120 lpcd for cities, 50 lpcd for district town and 20 lpcd for thanas and rural areas. For other Occupancy groups a waste water flow of 10 lpcd may be considered. |
| $t$    | Liquid retention time, day (minimum 1 day, Sec 7.9.11.12)                                                                                                                                                                                                                                                                                                                                                                                                                                               |
| $S$    | Volume required for sludge and scum (0.04 m³/capita/year, Sec 7.9.11.11)                                                                                                                                                                                                                                                                                                                                                                                                                                |
| $y$    | Desludging frequency, year (Minimum 1 year, Sec 7.9.11.13)                                                                                                                                                                                                                                                                                                                                                                                                                                              |

If computed volume is less than 2000 litres then minimum volume of the septic tank shall be 2000 litre (Sec 7.9.11.8).

## Appendix U: Completion Certificate (Drainage and Sanitation Works)

Ref. No. of the Authority's permit: \_\_\_\_\_ Date: \_\_\_\_\_

This is to certify that I/We have completed the drainage and sanitation system for the building and the premises at: \_\_\_\_\_

Detailed description of the work: \_\_\_\_\_

This may be inspected, tested and approved.

Signature of the plumber — Name and Address: \_\_\_\_\_

**The Authority's Certificate**

This is to certify that the above drainage and sanitation system has been completed in accordance with Chapter 7 of Part 8 of the Bangladesh National Building Code. The drainage connection to the main sewer (if any) will be made on \_\_\_\_\_.

Signature of the Building Official or his authorized deputy

Seal

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-u-completion-cert-drainage.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=3e3c5c57e43bc9ca3c7d6eb162757c7b" width="849" height="1186" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-u-completion-cert-drainage.png" />
</Frame>

## Appendix V: Work on the Gas Supply System

This appendix applies only to work on gas supply systems ahead of the outlet of the meter set assembly, or of the service regulator when there is no meter.

**Serving Gas Supplier's Main**

No person, unless in the employ of or authorized by the gas supply company shall open or make connections with gas main.

**Serving Gas Piping**

No person, unless in the employ of or authorized by the gas supply company, shall repair, alter, open or make connections to the services gas piping or do any other work on the parts of the gas supply system up to the meter set assembly or the service regulator when there is no meter.

**Meter or Service Regulator When a Meter is Not Provided**

No person, unless in the employ of or authorized by the gas supply company, shall disconnect the inlet of the gas meter or service regulator when there is no meter, nor move such meter or regulator. A gas fitter may disconnect the outlet of such a meter or regulator from the house piping only when necessary. He shall make the joint at the meter or service regulator outlet when there is no meter, carefully replacing all insulating fittings or insulating parts of such fittings, and shall leave the gas turned off at the meter or regulator unless the gas supply company's rules require or allow deviation from this procedure.

**Notify Gas Supply Company of any Repairs Needed**

In case any work done by a gas fitter reveals the need for repairs or alterations on any part of the gas supply system, the gas supply company shall be notified promptly of this fact.

**Notify Gas Supply Company of any Leakage**

If gas is leaking from any part of the gas supply system, a gas fitter or plumber not in the employ of the gas supply company may make necessary repairs and shall promptly notify the gas supply company.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-v-gas-supply-work.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=8aca51ec0a1cc2760d67c39578c25916" width="856" height="1140" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-v-gas-supply-work.png" />
</Frame>

## Appendix W: Documentation for the Piping Installation

The gas supply company requires the following to be fulfilled by the consumer(s) for having gas supply from its distribution piping system:

a) Application for gas connection in prescribed from along with the approved plan of the building where the gas is to be used. If the building is not approved by the Authority its plan is to be prepared by an approved contractor of the gas supply company.

b) An approved contractor of the gas supply company shall prepare the plan of the gas piping system for the building. The plan is to include plan and elevation of the proposed piping system. The plan so prepared shall be submitted to the gas supply company.

c) Installation of the piping system as approved by the gas supply company shall be carried out by an approved contractor of the gas supply company.

d) Completion report of the installation of the piping system (using the approved drawing) along with the pressure and lead tests by the approved contractor shall be submitted to the gas supply company. The pressure test is to be witnessed by the approved official of the gas supply company.

e) Completion report mentioned in (d) above is to include the papers related to the permission from the Authority for digging/cutting the road for taking the connection from the main supply line lying under the road, if needed.

f) The legal owner of the building shall sign an agreement with the gas supply company using the prescribed agreement document of the gas supply company prior to having the gas supplied to his premises.

<Frame>
  <img src="https://mintcdn.com/abusayed/94eg1vzil5gABA3Z/images/bnbc2006/part-8-building-services/appendices/appendix-w-piping-documentation.png?fit=max&auto=format&n=94eg1vzil5gABA3Z&q=85&s=96464d44dcd9f6f3a607e59b06cf896c" width="856" height="1190" data-path="images/bnbc2006/part-8-building-services/appendices/appendix-w-piping-documentation.png" />
</Frame>