2.1 Occupancy Classification 2.1.1 Every building or portion thereof and land-use shall be classified according to its use or the character of its occupancy as a building of Occupancy A, B, C, D, E, F, G, H, I, J, K, L or M as defined below: Occupancy A: Residential Occupancy B: Educational Occupancy C: Institution for care Occupancy D: Health Care Occupancy E: Business Occupancy F: Mercantile Occupancy G: Industrial Occupancy H: Storage Occupancy I: Assembly Occupancy J: Hazardous Occupancy K: Garages Occupancy L: Utilities Occupancy M: Miscellaneous 2.1.2 Utilities under Occupancy L is incidental to operation in all other type of occupancy except Occupancy J shall be considered as non-separated use of the main occupancy but shall be taken special safety measure as per provision of this Code. 2.1.3 Any occupancy or use type not mentioned specifically in Table 3.2.6 (A-Z list) or elsewhere in this Code shall be classified by the Board of Appeals under the occupancy group to which its use most closely resembles, considering the life safety and fire hazard. 2.1.4 Each occupancy group shall be subdivided as detailed in the following sections. The detail classification including mixed occupancy provided in the Table 3.2.6 (A-Z list) is non-exhaustive. If there is any use or character of occupancy in a building which is not mentioned here, it shall be classified as per provision of Sec 2.1.3 of this Chapter. 2.1.5 Occupancy A: Residential Buildings This occupancy type shall include any building or portion thereof providing sleeping and living accommodations to related or unrelated groups of people, with or without independent bathroom, cooking or dining facilities, except any building classified under Occupancy C or D. This Occupancy shall be subdivided as follows: 2.1.5.1 Single Family Dwelling (A1) These shall include any building, row type or semi-detached or detached from neighboring buildings by distances required by this Code and having independent access to the plot, which is used as private dwelling by members of a single family. 2.1.5.2 Two Family Dwelling (A2) These shall include any building, row type or semi-detached or detached from neighboring buildings by distances required by this Code and having shared or independent access for two families and having facilities for living, cooking and bathroom facilities independent of each other. 2.1.5.3 Flats or Apartments (A3) These shall include any building or portion thereof which is provided for more than two families, having facilities for living, cooking and bathroom facilities independent of each other. 2.1.5.4 Mess, Boarding Houses, Dormitories and Hostels (A4) These shall include any building or portion thereof in which sleeping, living accommodations and bathroom are provided for groups of related or unrelated persons, with or without common dining and facilities, and with common cooking under single management control or with individual or group cooking facilities. 2.1.5.5 Hotels and Lodging Houses (A5) These shall include any building, a portion thereof or group of buildings under single management, in which sleeping, living accommodation and bathroom facilities are provided with or without dining facilities but without cooking facilities for adult individuals, is provided for hire on transient or permanent basis. 2.1.6 Occupancy B: Educational Facilities This occupancy type shall include any building or portion thereof in which education, training and care are provided to children or adults. This Occupancy shall be subdivided as follows: 2.1.6.1 Educational Facilities up to Higher Secondary Level (B1) These shall include any building or portion thereof used for purposes involving assembly for instruction, education and recreation of more than six persons on regular basis to fulfil the requirement of an academic curriculum approved by the Government up to Higher Secondary (12th Grade), and which is not covered by occupancy I. 2.1.6.2 Facilities for Training and for Above-Secondary Level (B2) These shall include any building or portion thereof used for purposes involving assembly for instruction, education, training and recreation of more than six persons, and which is not covered by occupancy I and B1. 2.1.6.3 Pre-School Facilities (B3) These shall include any building or portion thereof used for purposes involving care, recreation and education of children more than six in number, who have not yet reached the age to attend the school. 2.1.7 Occupancy C: Institution for Care Buildings classified under this occupancy shall include those used for purposes of institutional care of the occupants, such as detention for correctional or penal purposes, medical or nursing care of persons suffering from illness or infirmity due to mental condition, or accommodation of children or minor, where the personal liberty of the inmate is restricted. These buildings shall ordinarily provide accommodation for sleeping, dining and other provisions approved by the authority for the occupants. This occupancy shall be subdivided as follows: 2.1.7.1 Institution for Care of Children (C1) These shall include any building or portion thereof or group of buildings under single management used as an institution for the full time care of children or minor, each providing accommodation for sleeping, dining and other provisions approved by the authority for more than six children. 2.1.7.2 Custodial Institution for Physically Capable Adults (C2) These shall include any building or portion thereof or group of buildings under single management used for purposes of full time care and custody of adult or mentally disabled persons but physically capable of responding to emergency. 2.1.7.3 Custodial Institution for the Incapable Adults (C3) These shall include any building or portion thereof or group of buildings under single management used for purposes of full time care and custody of persons physically or mentally incapable of responding to emergency. 2.1.7.4 Penal and Mental Institution for Children (C4) These shall include any building or portion thereof or group of buildings under single management used for housing children under restraint, or who are detained for penal and corrective purposes, in which personal liberty of the inmates is restricted. 2.1.7.5 Penal and Mental Institution for Adults (C5) These shall include any building or portion thereof or group of buildings under single management used for housing persons under restraint, or who are detained for penal and corrective purposes, in which personal liberty of the inmates is restricted. 2.1.8 Occupancy D: Health Care Facilities Buildings under this Occupancy group shall include those used for purposes of providing medical care, diagnostic facilities and treatment to persons suffering from physical discomfort, in which sleeping accommodation may or may not be provided. This Occupancy shall be subdivided as follows: 2.1.8.1 Normal Medical Facilities (D1) These shall include any building or portion thereof or group of buildings under single management in which essential medical facilities having surgery, emergency and casualty treatment facilities, general or specialized medical and other treatment are provided to persons suffering from physical discomfort. 2.1.8.2 Emergency Medical Facilities (D2) These shall include any building or portion thereof used for purposes of providing essential medical facilities having surgery, emergency, casualty treatment facilities, general or specialized medical and other treatment is provided to persons suffering from physical discomfort. This Type shall be equipped and designated to handle post disaster emergency, by construction it is required to remain operational during and after disasters, built as a part of disaster preparedness program. 2.1.9 Occupancy E: Business These shall include any building or portion thereof which is used for any business transaction other than mercantile. This Occupancy shall be subdivided as follows: 2.1.9.1 Office (E1) These shall include any building or part thereof which is used for paper works, documentations, only display of samples of Products but not for direct sale, maintaining accounts and records for administrative or consulting services, banking or activities for business purposes and professional training. 2.1.9.2 Research and Testing Laboratories (E2) These shall include any building or portion thereof which is used as research establishment and/or test laboratory involving hazardous materials within the limit of exempted quantity permitted in this Code. 2.1.9.3 Essential Services (E3) These shall include any building or portion thereof used for purposes of providing emergency services and utilities which are required to remain operational during and after a disaster or other emergency situations. 2.1.10 Occupancy F: Mercantile This occupancy type shall include any building or portion thereof or group of buildings which is used for display and sale of merchandises. This Occupancy shall be subdivided as follows:
2.1.10.1 Small Shops and Market (F1)
These shall include any building or portion thereof with an area divided or undivided not exceeding 300 m², used for purposes of display and sale of merchandise, either wholesale or retail, with or without incidental storage and service facilities.
2.1.10.2 Large Shops and Market (F2)
These shall include any building or portion thereof with an area divided or undivided more than 300 m² used for purposes of display and sale of merchandise, either wholesale or retail, with or without incidental storage and service facilities.
2.1.10.3 Refueling Station (F3)
These shall include any building or portion thereof used for providing refueling and maintenance without repair services for automobiles which is moderately hazardous in nature. 2.1.11 Occupancy G: Industrial Buildings Buildings under this Occupancy shall be subdivided on the basis of hazard potential of the contents and the processes of the industry. The hazard shall generally mean the relative danger of the start of fire and the rapidity of its spread, the danger of smoke and gases generated that pose a potential threat to the safety of the occupants of the building. Unless areas with different degrees of hazard are effectively segregated and separated in accordance with the provisions of this Code, the most hazardous area in a building shall govern its classification. This occupancy shall also include facilities for public utility ংবৎারপবং ধঃ:যব ঢ়ৎড়ফঁপবৎ ড়ৎ ফরংঃৎরনঁঃড়ৎ্থং বহফ:যধঃ ফবধষং রিঃয মবহবৎধঃরড়হ ধহফ ফরংঃৎরনঁঃরড়হ ড়ভ utility facilities. Any such building or portion thereof, which is not using hazardous material quantified and categorized in occupancy group J, shall be subdivided as follows:
2.1.11.1 Low Hazard Industry (G1)
These shall include any industrial building in which the contents are of such low combustibility and the processes conducted therein are of such low hazardous nature that danger of self-ignition and self-propagation of fire is nonexistent, the only danger being an onset of fire from external sources with the resulting danger to life and property.
2.1.11.2 Moderate Hazard Industry (G2)
These shall include any industrial building in which the contents are moderately combustible and the industrial processes conducted therein are liable to give rise to a fire which will spread with moderate rapidity, giving off considerable smoke. 2.1.12 Occupancy H: Storage Buildings Buildings under this Occupancy group shall include any building or portion thereof used primarily for storage or sheltering of goods, wares, merchandises, vehicles or animals. Any such building or portion thereof, which is not used for storing hazardous material quantified and categorized in occupancy group J, shall be subdivided as follows:
2.1.12.1 Low Fire-risk Storage (H1)
These shall include any building or portion thereof which is used for storage of materials or other contents which do not constitute the danger of self-ignition, and in the event of fire the rate of burning shall be less than moderate rapidity.
2.1.12.2 Moderate Fire-risk Storage (H2)
These shall include any building or portion thereof which is used for storage of materials which do not constitute the danger of self-ignition but which in the event of fire will burn with moderate rapidity. Items which shall be deemed to render a building hazardous are specified in Sec 2.14.3 along with the exempted amount for each item. 2.1.13 Occupancy I: Assembly Buildings under this Occupancy group shall include any building or portion thereof in which groups of people congregate or assemble for recreation, amusement, social, religious, political, cultural, travel and similar purposes. This Occupancy shall be subdivided as follows:
2.1.13.1 Large Assembly with Fixed Seats (I1)
This occupancy shall include a building or a portion thereof for assembly in a space provided with fixed seats for 1000 or more persons. Assembly buildings under this subdivision may be for theatrical, operatic performances or cinema projection having or not a raised stage, proscenium curtains, scenery loft or projection screen, lighting equipment, projection booth and necessary theatrical and mechanical equipment.
2.1.13.2 Small Assembly with Fixed Seats (I2)
This occupancy type shall include any building or portion thereof primarily meant for use as described for buildings under Occupancy I1, but with fixed seats for less than 1000 persons in a space. These assembly buildings may or may not be provided with a legitimate theatrical stage or related accessories or equipment.
2.1.13.3 Large Assembly without Fixed Seats (I3)
This occupancy type shall include any building or portion thereof for assembly in a space, in which there are no fixed seats, which may or may not be provided with a legitimate stage or theatrical accessories, and which has accommodation for 300 or more persons.
2.1.13.4 Small Assembly without Fixed Seats (I4)
This occupancy type shall include any building or portion thereof primarily intended for use as described in Occupancy I3, but with accommodation for less than 300 persons in a space.
2.1.13.5 Sports Facilities (I5)
This occupancy type shall include any building or portion thereof meant for assembly of spectators for recreational and amusement purpose mainly related to sports. 2.1.14 Occupancy J: Hazardous Buildings Any Building or portion thereof used as storage, industrial, research and other facilities dealing with hazardous material in excess of exempted quantity defined in the Table 3.2.5 or any micro-biological facilities shall be categorized in this Occupancy group. Definition of hazard and the amount of such materials which shall be deemed to render a building hazardous are set forth in Sec 2.14.3. This Occupancy shall be subdivided as follows:
2.1.14.1 Explosion Hazard Buildings (J1)
These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of explosive materials and products that have explosion hazard.
2.1.14.2 Chemical Hazard Buildings (J2)
These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that are highly corrosive, toxic, poisonous and physically harmful including corrosive and toxic alkalis, acid or other liquids or chemicals, producing flame, fumes, radiation, and explosive, poisonous, irritant and corrosive gases.
2.1.14.3 Biological Hazard Buildings (J3)
These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use biological processes and in which the risk of harmful biological threat to the occupants exist.
2.1.14.4 Radiation Hazard Buildings (J4)
These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use nuclear and radioactive processes and in which the risk of radioactive contamination exists. 2.1.15 Occupancy K: Garage These occupancy types shall include any building or portion thereof used one or more vehicles having containers of flammable liquid or compressed gas or carrying power or combination of any of these as a supply source for self-propelling are kept for use, sale, rental purpose, storage, repair, exhibition and all those floors of a building or portion thereof in which such vehicles are not separated by suitable cutoff to prevent fire spreading.
2.1.15.1 Parking Garage (K1)
This occupancy type shall include any building or portion thereof used solely for parking Motor Vehicles for a limited period of time.
2.1.15.2 Private Garage (K2)
This occupancy type shall include any building or portion thereof used as store of owner’s or tenant’s Motor Vehicles for private use for unlimited period of time.
2.1.15.3 Repair Garage and Showrooms (K3)
This occupancy type shall include any building or portion thereof wherein repair of electrical or mechanical system or denting or painting works of body is performed on any type of vehicles and includes associated floor spaces used as office, showrooms, incidental store and parking. 2.1.16 Occupancy L: Utility This occupancy type shall include any building or portion thereof used to install any type of equipment to provide support service to any building or portion thereof or group of buildings of all occupancy groups and with special provisions for occupancy J. ঞযরং ংযধষষ ধষংড় রহপষঁফব ধষষ ঢ়ঁনষরপ ধহফ ঢ়ৎরাধঃব ঁঃরষরঃু ভধপরষরঃরবং ড়ভ:যব পড়হংঁসবৎ্থং বহফ:যধঃ ধৎব ষড়পধঃবফ রিঃযরহ:যব পড়হংঁসবৎ্থং ংরঃব ধহফ ধষষ রহংঃধষষধঃরড়হং ধৎব ৎবয়ঁরৎবফ ংঢ়বপরধষ পধৎব:ড় ensure life and property safety as per provisions of this Code. 2.1.17 Occupancy M: Miscellaneous Buildings under this Occupancy group shall include special buildings not covered in other Occupancy groups. These Occupancies shall be subdivided as follows:
2.1.17.1 Special Structure (M1)
Any building or structure which is neither listed in the A-Z list nor covered in any occupancy group provided in this Code but unique in character may be categorized in this occupancy by the Board of Appeals. Each and every individual M1 Structure shall be complied with NFPA or equivalent standards for the life and fire safety.
2.1.17.2 Fences, Tanks and Towers (M2)
These shall include fences and boundary walls over 1.5 m high, standalone structures for gravity water tank and towers for telecommunication, power distribution, air-traffic control terminal or observation towers.

2.2 Change of Use

2.2.1 Without prior permission from the Authorities having jurisdiction no change shall be made in the type of occupancy or use of any building that would place it in a different occupancy group or in a different subdivision of the same occupancy group. Such changes shall be permitted only when the land use and the building complied with the provisions of this Code and the laws of the land for such group of Occupancy.

2.3 Mixed Occupancy

2.3.1 The following occupancies shall not be required to designate as a separated occupancy classification from uses to which they are accessory any occupancy Group other than Occupancy Group J (a) Assembly rooms having a floor area not more than 75 m². (b) The administrative and clerical offices and similar offices not exceeding 25 Percent of the floor area of the major occupancy and not related to Hazardous Buildings as defined in Occupancy J. (c) Administrative offices, gift shops and other similar uses in Occupancy A provided the uses do not exceed 10 Percent of the floor area of the major occupancy. (d) Kitchens associated with a dining area. (e) Carports having at least two sides entirely open associated with Occupancy A. 2.3.2 Forms of Occupancy Separations A building is permitted to have multiple occupancy type, each type of occupancy shall be in groups, which may have combination of different occupancies and shall be separated horizontally or vertically or both accordingly as specified in the Table 3.2.1. 2.3.3 Types of Occupancy Separation The occupancy separations shall be classified as follows: (a) Four Hour Fire Resistive: The four hour fire resistive separation wall or slab shall have no unprotected openings therein and shall provide a fire resistance for at least four hour. (b) Three Hour Fire Resistive: The three hour fire resistive separation wall or slab shall provide a fire resistance of not less than three hour. The total width of all openings in separation wall of any one storey shall not exceed 25 Percent of the length of that wall in that storey and no single opening shall have an area greater than 12 m². The openings shall be protected with a fire resistance assembly doors or windows providing fire resistance of at least three hour. (c) In case of a floor slab having three hour fire resistance rating, the openings on floor slab shall be protected by vertical enclosures extended above and below such floor openings. The walls of such vertical enclosures shall be at least two hour of fire resistance. All openings in such enclosures shall be protected with fire assembly door or window having fire resistance rating of at least one and one-half hour. (d) Two Hour Fire Resistive: The two hour fire resistive separation shall be of a construction having a fire resistance rating of not less than two hour. All openings in such separations shall be protected with a fire assembly door or window of a fire protection rating of at least one and one-half hour. (e) One Hour Fire Resistive: The one hour fire resistive separation shall be of at least one hour fire protection construction. All openings in such separations shall be protected with a fire protection assembly door or window of at least one-half hour fire resistance. Table 3.2.1: Fire Resistance Rating Requirements for Barrier Walls and Floor/Ceiling Assemblies between Separated Occupancies (hours)

2.4 GENERAL REQUIREMENTS OF ALL OCCUPANCIES

2.4.1 Location on Property 2.4.1.1 All plots for building construction shall have access to a public road from at least one side. 2.4.1.2 Fire separation distance shall be measured from the face of peripheral wall of a building to the adjacent property line. For the purpose of this Section, if a public road adjoining all along a property line shall get the benefit of half of Road width as a part of Fire separation distance. For two or more buildings on the same plot, distances of imaginary lines equidistant from all side of buildings shall be considered as the required fire separation distances. 2.4.1.3 The exterior walls of a building shall have a fire resistance and opening protection as specified in Tables 3.3.1 (a), 3.3.1 (b) and 3.2.3. 2.4.1.4 Any outward projected elements from the peripheral wall of a building line shall be limited to the sunshade line. 2.4.1.5 When openings in exterior walls are required to be protected due to distance from the property line, the aggregate area of such openings shall not exceed 50 Percent of the total area of the wall in each storey. 2.4.1.6 Dwellings separation walls in semi-detached or row type development shall comply with Sec 2.4.3. 2.4.2 Allowable Floor Areas 2.4.2.1 The total area of the building shall comply with Sec 1.8.3 Chapter 1 of this Part. 2.4.2.2 The floor area of the mezzanines shall be included in the area of the respective main floor. 2.4.2.3 Floor area calculation shall be divided in to two: (a) All Floor areas at and above the formation level which shall be generally included in the FAR calculation. (b) Floor areas below the formation level shall generally be excluded in FAR calculation provided the Occupancy classifications remain within Utility or Private Garages. Table 3.2.2: Fire Resistance Ratings in Hours of Exterior Walls for Various Occupancy Groups Fire Separation Distance Occupancy A1, A2, K2 , M2 A3, A4, A5, B,C, D, E1, F1, F2, G1, I E2, F3, F4, E3, G2, H1 H2, J Up to 1.5 m Greater than 1.5 m and up to 3 m N Greater than 3 m and up to 4.5 m N N Greater than 4.5 m and up to 9 m N N N Greater than 9 m N N N N N= No requirements Table 3.2.3: Requirements for Opening Protection Assembly Based on Fire Resistance Rating of Exterior Walls Fire Resistance Ratings of Exterior Walls (in hours) Fire Resistance Ratings for Opening Assembly (in hours) Not permitted 3.0 1.5 0.5 N No requirements 2.4.3 Permitted Types of Construction 2.4.3.1 The types of construction for any occupancy shall conform to the specifications set in Table 3.2.4. 2.4.3.2 Common walls in semi-detached or row type development shall not have any unprotected openings and shall be Type I-A construction and all such wall shall comply with requirements of Party wall or Fire wall or Separation wall. 2.4.3.3 Ground floor or basement of a building used for car parking and utilities within the barriers by at least three hour fire resistive construction shall be considered as non-separated occupancy provided the building accommodates one or more of the following occupancies: (i) A3, A5 (ii) E1, F1, F2 (iii) I2, I3, I4 2.4.3.4 Entry lobbies, mechanical and electrical rooms and other similar uses incidental to the operation of the building may be provided in the car parking floors provided that the total area of such uses remains within ⅓ (one third) of the parking floor area. Table 3.2.4: Permitted Types of Construction and Fire Zones for Various Occupancy Groups Occupancy Permitted Types of Construction Fire Zones A Group I and Group II* B C D E1 F1,F2 I K1, K2, M2 E2, E3, F3, K3, M1 Group I or Group II* G H J Group I *Fire resistance rating of a building shall be credited in case of the mixed type of construction on the basis of lower rated construction elements among the same group or same type used thereof. 2.4.4 General Provision for High-Rise Buildings For the purpose of this Code, a building of any class of Occupancy will be considered as high-rise when it has floors used for human occupancy located more than 33 m from ground level or the lowest level of fire department vehicle access. The provisions of Sec

2.9.6 shall be applicable to all such buildings.

2.4.4.1 Maintenance and inspection All fire protection systems shall be maintained and inspected on a regular basis to keep them in operative condition. The maintenance inspection shall be performed quarterly. All plumbing installations shall be maintained and inspected periodically to keep them in operative conditions. 2.4.4.2 Type of construction All high-rise buildings shall be of Type I-A or I-B construction. 2.4.4.3 Fire detection, alarm, evacuation and extinguishment system All high-rise buildings shall conform to regulations set forth in Part 4 of this Code 2.4.5 Helipads 2.4.5.1 General Helipads on the roof top of a building or other locations shall be constructed in accordance with this Section. 2.4.5.2 Size The minimum dimension of the landing area for helicopters weighing less than 1600 kg shall be 6 m  6 m. There shall be an average clearance of 4 m surrounding and at the level of the landing area which shall not be less than 2 m at any point. 2.4.5.3 Construction Helicopter landing areas and supports shall be constructed with non-combustible material. 2.4.5.4 Aviation approval Before helipads start operating, formal approval shall be obtained from the civil aviation authority. 2.4.6 Universal Accessibility 2.4.6.1 All Building (except Occupancies G, H, M and J) shall have universal accessibility as per provisions of this Code. 2.4.6.2 Buildings have universal accessibility shall have accessible egress system.

2.5 Requirements For Occupancy A- Residential Buildings

Buildings shall be classified as Occupancy A in accordance with Sec 2.1.5. 2.5.1 Construction, Height and Allowable Area 2.5.1.1 Buildings or parts thereof classified as Occupancy A shall be limited to the type of construction set forth in Table 3.2.4 and shall not exceed in area or height as specified in Sections 1.8 and 2.4.2 of this Part. 2.5.1.2 Walls and floors separating dwelling units in the same building shall not be less than Type I-D construction. 2.5.1.3 Storage or laundry rooms in Occupancy A2, A3, A4 or A5 that are used in common by the occupants shall be at least Type I-D construction. 2.5.1.4 When a basement or a ground floor of a building of Occupancy A3 or A5 is used for parking or storage of private cars of the occupants, the parking floor shall be of at least Type I-B construction. 2.5.1.5 When the basement or ground floor of a building of Occupancy A is used wholly or partly for generator or electrical substation, the walls and floors surrounding such use shall be of at least Type I-B construction. 2.5.2 Location on Property Buildings of Occupancy A shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in this Code. 2.5.3 Access and Exit Facilities and Egress System 2.5.3.1 Facilities for access and exit and egress or escape shall comply with the provisions set forth in this Code. 2.5.3.2 Every sleeping room in ground, first and second floors shall have at least one operable window or door for emergency escape which shall open directly into the exterior or an interior courtyard. The units shall be operable from the inside without the use of any tool to provide a minimum clear opening of 500 mm width by 600 mm height with a maximum sill height of 1 m above the floor. 2.5.4 Lighting and Ventilation All buildings or part of a building classified as Occupancy A shall conform to the provisions of Part 3, and Chapters 1 and 3 of Part 8. 2.5.5 Sanitation Sanitation facilities provided in all Occupancy A buildings shall conform to this Part and Chapter 7 Part 8. 2.5.6 Minimum Dimension of Habitable and Non-habitable Rooms The minimum dimensions of habitable and non-habitable rooms are specified in Sec

1.12.2 Chapter 1 Part 3.

2.5.7 Fire detection, Alarm, Evacuation and Extinguishment All buildings shall conform to regulations set forth in Part 4 of this Code. 2.5.8 Shaft and Exit Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Part 4 of this Code.

2.6 Requirements For Occupancy B - Educational Buildings

Buildings shall be classified as Occupancy B in accordance with Sec 2.1.6. 2.6.1 Construction, Height and Allowable Area Buildings or parts of buildings classified as Occupancy B shall be limited to type of construction set forth in Table 3.2.4 and comply with the provisions of Sections 1.8 and

2.4.2 of this Part to meet the requirements of height and area limitations.

2.6.1.1 Rooms or groups of rooms sharing a common space where flammable liquids, combustible dust or hazardous materials are used, stored, developed or handled in an amount exceeding that specified in Sec 2.14.3 shall be classified as Occupancy J. Such rooms or groups of rooms shall comply with the requirements of fire protection as specified in Part 4, Chapters 4 and 5. 2.6.1.2 Rooms or groups of rooms, sharing a common space or having separate spaces, served by a common corridor or passage with less than 20 percent outdoor opening of wall in a building of height 11 m or less, or three storeys or less, need not be provided with smoke detectors and standpipe or sprinkler system for fire protection provided it conforms with the access and exit requirements specified in Part 3, Chapter 1, Sec 1.6 and Part 4, Chapters 4 and 5. 2.6.1.3 Buildings of Occupancy B situated outside the jurisdiction of any municipality shall have a construction of at least two hours fire resistance. 2.6.2 Location on Property Buildings of Occupancy B shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.6.3 Access and Exit Facilities and Egress System Facilities for access and exit and Egress system shall comply with the provisions set forth in Sec 1.6, Chapter 1 Part 3 and Chapter 3 Part 4. 2.6.4 Lighting, Ventilation and Sanitation Lighting, ventilation and sanitation facilities provided in Occupancy Group B buildings shall conform to Sec 1.16, Chapter 1 Part 3 and Chapters 1 and 3 Part 8. 2.6.5 Minimum Dimensions of Class Rooms, Common Toilets and Staircases The dimension of a class room shall be not less than 4 m on any side and shall have an area of not less than 0.75m² per student. Other provisions for minimum dimensions shall comply with the requirements set forth in Sec 1.8 of Chapter 1 Part 3. 2.6.6 Shaft and Exit Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 Part 4. 2.6.7 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code.

2.7 Requirements For Occupancy C- Institutional Buildings

Buildings shall be classified as Occupancy C in accordance with Sec 2.1.7. 2.7.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy C shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations. 2.7.2 Location on Property Buildings of Occupancy C shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.7.3 Access and Exit Facilities and Egress System Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6, Chapter 1 Part 3 and Chapter 3 Part 4. 2.7.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy C shall conform to the provisions of Sec 1.16, Chapter 1 Part 3 and Chapters 1 and 3, Part 8. 2.7.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4. 2.7.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code.

2.8 Requirements For Occupancy D–Health Care Facilities

Buildings shall be classified as Occupancy D in accordance with Sec 2.1.8. 2.8.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy D shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations. 2.8.2 Location on Property Buildings of Occupancy D shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.8.3 Access and Exit Facilities and Egress System Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1, Part 3 and Chapter 3 of Part 4. 2.8.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy D shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3 of Part 8. 2.8.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 of Part 4. 2.8.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code.

2.9 Requirements For Occupancy E–Business

Buildings shall be classified as Occupancy E in accordance with Sec 2.1.9. 2.9.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy E shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations. 2.9.2 Location on Property Buildings of Occupancy E shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.9.3 Access and Exit Facilities and Egress System Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3, Chapter 3 of Part 4. 2.9.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy E shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3 of Part 8. 2.9.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 of Part 4. 2.9.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code. 2.10 Requirements For Occupancy F–Mercantile Buildings Buildings shall be classified as Occupancy F in accordance with Sec 2.1.10. 2.10.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy F shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8, Chapter 1 of Part 3 and Sec 2.4.2 to meet the requirements and limitations of height and area. 2.10.2 Location on Property Buildings of Occupancy F shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.10.3 Access and Exit Facilities and Emergency Escapes Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3 and Chapter 3 Part 4. 2.10.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy F shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3, Part 8. 2.10.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4. 2.10.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code. 2.10.7 Special Hazards Installations which are discharging exhaust, heating apparatus, boiler and central heating/air-conditioning plant shall conform to the provisions of this Code as specified in this Code. 2.11 Requirements For Occupancy G–Industrial Buildings Buildings shall be classified as Occupancy G in accordance with Sec 2.1.11. A non- exhaustive and indicative list of low hazard and moderate hazard industrial uses are listed in A to Z list. Storage and use of hazardous materials shall not exceed the exempt amount specified in Sec 2.14.3. 2.11.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy G shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 of Chapter 1, Part 3 and Sec 2.4.2 to meet the requirements and limitations of height and floor area. The ceiling height of the production area, shall confirm to the minimum volume required per workers as specified by the Bangladesh Labor Act, 2006 and other laws of the land. In any case the ceiling height and the head room clearance of a production floor shall not be less than 3.3 meter and 2.286 meter respectively. 2.11.2 Location on Property Buildings of Occupancy G shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.11.3 Access and Exit Facilities and Egress System Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 Chapter 1, Part 3 and Chapter 3, Part 4. 2.11.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy G shall conform to the provisions of Sec 1.16 Chapter 1, Part 3 and Chapters 1 and 3, Part 8. Industrial buildings having roof opening for day lighting and natural ventilation shall comply with the following requirements: (a) The aggregate opening in roof and external windows shall not be less than 10 Percent of the floor area. (b) For natural ventilation by means of exterior window openings, the operable window area shall not be less than 5 Percent of the total floor area. Exception: Industrial buildings wherein artificial lighting and mechanically operated ventilation systems of approved quality are installed, need not be provided with natural ventilation or natural lighting. 2.11.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4. 2.11.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code. 2.11.7 Special Hazards Chimneys, vents and ventilation ducts shall be constructed with noncombustible materials. Every bailer, central heating plants, electrical rooms, or hot water supply boiler shall be separated from the rest of the occupancy or use by not less than two hour fire resistive construction. 2.12 Requirements For Occupancy H–Storage Buildings Buildings shall be classified as Occupancy H in accordance with Sec 2.1.12. 2.12.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy H shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 of Chapter 1, Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations. 2.12.2 Location on Property The location on property for Occupancy H shall conform to Sec 2.4.1. 2.12.3 Access and Exit Facilities and Egress System Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 of Chapter 1, Part 3 and Chapter 3, Part 4. 2.12.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy H shall conform to the provisions of Sec 1.16 of Chapter 1 Part 3, Chapters 1 and 3, Part 8.
2.12.4.1 Special provision
The provisions of Sec 1.16, does not apply to non-habitable spaces of H1 and H2 occupancies unless otherwise required by this Code. Ventilators of size not less than 0.25 m² shall be provided where suitable 0.30 m above the floor level for floor level ventilators and 0.30 m below the roof level for roof level ventilators. There shall be one floor level ventilator and one roof level ventilator for every 0.25 m² of the floor area. Mechanized ventilation system of approved quality shall be installed where required.
2.12.4.2 Though inhabitable, the minimum air quality of such indoor spaces shall be
maintained in a way that it does not pose any health hazard to the occasional users of that space. 2.12.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4. 2.12.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code. 2.12.7 Special Hazards The storage of hazardous materials shall not exceed the exempt amount as specified in Table 3.2.5. The storage of moderate and low hazardous materials shall be separated at least by a two hour fire resistive construction.

2.13 Requirements For Occupancy I–Assembly Buildings

Buildings shall be classified as Occupancy I in accordance with Sec 2.1.13. 2.13.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy I shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements and limitations of height and area. 2.13.2 Location on Property Buildings of Occupancy I shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.13.3 Access and Exit Facilities and Egress System Facilities for access and exit and Egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1 of Part 3 and Chapter 3 of Part 4 and universally accessibility as per provisions of this Code. 2.13.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy I shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Part 3 and Chapters 1 and 3, Part 8. 2.13.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4. 2.13.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code. The specification of this Section shall apply to all parts of buildings and structures that contain stages or platforms and other similar appurtenances as herein defined. (a) Stages: A stage is a three side enclosed or partially enclosed portion of a building which is designed or used for presentation of plays or lectures or other entertainment. A stage shall be further classified as legitimate stage, regular stage and thrust stage. (b) Stage, Legitimate: A stage wherein curtains, drops, leg drops, scenery, lighting devices or other stage effects are adjustable horizontally or vertically or suspended overhead. (c) Stage, Regular: A stage wherein curtains, fixed drops, valances, scenery and other stage effects are suspended and are not adjustable or retractable. (d) Stage, Thrust: A stage or platform extended beyond the proscenium line and into the audience.
2.13.6.1 Legitimate Stage
Legitimate stage shall be constructed as specified in Part 4, specifying the type of construction but shall not be less than construction Type I-C. The position of the legitimate stage extending beyond the proscenium opening line shall be permitted to be constructed with two hour fire-resistive materials. The floor of the stage may be constructed with one hour fire rating materials. Thickness of a wooden floor shall not be less than 50 mm.
2.13.6.2 Regular and Thrust Stages
Regular stages and thrust stages shall be constructed by not less than two hour fire resistive materials. Wooden floor when required in a stage shall not be less than 50 mm in thickness with one hour fire resistive rating.
2.13.6.3 Trap doors
All trap doors and any other opening in stage floors shall be equipped with tight fitting solid wood trap doors with thickness not less than 50 mm.
2.13.6.4 Stage rigging loft
The grid iron frame in the loft, housing lighting and audio equipment, all the machinery for flying scenery and fly galleries, along with their installations, shall be constructed of approved noncombustible materials.
2.13.6.5 Foot lights and stage electrical equipment
Foot lights and border lights shall be installed in a protective cover constructed of noncombustible materials.
2.13.6.6 Trim, finish and decorative hangings
All materials used in moulding and decoration around the proscenium shall be of approved noncombustible materials.
2.13.6.7 Proscenium curtain
The proscenium curtain shall be of approved fire retardant material and shall protect against passage of flame and smoke for at least 30 minutes. 2.13.7 Motion Picture Projection Rooms
2.13.7.1 Every projection room shall be constructed in conformity with the construction
requirements for the type of the building in which the projection room is located. The wall opening required for projection need not have a fire protection assembly but shall be closed with glass or other approved materials.
2.13.7.2 The floor area of a projection room shall not be less than 8 m² for a single
machine. The working space between the machines when more than one machine is used shall not be less than 0.75 m. 2.13.7.3 The height of the projection room shall have a minimum clear space of 2.5 m. 2.13.8 Sports Facilities
2.13.8.1 Vomiters, aisles and exits of seating galleries
Tunnels, aisles and exits of galleries shall be constructed conforming to the following requirements. (a) There shall be a minimum of two exits remotely located from each other immediately to the outside for each balcony or tier. There shall be at least three exits when seating capacity exceeds 1000 persons and four exits when it exceeds 4000 persons. For every additional 1000 persons the exit shall be designed to accommodate provision (f) given below. (b) There shall be at least 0.6 m2 of space per person in the gallery. Minimum width considered for a seat in the gallery shall be 0.45 m. (c) There shall be a maximum of 33 seats on each side of any aisle. Minimum width of the main aisles and the secondary aisles shall be 1.0 m and 0.7 m respectively. (d) Entrance and exits shall be protected by safety railings. (e) Back to back space between two rows of seats shall not be less than 0.80 m. (f) The evacuation time in the galleries shall not be more than 10 minutes. (g) All tunnels, aisles and exits shall conform to safety guidelines for means of escape set forth in Part 4. (h) One percent of the total seat capacity shall have provisions for accommodation with universal accessibility at the approach or exit level.
2.13.8.2 Swimming pools
Any swimming pool used or constructed for exclusive use by Occupancy A1 and is available only to the occupants and private guests shall be classified as a private swimming pool. Any swimming pool other than private swimming pool shall be classified as a public swimming pool. Swimming pools shall be constructed in conformity with the following requirements. (a) There shall be at least 1.5 m space between any sides of a swimming pool and a rear or side property line. For street property lines, this distance shall be at least 2.0 m. (b) Swimming pools shall be provided with overflow provision to remove scum and other materials from the surface of the water. When water skimmers are used for private pools there shall be one skimming device for each 50 m2 of surface area or fraction thereof. (c) The overflow gutters shall not be less than 75 mm deep and shall be pitched to slope of one unit vertical to 50 units horizontal (1:50) toward drains. (d) Public swimming pools shall be so designed that the pool water turnover is at least once every 8 hours. (e) Private swimming pools shall be designed so that there is a pool water turnover at least once every 18 hours. (f) Public swimming pools shall be equipped with filters, the capacity of which shall be controlled to filter 140 liters per minute per m2 of surface area. Private swimming pool filters shall not filter more than 230 liters per minute per m2 of the surface area. (g) The pH value of the pool water shall be between 7.0 and 7.5. (h) All recirculation systems shall be equipped with an approved hair and lint strainer installed in the system ahead of the pump. (i) All swimming pool and equipment shall be designed to be emptied completely of water and the discharged water shall be disposed in an approved manner and shall not create problems in the neighboring property. (j) Pumps, filters and other mechanical and electrical equipment shall be placed in enclosed spaces and shall not be accessible to the bathers. (k) Used water from the pool when being discarded shall be reused as grey water for the building and its premises as per provision of Appendix G. 2.13.9 Amusement Building Fire Protection System The fire protection system shall be as per provisions of this Code.

2.14 Requirements For Occupancy J–Hazardous Buildings

Buildings shall be classified as Occupancy J in accordance with Sec 2.1.14. 2.14.1 General The plans for buildings and structures accommodating Occupancy J shall clearly indicate the type and intended use of materials and its processing or handling methods so as to reflect the nature of use of each portion of such buildings.
2.14.1.1 Occupancy J1
Any building or portion thereof containing any of the following items more than exempted quantity shall be classified as Occupancy J1. (a) Combustible dusts and any similar solid material sufficiently comminuted for suspension in still air which, when so suspended, is capable of self-sustained combustion. (b) Combustible liquids - Any liquid having a flash point at or above 40°C shall be known as class II and class III liquids. Combustible liquids shall be classified as follows: (i) Liquids having flash point at or above 40°C and below 60°C. (ii) Liquids having flash points at or above 60°C and below 95°C. (c) Cryogenic liquids (flammable or oxidizing): Any liquid that has a boiling point below -130°C. (d) Flammable Gases: Any gas when mixed with air in a proportion of 13% (by volume) forms a flammable mixture under atmospheric temperature and pressure. (e) Flammable Liquids: Any liquid that has a flash point below 40°C and has a net vapour pressure exceeding 275 kPa at 40°C. Flammable liquids shall be known as Class I liquid and shall be further classified as follows: (i) Liquids having flash point below 25°C and having a boiling point below 40°C. (ii) Liquids having flash point below 25°C and having a boiling point at or above 40°C. (iii) Liquids having flash points at or above 25°C and below 40°C. (f) Oxidizers class 3: As determined in accordance with NFPA 43A. (g) Oxidizing gases: As determined in accordance with NFPA 43C. (h) Pyrophoric liquids, solids and gases that will ignite spontaneously in air at a temperature of 55°C or below. (i) Unstable (reactive) materials class 3, non-detonable as determined in accordance with NFPA 704. (j) Combustible fibers: Includes readily ignitable fibers like cotton, sisal, jute hemp, tow, cocoa fiber, oakum, baled waste, baled waste paper, kapok, hay, straw, excelsior, Spanish moss and other similar materials. (k) Flammable solid: Any solid including blasting agent or explosive that is liable to cause fire through absorption of moisture, spontaneous chemical change or retained heat from manufacturing or processing, or which when ignited burns so vigorously and persistently as to create a serious hazard. (l) Organic peroxides, Class II and Class III as determined in accordance with NFPA 43B. (m) Oxidizers Class I and Class II as determined in accordance with NFPA 43A. (n) The bulk storage of unstable (reactive) materials Class 1 and Class 2 as determined in accordance with NFPA 704, water reactive materials, Class 2 and Class 3 which react with water to release a gas that is either flammable or present a health hazard as determined in accordance with NFPA 704.
2.14.1.2 Occupancy J2
Any building or portion thereof containing the following shall be classified as Occupancy J2: (a) Corrosives: Any substance that causes visible destruction of or irreversible alteration in living tissues by chemical action at the site of contact. (b) Highly toxic materials: The materials falling in this category are as follows: (i) Oral Toxicity: A chemical that has a median lethal dose of 50 mg or less per kg of body weight when administered orally to albino rats weighing between 200 and 300 gm each. (ii) Toxicity of Inhalation: A chemical that has a median lethal concentration in air of 200 ppm or less by volume of gas or vapors, or 2 mg per liter or less of mist, fume or dust, when administered by continuous inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and 300 grams each. (iii) Toxicity by Skin Absorption : A chemical that has median lethal dose of 200 mg or less per kg of body weight when administered by continuous contact for 24 hours (or less if death occurs within 24 hours) with the bare skin of albino rabbits weighing between 2 and 3 kg each. (iv) Irritants: Any noncorrosive chemical or substance which causes a reversible inflammatory effect on living tissues by chemical action at the site of contact. (v) Radioactive Material: Any material or combination of materials that spontaneously emit ionizing radiation. (vi) Sensitizers: A chemical or substance that causes a substantial proportion of exposed people or animals to develop an allergic reaction in normal tissue after repeated exposure. (c) The Occupancy J2 shall also include among others the followings: (i) Dry cleaning establishments using flammable solvents. (ii) Explosive manufacturing. (iii) Paint or solvent manufacturing (flammable base). (iv) Pyrexin plastic manufacturing. (v) Sodium nitrate or ammonium nitrate. (vi) Storage of combustible film.
2.14.1.3 Occupancy J3
Any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use biological processes and in which the risk of harmful biological threat to the occupants exist, shall comply with the guidelines specified by the Department of Health.
2.14.1.4 Occupancy J4
Any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use nuclear and radioactive processes and in which the risk of radioactive contamination exists, shall comply with the guidelines specified by Bangladesh Atomic Energy Commission. 2.14.2 Special Provisions
2.14.2.1 The following shall not be included in Occupancy J but shall be classified in
the occupancy group which they most nearly resemble and such classification shall be approved by the Authority: (a) All buildings and structures and parts thereof which contain less than the exempt quantities as specified in Table 3.2.5, when such buildings comply with the fire protection provisions of this Code. (b) Rooms containing flammable liquid in lightly closed containers of 4 litre capacity or less for retail sales or private use on the premises and in quantities not exceeding 820 litres/m² of room area. (c) Retail paint sales rooms with quantities not exceeding 820 litres/m² of room area. (d) Closed systems housing flammable or combustible liquids or gases used for the operation of machinery or equipment. (e) Cleaning establishments. (f) Liquor stores and distributors without bulk storage. (g) Tire storage containing less than 10,000 vehicle tires. (h) The storage or use of materials for agricultural purposes for use on the premises. (i) Pyrophoric solids or liquids not exceeding 3 m3 in storage cabinet located in a building that is equipped throughout with an automatic sprinkler system provided in accordance with the fire protection provisions of this Code. (j) Pyrophoric solids or liquids not exceeding 3 kg in storage cabinet located in a building that is provided with an automatic sprinkler system installed in accordance with the fire protection provisions in accordance to Part 4 of this Code. (k) Class 2 water reactive materials not exceeding 100 kg in an approved storage cabinet located in a building that is provided with automatic sprinkler installed in accordance with the fire protection provisions in accordance to Part 4 of this Code. 2.14.3 Construction, Height and Allowable Area
2.14.3.1 The buildings or parts thereof classified as Occupancy J shall be limited to the
type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec

1.8 of Chapter 1, Part 3 and Sec 2.4.2 of this Chapter to meet the requirements of height

and area limitations.
2.14.3.2 Floors: The floors and spaces containing hazardous materials and in areas
where motor vehicles, boats, helicopters or airplanes are stored, repaired or operated shall be of noncombustible, liquid-tight construction. Exception: In floors and areas where no repair works are carried out may be surfaced or waterproofed with asphaltic paving materials.
2.14.3.3 Spill Control: The floors containing hazardous repair or other works shall be
recessed a minimum of 100 mm so as to prevent flow of liquids to adjoining areas.
2.14.3.4 Drainage: The buildings and areas shall be provided with approved drainage
system to direct the flow of liquids to an approved location or room or area designed to provide secondary containment of the hazardous materials and fire protection water. Table 3.2.5(a): Exempted Amount of Hazardous Materials in Terms of Physical Hazard in a Control Area Sl. No. Material Class/State Maximum Quantities in Storage Limit Use Closed Systems Use Open Systems Flammable liquids Class I-A 115 liters * 115 liters * 38 liters Class I-B and Class I-C 454 liters * 454 liters * 115 liters Combustible liquids Class-II 454 liters* 454 liters* 114 liters Class-III-A 1249 liters* 1249 liters* 320 liters Class-III-B 49962 liters* 49962 liters* liters Combination of flammable liquids Class I-A Class I-B Class I-C 454 liters* 454 liters* liters* Flammable gases Gaseous 28 m3 at NTP (Natural Temperature and Pressure) 28 m3 at NTP (Natural Temperature and Pressure) Not applicable Liquefied 113 liters 113 liters Not applicable Liquefied flammable Class I-A 113 liters 113 liters 38 liters Class I-B and Class I-C 454 liters 454 liters 113 liters Combustible fibres Loose

2.832 m3

2.832 m3

0.57 m3

Baled

28.32 m3

28.32 m3

5.7 m3

Sl. No. Material Class/State Maximum Quantities in Storage Limit Use Closed Systems Use Open Systems Flammable solids Pigs, ingots, heavy castings 454 kg 454 kg 454 kg Light castings, light metallic products 57 kg 57 kg 57 kg Scraps, shavings, powders, dusts

0.454 kg

0.454 kg

0.454 kg

Unstable (reactive) detonable Class 4 0.454kg or 0.28m3 (NTP)

0.113 kg or

0.057m3 (NTP) 0.454kg or 0.28m3 (NTP) Class 3 0.454kg or 0.28m3 (NTP)

0.113 kg or

0.057m3 (NTP) 0.454kg or 0.28m3 (NTP) Unstable (reactive) detonable Class 4 0.454kg or 0.28m3 (NTP)

0.113 kg or

0.057m3 (NTP) 0.454kg or 0.28m3 (NTP) Class 3

2.27 kg or

1.42m3 (NTP) 0.454kg or 0.2832m3 (NTP) 0.454kg Class 2 22.7kg or 70.8 m3 (NTP) 22.7kg or 70.8m3 (NTP)

4.54 kg

Class 1 Not limited or 21.24m3 (NTP) Not limited Not limited Water-reactive detonable

0.454 kg

11.25 kg

11.25 kg

0.454 kg

11.25 kg

11.25 kg

Water-reactive non-detonable

2.27 kg

2.27 kg

0.454 kg

22.7 kg

22.7 kg

4.54 kg

Not limited Not limited Not limited Oxidizing Materials Class 4

0.454 kg

0.1135kg 0.1135kg Class 3

4.54 kg

0.227kg 0.227kg Class 2 113 kg 113 kg 113 kg Class 1 1816 kg 1816 kg 1816 kg Sl. No. Material Class/State Maximum Quantities in Storage Limit Use Closed Systems Use Open Systems Oxidizing Gas Gaseous

42.48 m3 (NTP)

42.48 m3

(NTP) Not applicable Liquefied

56.78 liters

56.78 liters

Not applicable Pyrophoric Material detonable Not applicable

0.454 kg or

0.056 m3 (NTP)

0.056 m3

(NTP) Pyrophoric Material non- detonable Not applicable

1.8 kg. or 1.4

m3(NTP) 0.28m3 (NTP) Explosives** Division 1.1

0.454 kg

0.1135 kg

0.1135 kg

Division 1.2

0.454 kg

0.1135 kg

0.1135 kg

Division 1.3

2.27 kg

0.454 kg

0.454 kg

Division 1.4

22.7 kg

22.7 kg

Not applicable Division 1.4G

56.75 kg

Not applicable Not applicable Division 1.5

0.454 kg

0.1135 kg

0.1135 kg

Division 1.6

0.454 kg

Not applicable Not applicable * The maximum quantities may be increased by 100 percent in areas not accessible to the public in buildings provided with automatic sprinkler system. ** see: Explosive control act. Table 3.2.5(b): Exempted Amounts of Hazardous Materials in Terms Health Hazard in a Control Area Material Class/State Maximum Quantities in Single Storage Closed Systems Open Systems Corrosive Not applicable 2270 kg or 1892 liters or 23 m3 NTP 227kg or 1892 liters or 23 m3 NTP 454kg or 379 liters Highly toxic Not applicable

4.54 kg or 0.57 m3

NTP

4.54 kg or 0.57 m3

NTP

1.362 kg

Toxic Not applicable 227 kg or 23 m3 NTP 227 kg

56.75 kg

Table 3.2.5(c): Location and Number of Control Areas Grade Level Floor Level1 Number of Control Areas per Floor2 Fire Resistance Rating of Barriers in Hours Walls Floors Floor Supporting Members Above Higher than 9 7-9 12.5 12.5 12.5 Below Lower than 2 Not Allowed Not Allowed Not Allowed Not applicable The maximum allowable quantity per control area shown in Table 3.2.5
2.14.3.5 The drains shall be designed with adequate slope and section to carry the
design discharge of the sprinkler system. The material used in the drains shall be suitable for drainage of the storage materials.
2.14.3.6 Separate drainage system shall be designed for materials which react with each
other producing undesirable results. They may be combined when they have been provided with approved means of discharge into the public sewer or natural stream or river.
2.14.3.7 Containment: The outflow from the drains shall be directed to a containment
system or other area that provide a secondary storage for the hazardous materials and liquids and fire protection water. The containment capacity shall be capable of containing the outflow from the drains for a period of at least one hour.
2.14.3.8 The overflow from secondary containment system shall be directed to a safe
location away from the building, adjoining properties and storm drain.
2.14.3.9 If the secondary containment storage area is open to rainfall it shall be
designed to accommodate 24 hour rainfall or a continuous rainfall of 100 mm per day.
2.14.3.10 Smoke and Heat Vents: Smoke and heat vents shall be provided in areas or
rooms containing hazardous materials exceeding the exempt amount of Table 3.2.5.
2.14.3.11 Standby Power: Standby power shall be provided in the occupancies where
Class I, II or III organic peroxides are stored. 2.14.4 Location on Property The location on property for Occupancy J shall conform to Sec 2.4.1 and Part 4. 2.14.5 Access and Exit Facilities and Emergency Escapes Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 of Chapter 1, Part 3, and Chapter 3, Part 4. 2.14.6 Lighting and Ventilation
2.14.6.1 All spaces and rooms customarily occupied by human beings shall be provided
with natural light by means of exterior glazing with an area of not less than 10 Percent of the floor area. Such rooms and spaces shall be provided with natural ventilation by means of exterior openings with an open able area not less than 5 Percent of the total floor area or artificial light and mechanically operated ventilation system as per provisions of this Code.
2.14.6.2 Ventilation in Hazardous Locations: The rooms, spaces or areas where
explosive, corrosive, combustible, flammable or highly toxic dust, mists, fumes, vapors or gases are stored or may be emitted due to the processing, use, handling or storage of materials shall be mechanically ventilated.
2.14.6.3 The mechanical ventilation of all hazardous uses shall be segregated or
separated from the ventilation of other areas. The emissions generated at work areas shall be confined to the area in which they are generated and shall be removed or discharged outside the building and preventive measures against back flow of such hazardous fumes or gases inside the building shall be installed.
2.14.6.4 Ventilation of Toilets: Toilets shall be provided with fully openable exterior
window of at least 0.3 m² in area or a vertical duct not less than 62500 mm² in cross- section for the first water closet, with additional 31250 mm² for each additional fixture or a mechanically operated exhaust system equipped to provide a complete change of air in every 15 minutes. Such system shall be connected to the outside air and the point of discharge shall be at least 1.0 m away from any other opening into the building.
2.14.6.5 Other requirements of water closets are specified in Sec 1.12.4 Chapter 1,
Part 3. 2.14.7 Sanitation All buildings or part of a building classified as Occupancy J shall conform to the provisions of Sec 1.16 of this Chapter and Part 8 of this Code. 2.14.8 Shaft and Exit Enclosures Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4. 2.14.9 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code.

2.14.10 Explosion Control

Explosion control, equivalent protective devices or suppression systems or barricades shall be installed to control or vent the gases resulting from deflagrations of dusts, gases or mists in a room or area, building or other enclosures to minimize structural or mechanical damage. Walls, floors and roofs separating a use from explosion exposure shall be designed according to the provisions of Chapter 1, Part 6. Explosion venting shall be designed in exterior walls or roof only. The venting shall be provided to prevent serious structural damage and production of lethal projectiles. The venting design shall recognize the natural characteristics and behaviors of building materials in an explosion. The vents shall be designed to relieve at a maximum internal pressure of 1.0 kPa but not less than the loads required by Chapter 2, Part 6. One or more of the following systems shall be installed to relieve explosion, where applicable: (a) Lightweight materials in walls (b) Light fastening devices with hatch covers (c) Light fastening with outward opening swing doors in exterior walls (d) Nonbearing walls with light ties The venting devices shall discharge vertically or horizontally directly to an unoccupied yard having a width of not less than 16 m on the same plot. The releasing devices shall be so located that the discharge end shall not be less than 3 m vertically and 6 m horizontally from window openings or exits in the same or adjoining buildings.

2.14.11 Special Hazard

Chimneys, vents and ventilation ducts shall be of noncombustible materials. All boilers, central heating plants, electrical rooms or hot water supply boiler shall be separated from the rest of the occupancies or uses by not less than 2 hour fire resistive construction. The devices that generate a spark, flame or glow capable of igniting gasoline shall not be installed or used within 0.5 m of the floor. Equipment or machinery that produces or emits combustible or explosive dust or fibers shall be provided with an approved dust collecting and exhaust system. The equipment or systems that are used to collect or process or convey combustible dust or fibers shall be installed with explosion venting or containment system. 2.15 Requirements For Occupancy K–Garage Buildings Buildings shall be classified as Occupancy K in accordance with Sec 2.1.15. Exception: Non-separated use mentioned in Sec 2.3.1. 2.15.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy K shall be limited to the type of construction set forth in Table 3.2.4 and Sec 2.4.4.2 and shall comply with the other provisions of Sec 1.8 Chapter 1 Part 3, Appendix F and Sec 2.4.2 to meet the requirements and limitations of height and area. With the exceptions mentioned in Sec 2.4.3, all garage floors shall be constructed with not less than 4 hour fire resistance materials.
2.15.1.1 Floors: The floors and spaces where motor vehicles are stored, repaired or
operated shall be of noncombustible, liquid-tight construction. Exception: In floors and areas where no repair works are carried out may be surfaced or waterproofed with asphaltic paving materials.
2.15.1.2 Spill Control: The floors containing hazardous repair or other works shall be
recessed a minimum of 100 mm so as to prevent flow of liquids to adjoining areas.
2.15.1.3 Drainage: The buildings and areas shall be provided with approved drainage
system to direct the flow of liquids to an approved location or room or area designed to provide secondary containment of the hazardous materials and fire protection water. The drains shall be designed with adequate slope and section to carry the design discharge of the sprinkler system. The material used in the drains shall be suitable for drainage of the storage materials. The quality of discharged liquids must attain approved level before discharging into the public sewer or natural stream or river.
2.15.1.4 Smoke and Heat Vents: Smoke and heat vents shall be provided in areas or
rooms containing hazardous materials exceeding the exempt amount of Table 3.2.5. 2.15.2 Location on Property Buildings of Occupancy K shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.15.3 Access and Exit Facilities and Emergency Escapes Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3, Chapter 3 Part 4 and Appendix F. 2.15.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy K shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3, Part 8. 2.15.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 Part 4. 2.15.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code.

2.16 Requirements For Occupancy L–Utility Buildings

Buildings shall be classified as Occupancy L in accordance with Sec 2.1.16. 2.16.1 Construction, Height and Allowable Area The buildings or parts thereof classified as Occupancy L shall be limited to the type of construction set forth in Table 3.2.4 and Sec 2.4.3, and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3, and Sec 2.4.2 to meet the requirements and limitations of height and area. 2.16.2 Location on Property Buildings of Occupancy L shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1. 2.16.3 Access and Exit Facilities and Egress System Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3 and Chapter 3 Part 4. 2.16.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy L shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3, Part 8. 2.16.5 Shaft and Enclosure Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 Part 4. 2.16.6 Fire Detector, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code. 2.16.7 Special Hazard
2.16.7.1 Since the nature of use of this occupancy involves hazard, special
consideration for maintenance and operational safety must be ensured. Depending upon the degree of hazard involved, this occupancy type may have separate and isolated structure. 2.16.7.2 Chimneys and vents and ventilation ducts shall be of noncombustible materials. All boilers, central heating plants, electrical rooms or hot water supply boiler shall be separated from the rest of the occupancies or uses by not less than 2 hour fire resistive construction. The devices that generate a spark, flame or glow capable of igniting gasoline shall not be installed or used within 0.5 m of the floor. Equipment or machinery that produces or emits combustible or explosive dust or fibers shall be provided with an approved dust collecting and exhaust system. The equipment or system that is used to collect or process or convey combustible dust or fibers shall be installed with explosion venting or containment system. 2.17 Requirements For Occupancy M–Miscellaneous Buildings Buildings shall be classified as Occupancy M in accordance with Sec 2.1.17. 2.17.1 General The buildings or parts thereof classified as Occupancy M shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the requirements of Sections

1.8 and 2.4.2 to meet the requirements of height and area limitations.

Any building or portion thereof that exceeds the limitations provided in this Chapter shall be classified in the occupancy group other than M that it most nearly resembles. 2.17.2 Location on Property The location on property for Occupancy M shall conform to Sec 2.4.1. 2.17.3 Access and Exit Facilities and Emergency Escapes Access and exit facilities for Occupancy M shall comply with the specification set in Sec

1.6 Chapter 3, Part 4.

2.17.4 Lighting, Ventilation and Sanitation All buildings or part of a building classified as Occupancy M shall conform to the provisions of Sec 1.16 Chapters 1 and 3, Part 8. 2.17.5 Shaft and Exit Enclosures Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with the requirements of Chapter 3, Part 4. 2.17.6 Fire Detection, Alarm, Evacuation and Extinguishment System All buildings shall conform to regulations set forth in Part 4 of this Code. Table 3.2.6: AZ List of Occupancy Classification Use or Occupancy Brief Description Occupancy Class/Sub-class A Adhesives manufacture Excluding manufacture of basic components G or J depending on nature of materials involved Advertising displays manufacture G Agricultural machinery manufacture Including repairs G Use or Occupancy Brief Description Occupancy Class/Sub-class Agriculture Without nuisance or sales limitation H Agricultural Small farm house, (limited to storage quantity) F Large farm house, storage quantity unlimited H or J Small grain processing unit, (limited to quantity) G Large grain processing unit, quantity unlimited G or J Aircraft manufacture (including parts) G or J depending on nature of materials and process involved Airports

MIXED USE (depending on detail requirement) Amusement parks, children’s (See children’s amusement parks)

Amusement park activities I Animal Animal hospitals F Animal pound (for stray and lost animal) H Animal crematorium G Killing establishments, for retail sales F Slaughtering, processing and packing G Antique stores F Apartments (see residential) in walkup buildings A In high rises A in housing complex A Apartment hotels A5 Apparel (See clothing) Use or Occupancy Brief Description Occupancy Class/Sub-class Appliances Electrical appliance Manufacturing G Television, radio, phonograph or household appliance stores, (Limited as to floor areas) F Television, radio, phonograph or household appliance stores, (Unlimited) F Household appliance repair shops F Arenas, auditoriums, or stadiums See Assembly (Limited as to capacity) I See Assembly (Unlimited) I Art Galleries Commercial (sales included) F With exhibition open to public viewing for limited period (sales included) I Art goods manufacture, religious temple or church, excluding foundry operations G Art metal craft shops F Art needle work Six occupants or less Non-separated use to A1 and A2 Occupancy More than six occupants (see industrial) G Artist’s supply stores F Asphalt or asphalt products Manufacture J Assembly Large assembly with fixed seats I1 Small assembly with fixed seats I2 Large assembly without fixed seats I3 Small assembly without fixed seats I4 For sport facilities I5 Athletic equipment manufacture G Use or Occupancy Brief Description Occupancy Class/Sub-class Athletic goods stores F Auctions rooms, open to public I Auditoriums See assembly I Automatic laundries G Automobiles Dead Storage H Driving Schools E Glass or mirror shops F Washing K Manufacture, including parts, or engine rebuilding J Rental establishments K Repairs, body K Repairs, without body repairs K Sales open or enclosed K Seat cover or convertible top establishments, selling or installation F Showrooms, no repair services K Supply stores, no repair services F Tire sales establishments, limited to quantity F Tire sales establishments, unlimited J Wrecking establishments G Automotive service stations Limited as to total area K Unlimited… K Awnings Custom shops H Manufacture, with no limitation on production or on floor area G Use or Occupancy Brief Description Occupancy Class/Sub-class B Bakeries Home-made, six or less occupants (baking included) non-separated use to main occupancy Large scale, more than six occupants (baking included) G Sales only F Banks, Including drive-in banks E Banquet halls I Bar, alcoholic I Barber shops F Barns H Barracks (See residential) A4 Baths, steam I Beaches, commercial Not applicable Beauty parlors F Beverages Bottling works G Manufacture, Alcoholic J Non-alcoholic G Bicycle Manufacture G Rental or repair shops F Sales F Billiard parlors I Blacksmith shops small scale (limited to six occupants), repair or making F Unlimited G Blueprinting establishments drawing printing G Boarding houses (See residential) A Borstals C Boatels A Use or Occupancy Brief Description Occupancy Class/Sub-class Boats or ships Bailer works at port or dock J Breaking J Building or repair, for boats less than 200 ft. in length J Building or repair, for boats 200 ft. or more in length J Docks, for small pleasure boats Not applicable Fuel sales, open or enclosed Un- restricted as to location F Restricted as to location J Rentals opened or enclosed F Sales opened or enclosed F Showrooms, with no repair services.. F Storage, repair, or painting, including the incidental sales of boats, boat parts, or accessories, with restrictions on boat size and setbacks G Bone distillation G or J depending on process or material used Botanical garden structures M Book Binding (see printing) Hand binding or tooling G Store F Bottling works, for all beverages G Bowling alleys Limited as to number of lanes I Unlimited I Breweries G Brick manufacture J Brush or broom manufacture G Use or Occupancy Brief Description Occupancy Class/Sub-class Building materials sales open or enclosed, limited as to lot area F Yards, for sales, storage, or handling, open or enclosed, unlimited as to lot area except in the case of lumber yards F Bungalow (See residential) A Business Offices B1 Research and testing laboratories B2 Essential services B3 Bus stations With less than 10 berths K (bus area) and I (passenger area) With 10 or more berths MIXED (as per detail requirement including K and I) Bus stops see Bus stations Business machines Manufacture G Small, repair shops F Stores, sales, or rentals.. F Business schools or colleges B Buying house (garments) storage restricted to sample E C Café Six persons or less Non-separated use to main Occupancy More than six persons (see mercantile) F Cafeteria With commercial kitchen MIXED (G and I) Without commercial kitchen I Camera and photo equipment Manufacture G Camps, overnight or outdoor day MIXED (A, I and other depending on the nature of use) Use or Occupancy Brief Description Occupancy Class/Sub-class Candy stores F Canneries, including food products J Canteen With or without cooking facility I Canvas or canvas products manufacture G2 Cargo terminal containing low fire-risk materials H containing moderate fire-risk materials H containing high fire-risk materials J Carnivals, temporary I5 Carpentry shops G Carpet Cleaning establishments… J or G depending on the nature of materials involved Manufacture G Carpet, rug, linoleum or other floor covering stores Unlimited F Carport Roofed wall less shelter for car K or H depending on the nature of use Automated mechanical parking K or H depending on the nature of use Catering establishments Commercial kitchen G Office E Storage, open or enclosed H Storage for temporary structure’s fabrication material J Cattle shed, stables H Cement manufacture G2 Cemeteries H Ceramic products Manufacture G or J based on nature of material used Display and sales F Use or Occupancy Brief Description Occupancy Class/Sub-class Chamber, doctors’ or dentists’, (outpatient only) 50 or less occupants E above 50 occupants D Charcoal manufacture G Chemicals Compounding or packaging G or J depending on nature of materials involved Manufacture G or J depending on nature of materials involved Child care home C Child care institution C Children’s amusement parks Small I Medium size I Large size I Unlimited as to size I Churches, with fixed pews (See Assembly with fixed seats) I Cigar stores F Cinema hall (See Assembly with fixed seats) I Cineplex (See Assembly with fixed seats) I Circuses, temporary (See Assembly) I Class room School, college or university B Clay manufacture G Clay pits Not applicable Cleaning or cleaning and dyeing establishments (See dry cleaning)… Clinics With inpatient D Only outpatient, limited to quantity (see chambers, doctors’ or dentists’) Only outpatient, unlimited D With diagnostic facilities (see diagnostic facilities) Government community clinic E Use or Occupancy Brief Description Occupancy Class/Sub-class Coaching centre (See educational facilities) B Cold storage H Composite textile mill G or J depending on nature of material and process used Cottage industries Small, fifty or less workers (see industrial facilities) G1 Large, more than fifty workers… (see industrial facilities) G1 or G2 depending on the nature of material and process used Clock Manufacture G Stores or repair shops F Clothing Accessory stores F Custom manufacture or altering for retail F Manufacture G or J depending on nature of the material involved Rental establishments F Store, Limited as to floor area F Store, Unlimited F Clubs Non-commercial (members only) Including accommodation MIXED (A and I) Night-club I All types except those with outdoor swimming pools Clubs, for public use Excluding accommodation I Including accommodation MIXED (I and A or other occupancies depending upon nature of use) Clubs, Sporting MIXED (I and A or other occupancies depending upon nature of use) Use or Occupancy Brief Description Occupancy Class/Sub-class Coal Products manufacture J Sales, open or enclosed, Limited as to plot area J Unlimited (see coal storage) J Storage, open or enclosed J Coin stores F Condensed and powdered milk Manufacture J Coke products Manufacture J Colleges or universities See educational facilities B Colony, government or non-government MIXED (A and other occupancies depending on use) Commercial building (see business and/or mercantile) Commercial parking garages or plots (See garages) K Community centers With commercial kitchen MIXED (G and I) Without commercial kitchen I Concrete batching G Concrete products manufacture G Construction machinery Manufacture, including repairs G Container terminal H or J (According to the hazard classification regulation of the port authority) Contractors’ establishments Electrical, glazing, heating, painting, paper hanging, plumbing, roofing, or ventilating F Contractors’ yards Not applicable Convalescent homes (See nursing homes) Use or Occupancy Brief Description Occupancy Class/Sub-class Convents MIXED (A, B and I) Cork products Manufacture G Cosmetics or toiletries Manufacture.. J Costume rental establishments F Cottage, tourist (See residential) A5 Cotton ginning or cotton wadding or liner manufacture J Court houses I Crate manufacture G or J depending on the material and process involved Crematoriums Animals. J Human. MIXED (J and I) Cultural center Mixed (depending on detail requirement) D Dance halls Public I Dance School A Dance studios (see studios) Day camps, outdoor I Day care Centre With six or less children Non-separated use to Residential Occupancy More than six children C Decorator’s establishment Office E Storage, separated H or J depending upon the material involved Defense Buildings, for critical national defense capabilities Not Applicable Delicatessen stores (See food stores) F Use or Occupancy Brief Description Occupancy Class/Sub-class Dental Instruments manufacture G Laboratories (See laboratories, medical or dental) Department stores not exceeding 300 m² F1 more than 300 m² F2 Diagnostic facilities, medical Outpatients only D Diaper supply establishments H Disinfectants manufacture G Dispensaries Attached to hospital L See drug store F Dormitories Universities or colleges (above 12 grade) A Schools (12 grade or below) C Drafting instruments Manufacture G Dressmaking shops, custom F Drinking places, non- alcoholic (See cafe) Drive-in theaters I Drug stores F Dry cleaning or clothes pressing establishments Limited as to floor area, solvents and machine capacity G or J depending on the process and quantity of material used Dry cleaning or cleaning and dyeing establishments Without restrictions G or J depending on the process and quantity of material used Dry Cleaning, using other than flammable liquids in cleaning or dyeing operations G Use or Occupancy Brief Description Occupancy Class/Sub-class Dry goods stores Limited as to floor area F Unlimited F Dumps Not applicable Dyeing facilities/ industries J E Eating or drinking places With restrictions on entertainment (see Assembly) I Without restrictions on entertainment or dancing but limited to location in hotels (see Assembly) I Without restrictions (See assembly) I Eco park structures MIXED (depending upon the nature of use) Educational facilities Up to higher secondary level B1 Training and above-higher-secondary education B2 Pre-school facilities B3 Electric Power or steam generating plants G Substations, Public transit or railroad G Substations, as part of public distribution system G Substations, low to medium voltage step down, at consumers’ end L Electrical Appliance Manufacture G or J depending upon the process or material to be used Stores (including television, radio, phonograph or household appliances) F Contractors (See contractors’ establishments) Equipment assembly, not including electrical machinery G Supplies, manufacturing G Use or Occupancy Brief Description Occupancy Class/Sub-class Electronics manufacturing J Electrolysis works J Electrotyping or stereotyping Limited to quantity F Unlimited (see printing) G Embassy or High- commission or Consulate MIXED (depending on detail requirement) Engine including rebuilding or reconditioning J Engraving or photo- engraving Limited to quantity F Unlimited (see printing) G Excelsior manufacture J Exhibition hall See assembly I Exterminators See pest control F F Fabric stores F Factory G or J (depending on process and material involved) Fairs, temporary MIXED (I and F) Feathers Bulk processing, washing, curing, or dyeing J Products manufacture, except washing , curing or dyeing J Felt Bulk processing, washing, curing, or dyeing G Products manufacture, except washing, curing or dyeing G Fertilizer manufacture J Field hospital, temporary With provision for ambulance access (to parks and play grounds) E Filling stations (See refueling station) B Use or Occupancy Brief Description Occupancy Class/Sub-class Film, photographic Manufacture G Fire Stations E Fish products, packing or processing G Fishing tackle or equipment rental or sales F Flats (see residential) A In walkup buildings A In high rises A in housing complex MIXED (A and other occupancies) Florist shops F Food Products processing, except meat slaughtering or preparation of fish for packing G Stores, including supermarkets, grocery stores, meat markets, or delicatessen stores F Foundries Ferrous or non-ferrous G or J (depending on process and material involved) Fraternity houses (See colleges or universities) Freight depot See storage and hazardous buildings H and/or J Frozen food lockers J Fuel briquettes manufacture G Fuel sales, open or enclosed Limited up to exempted quantity F Unlimited, See coal storage or petroleum storage J Funeral establishments I Fungicides manufacture G Use or Occupancy Brief Description Occupancy Class/Sub-class Fur Goods manufacture, not including tanning or dyeing G Tanning, curing, finishing, or dyeing J Furniture Custom shop, floor area of 100 m² or less F Custom shop, floor area over 100 m² G Manufacture J or G depending upon nature of materials involved Store, Limited as to floor area F Store, Unlimited F Furriers shops, custom F Freight depot H or J depending on the nature of material involved G Garages Parking garage K1 Private garage K2 Repair garage and show-rooms K3 Garbage incineration or reduction G Garden shed M Garden supply stores F Gardens, truck (See agriculture) Garments industries G Gas, fuel Manufacture J Distribution regulatory system (DRS) G Gas manufacture for Medical purpose J Hot-works (welding) J Gasoline service stations (See refueling stations) Gelatin manufacture G Use or Occupancy Brief Description Occupancy Class/Sub-class Generating plants, electric or steam G Gift stores F Glass Cutting shops F Manufacture G Products manufacture from previously manufactured glass G Glazing contractor’s establishment (See contractors’ establishments) F Glue manufacture G Godown See storage buildings Golf Courses Not applicable Courses, miniature I Driving ranges I Grain Milling or processing J Storage J Graphite or graphite products Manufacture G Gravel pits Not applicable Grocery stores F Group homes Segregation of occupants on the basis of age group and disabilities (See institutional) C Gypsum production industry J Gymnasiums Less than 300 occupants I 300 or more occupants I Commercial without spectator gallery (max 50 occupants) Use or Occupancy Brief Description Occupancy Class/Sub-class H Hair Bulk processing, washing, curing, or dyeing G Products manufacture (except washing, curing, or dyeing) G Products manufacture, custom G Hall, for incidental show (picture, drama, theatre) (See assembly) I Hardware Manufacture G Stores F Bodies manufacture G Repair shops F Hazardous buildings Explosion-hazard building J1 Chemical-hazard building J2 Biological-hazard building J3 Nuclear-hazard building J4 Health centers With inpatient D Without inpatient (not more than 50 occupants) E Government operated health centers E or D (depending upon the facilities) Healthcare facilities Normal medical facilities D1 Emergency medical facilities D2 Health club I Heating contractor’s establishment (See contractors’ establishments) Heat, ventilation and air-conditioning equipment showrooms Without repair facilities F Heliports G Hemp products manufacture G Use or Occupancy Brief Description Occupancy Class/Sub-class High Commission See embassy Home for care of the old and infirm (see institution) of mentally disabled (see institution) Home office Not more than 6 occupants Non-separated use of Occupancy A Hosiery manufacture G Hospital, except animal hospital As part of disaster preparedness program D Casualty unit D Emergency unit D Non-profit or voluntary, and related facilities D Proprietary and related facilities D Hostels For adults A For children C Hotels Transient A Apartment hotel A Starred hotel MIXED Household Appliance repair shops F Appliance stores (See appliances television, radio, phonograph, or household appliance stores) F Housing, complex multi-storied MIXED (see appendix) Housing, cluster MIXED (see appendix) Housing, low-income MIXED (see appendix) Housing, minimum standard MIXED (see appendix) Housing, rehabilitation MIXED (see appendix) Use or Occupancy Brief Description Occupancy Class/Sub-class I Ice cream stores F Ice Manufacture, dry or natural G or J (depending on the process or material used) Sales, open or enclosed Limited as to lot area F Unlimited F Incineration or reduction of garbage, offal, or dead animals G Indoor facility, for amusement park I Industrial buildings Low-hazard Industries G1 Moderate-hazard Industries G2 Infirmaries C Ink or inked ribbon manufacture G or J depending on nature of materials involved Inns See residential A Insecticides manufacture G or J depending on nature of materials involved Institution For care of children C1 Custodial, for physically capable adults C2 Custodial, for physically incapable adults C3 Penal or mental, for children C4 Penal or mental, for adults C5 Institutions, philanthropic or non- profit With sleeping accommodations A Without sleeping accommodations Use or Occupancy Brief Description Occupancy Class/Sub-class Interior decorating establishments Limited as to floor area for processing, servicing, or repairs F Unlimited, see furniture, textiles or upholstering F Irradiation plant J J Jail see prisons Jewelry Manufacture G Costume G From precious metals G Shops F Junk Yards Not applicable Jute products manufacture G or J (depending on quantity or process) Juvenile correctional center For children (see assembly) K Kennels H Kindergarten See educational facilities B Knitwear industries G2 L Laboratories Medical or dental, for research or testing, with limitations on objectionable effects E Research, experimental, or testing, unlimited (G or J) and H depending on process or material used in compliance with safety standards Radiological laboratory, see radiological facilities Pathological laboratory G (in compliance with safety standards) Use or Occupancy Brief Description Occupancy Class/Sub-class Microbiological laboratory, for diagnostic facility G or J depending on process or material used in compliance with safety standards Microbiological laboratory, for research G or J depending on process or material used in compliance with safety standards Microbiological laboratory, for academic facility G or J depending on process or material used in compliance with safety standards Lampblack manufacture G Laundries, with no limitations on type of operation G Laundry establishments, hand or automatic self- service G Lavatory, public see public toilet Leather Tanning, curing, finishing or dyeing J Goods stores F Products manufacture G Libraries Reading area (see assembly) I Stack area (see storage) H Reading and stack area combined MIXED (I and H) Lillah boarding For children (see institutional) C For adults (see residential) A Linen supply establishments Linoleum Manufacture J Stores (See carpet stores) Use or Occupancy Brief Description Occupancy Class/Sub-class Liquor stores, package F Livestock Storage, more than six castles H Slaughtering or preparation for packing G Loan offices E Locksmith shops F Lodging See residential A Luggage Manufacture G Stores F Lumber Processing or woodwork, bulk G Sales, Limited as to lot area G Sales, Unlimited G Yard, Limited as to lot area G Yard, Unlimited G M Machine Shops including tool, die or pattern making G Tools manufacture G Machinery Manufacture or repair, Heavy G or J depending on material and process Miscellaneous or electrical equipment G or J depending on material and process Rental or sales establishments F Repair shops F Machines, business (See business machines) Madrasa (See institution) Manure storage H Markets Retail, including meat (See mercantile) F Wholesale, produce or meat (See mercantile) F Masseurs F Use or Occupancy Brief Description Occupancy Class/Sub-class Matches manufacture J Mattress manufacture, rebuilding or renovating J Meat Markets, Retail (See food stores) F Markets, Wholesale F Slaughtering or preparation for packing G Medical Appliances, Custom manufacture G Appliances, Manufacture G Stores F Instruments, manufacture G Laboratories (See laboratories, medical) Offices or group medical centers, Limited as to location within building E Offices or group medical centers, Unlimited E Meeting halls See Assembly I Mess houses (See residential) Metal Fabrication industry J Metal Assembly industry J Metals manufacture Alloys or foil, miscellaneous G Casting or foundry products, heavy G Finishing, plating, grinding, sharpening, polishing, cleaning, rust proofing, heat treatment, or similar processes G Ores reduction or refining G Products treatment or processing G Reduction, refining, smelting, or alloying G Stamping or extrusion G Treatment or processing G Use or Occupancy Brief Description Occupancy Class/Sub-class Mental institution Without detention facilities D Mental hospitals (See institution) C Mercantile Small shops and markets F1 Large shops and markets F2 Refueling station F3 Mill (See industrial and/ or hazardous buildings) G or J (depending on material or process) Mill works, and woodworking, wood distillation and particle boards manufacturing J Millinery shops F Mining machinery manufacture Including repairs G Mirror silvering shops G Miscellaneous buildings Special structures M1 Fences, tanks and towers M2 Monasteries MIXED Monument Sales establishments, with incidental processing to order F Works, with no limitations on processing G Mosque (See assembly) I Motels (See residential) A Motion picture production and filming facilities MIXED (G and other Occupancies as required) Motorcycles Manufacture G Repairs, body G Repairs, except body repairs G Sales open or enclosed F Showrooms, with no repair services (See garage) K Motor freight stations See truck terminals Use or Occupancy Brief Description Occupancy Class/Sub-class Motor vehicles Dead storage H Moving or storage offices, Limited as to storage K Unlimited K Movie theatre See assembly I Museums See assembly I Music stores F Music studios See studios Musical instruments Manufacture, Excluding pianos and organs G1 Including pianos and organs… G2 Repair shops… G1 N Newspaper publishing MIXED (G and E) Printing G Office E Newsstands, open or closed F Novelty products manufacture G Novitiates… See institution A Nuclear medicine facilities see radiological facilities Nuclear plant J Nurseries See agriculture Nursing homes Philanthropic or non-profit C or D depending on the type of occupants and nature of use Private C or D depending on the type of occupants and nature of use Nursery schools See pre-school B Use or Occupancy Brief Description Occupancy Class/Sub-class O Oakum products manufacture G Office equipment or machinery repair shops F Office or business machine stores sales or rental F Offices General E Business, professional or Governmental (see business occupancy) E Dental, medical, or osteopathic (See medical offices) E Wholesale, with storage restricted to samples (see business occupancy) E Offices, small Architect’s/engineer’s/ consultant’s (Limited to six occupants) Non-separated use of Occupancy A Architect’s/engineer’s/consultant’s ( more than six occupants) E Oil cloth manufacture J Oil sales, open and enclosed Limited as to lot area F Unlimited (See petroleum or petroleum products storage) J Old home See institution C Optical Equipment manufacture G Goods manufacture G Orphanage See institution C Optician or optometrist establishments F Orthopedic Appliances, Custom manufacture G Manufacture G Stores F Instruments, manufacture G Osteopathic offices (See medical offices) Use or Occupancy Brief Description Occupancy Class/Sub-class P Packing or crating establishments G2 Packing materials manufacture G2 Pagoda See Prayer hall Paint Manufacture J Stores, limited to quantity F Stores, unlimited H Painting contractors (See contractors’ establishments) Paper Mills (See wood pulp or fiber) G Products manufacture G Stock companies H Paper-hanging contractors (See contractors’ establishments) Parish houses A Parks, public or private With provision for emergency vehicle access as part of disaster preparedness program Not applicable Park structures M Parking garages, public See garage, parking K Parking lots, public See garage, parking K Passenger stations and terminals Small, passenger station MIXED (depending on nature of use) Large, passenger station or terminal MIXED (depending on nature of use) Passenger and freight terminal MIXED (depending on nature of use) Peat storage H Perfumed or perfumed soaps compounding only, not including soap manufacture J Use or Occupancy Brief Description Occupancy Class/Sub-class Pest control Exempted quantity only F Pet shops F Petrol pump See refueling station F Petroleum or petroleum products Refining J Storage and handling J Pharmaceutical products manufacture G or J depending on nature of materials used Philanthropic, religious or non-profit activities MIXED (depending on nature of use) Phonograph Repair shops F Stores (See appliances) F Photocopying and book binding Binding limited in quantity F Photographic Developing or printing establishment, Retail F Developing or printing establishment, Wholesale, Limited as to floor area H Developing or printing establishment, Wholesale, Unlimited H Equipment, Manufacture (film) J Equipment, Manufacture (except film) G Stores F Studios F Supply stores (limited to exempted quantity) F Photostatting establishments F Physical culture establishments I Picture framing stores F Plants, Industrial G Plants, Refrigeration G Use or Occupancy Brief Description Occupancy Class/Sub-class Plastics Products, manufacture J Raw, manufacture J Plate making (See printing) Playgrounds With provision for emergency vehicle access as part of disaster preparedness program I Plots, parking (See parking lots, public) Plumbing Contractors’ establishments F Equipment manufacturer (See tools or hardware manufacturing) Showrooms, without repair facilities F Police Stations E Pool halls I Porcelain products manufacture G Post offices E Poultry Storage (live) H Killing establishments, for retail sales on the same zoning lot only G Packing or slaughtering G Power plant G Power stations As part of national grid power distribution system E At consumer’s end L Prayer hall See assembly I Precision instruments manufacture Optical equipment, clocks, or similar products G Medical, dental, or drafting instruments, optical goods, or similar products G Pre-school facilities See educational Use or Occupancy Brief Description Occupancy Class/Sub-class Press club, for journalist I Press, printing See printing Primary schools See educational Printing Custom G Limited as to floor area G Unlimited G Printing, publishing, dyeing and printing industries J Prisons See jail C Produce or meat markets, wholesale F Psychiatric sanatoria With detention facilities (see institution) Public auction rooms MIXED (F and/or I) Public transit yards Not applicable Publishing With printing G Without printing E Pumping stations Water or sewage (for city supply system) G Dedicated to consumer U Q Quarter, Staff Government or non-government A or Mixed (See appendix) R Racetracks I Radio Appliance repair shops F Stores F Studios, with less than six occupants Non-separated use to main Occupancy Studios, without transmission tower E Studios, with transmission tower (see radio station) Towers, non-accessory M Use or Occupancy Brief Description Occupancy Class/Sub-class Radio station Mixed (depending on the type of use) Radiological facilities, medical In compliance with the standard of atomic energy commission D Radioactive waste disposal services J Railroad Equipment manufacture, including railroad cars or locomotives G or J depending on the material and hot-work used Passenger stations I Right-of-way Not applicable Substations Small or medium size G Large G Railroads, including rights-of-way, freight terminals, yards or appurtenances, or facilities or services used or required in railroad operations, but not including passenger stations Not applicable Rail station Mixed (depending on the type of use) Record stores F Recreation centers, non-commercial I Recreation piers See assembly I Recreational vehicles manufacturing J Rectories A Reducing salons I Reformatories See institutional facilities Refreshments stand, drive-in I Refrigerating plants G Use or Occupancy Brief Description Occupancy Class/Sub-class Refueling station Petroleum product storage within exempted quantity E Refuse incinerators J Religious or church art goods manufacture G Research establishment dealing with non-hazard or low hazard materials only E Residences Single-family detached A One-family semi-detached or two- family detached or semi-detached A Boarding or rooming houses A Rest homes (See nursing homes) Residential Single family dwelling A1 Two family dwelling A2 Flats or apartments A3 Mess, boarding house, dormitories and hostels A4 Hotels and lodging houses A5 Rest Houses Restaurant Dining area I Performing area, limited I Kitchen and storage L Reviewing stand I Riding academies, open or enclosed E and H Roofing contractors’ establishments F Rooming houses See residential A Rubber Processing or manufacture, natural or synthetic J Products manufacture (excluding all natural or synthetic rubber processing) J Rug stores (See carpet stores) Use or Occupancy Brief Description Occupancy Class/Sub-class S Sail-making establishments F Salvage storage H Sand pits Not applicable Saloon, hair dressing F Sanatoriums With detention facilities (see institution) C Without detention facilities D Sawmills G Scenery construction G School (see educational) Dormitories, for children C Nursery, kindergarten, elementary or secondary schools B Trade or other schools for adults, limited as to objectionable effects B Trade schools for adults, unlimited B For physically challenged, without accommodation B For mentally challenged, without accommodation B Scrap metal, paper and rag storage H Secondary school See educational B Seed stores F Seminar halls For 50 or more occupants, See assembly I Seminaries B Settlement houses (see housing) MIXED (A and other Occupancy depending on the nature of use Sewage Disposal plants G Pumping stations G Use or Occupancy Brief Description Occupancy Class/Sub-class Sewing machine stores, selling household machines only F Ship chandlers, candle shops F Ship or boat building or repair yards For ships 200 ft. in length or over G Shipping, waterfront Not applicable Shoes Manufacture G or J depending on the process and material involved Repair shops F Stores F Shops see definition F or G (depending on the process and material involved) Shop-house mixed occupancy (A and F) or (A, F and G) Sign painting shops Limited as to floor area G Unlimited G Silk processing and spinning J Silo, for storage of grain H Silver plating shops, custom G Silverware manufacture, plate or sterling G Sisal products manufacture J Skating rinks, roller Indoor I Outdoor I Slag piles Not applicable Use or Occupancy Brief Description Occupancy Class/Sub-class Slaughtering of animals or poultry G Soap or detergents Manufacture, including fat rendering J Packaging only G Soldering shops G Solvent extracting J Sorority houses (See hostel) A Sports centre I Sporting equipment manufacture. G Sporting goods stores F Stable for horses H Stadiums Indoor or outdoor, with access for emergency vehicle as part of disaster preparedness program I Staff quarter see quarter, staff Stamp stores F Station Rail, bus, air and water way MIXED (I and other Occupancy depending on the nature of use Stationary stores F Statuary, mannequins, figurines, religious or church art goods manufacture, excluding foundry operations G Steel products Miscellaneous fabrication or assembly (without hot-work) G Structural products manufacture J Stock yards or slaughtering of animals or poultry G Use or Occupancy Brief Description Occupancy Class/Sub-class Stone processing or stone products G Storage buildings Low-fire-risk storage H1 Moderate-fire-risk storage H2 Storage facilities Wholesale (see storage buildings) H Offices, limited to quantity Non-separated use For cotton/jute/ paper/textile J Stores See definition F Students’ halls of residence For children C For adults A Studios Music, dancing, or theatrical I Radio (see radio studio) Television, with spectator MIXED (I, E or G) Television, without spectator MIXED (depending on nature of material and process involved) Sugar Production and Refining J Super market See mercantile F Swimming pools Commercial I Non-Commercial (See clubs) I T Table tennis halls See assembly I Tailor shops, custom F Tanning (See leather or fur) J Tapestries manufacture G Tar products manufacture G Taxidermist shops F Telegraph offices E Use or Occupancy Brief Description Occupancy Class/Sub-class Telephone exchanges or other communications equipment structures E Television Repair shops F Stores (See appliances) F Studios (see television studios) Towers, non-accessory M Television station See business MIXED (E3 with other Occupancies according to detail requirement) Temple See prayer hall Tennis courts, indoor I Terminal facilities at river crossings for access to electric, gas, or steam lines G Test laboratory involving low hazard material E Textiles Bleaching (see industrial) G Products manufacture (see industrial) G Spinning, weaving, manufacturing, dyeing, printing, knit goods, yarn, thread, or cordage (see industrial) G Textile industries and jute mills including canvas, cotton cloth, bagging burlap, carpet and rags (see industrial) J Theater See assembly I Theaters, drive-in (See studios) Theatrical studios without spectator G Tile Manufacture G Tire sales establishments Including installation services, Limited to quantity F Including installation services, unlimited quantity J Use or Occupancy Brief Description Occupancy Class/Sub-class Tobacco Curing or manufacture, or tobacco products manufacture J Stores (retail) F Toilet, public L Toiletries manufacture G or J depending on the material and process involved Tool or hardware manufacture See industries G Topsoil storage See storage H Tourist cabins See residential A Towel supply establishments F Toys Manufacture G Stores F Trade or other schools for adults Limited as to objectionable effects (see educational) B Unlimited (see educational) B Trade expositions Limited as to rated capacity I Unlimited I Trailer, truck, bus Manufacture, including parts G or J depending on the material and process involved Repairs, body G or J depending on the material and process involved Sales open or enclosed F Showrooms, with no repair services F Training center lecture based, limited to quantity (see educational facilities) E1 or B2 vocational or demonstrative (see educational facilities) B2 Transit substations Small or medium size G Large G Use or Occupancy Brief Description Occupancy Class/Sub-class Transport terminal Small or medium size MIXED depending on nature of use Large MIXED depending on nature of use Travel agency (see business) E Travel bureaus (see business) E Truck Manufacture (including parts) or engine rebuilding G or J depending on the material and process involved Repairs, body G Repairs, except body repairs G Sales open or enclosed F Showrooms, with no repair services F Trucking terminals or motor freight stations, Limited as to lot area K1 Trucking terminals or motor freight stations, Unlimited K1 Tutorial homes More than six occupants (see educational) B Turpentine manufacture J Typewriter stores F Typewriter or other small business machine repair shops F Typography (See printing) U Umbrellas Manufacture G Repair shops F University See educational facilities B2 Upholstery Manufacturing J Bulk, including shops not dealing directly with consumers J Shops dealing directly with consumers, retail F Utility L Use or Occupancy Brief Description Occupancy Class/Sub-class V Variety stores Limited as to floor area F Unlimited F Varnish manufacture J Vehicles Dead storage of motor H Manufacture, children’s G Storage, commercial or public utility, open or enclosed K Venetian blind, window shade, or awning Custom shops, limited as to floor area F Manufacture, with no limitation on production or on floor area J or G depending upon nature of materials involved Ventilating contractors (See contractors’ establishments) F Ventilating equipment showrooms Without repair facilities F Video games shop F Vihara, Buddhist with occasional or regular assembly mixed use W Wallpaper stores Limited to quantity H Warehouses H or J (depending on the nature of material stored) Watch or clock stores or repair shops F Watch making G Waterfront shipping Not applicable Water pumping stations At distributor’s end G At consumer’s end L Water tank tower M Wax products manufacture G Use or Occupancy Brief Description Occupancy Class/Sub-class Weaving, hand Up to six hand-weaving machines Non- separated use to main Occupancy More than six hand-weaving machines G Wedding chapels See assembly I Welding shops Arc welding only G Gas welding within exempted quantity G or J depending upon the quantity of material and process Welfare centers Wholesale establishments H or J depending upon the nature of material Wholesale offices or showrooms, with storage restricted to samples E Window manufacture G Window shades Custom shops, limited as to floor area F Manufacture, without limitation on production or on floor area G Wood Bulk processing or woodworking G Distillation G Products manufacture G Pulp or fibre, reduction or processing, including paper mill operations G Sales, open or enclosed, Limited as to lot area F Unlimited (See lumber yards) F Woodworking shops, custom J or G depending upon nature of materials involved Wool scouring or pulling G Workshops With hot-works J Without hot-works G Use or Occupancy Brief Description Occupancy Class/Sub-class X X-ray facilities See radiological facilities Y Yard Not applicable Yard, ship See ship or boat building or repair yards Yarn, manufacturing G or J depending on the quantity (see Table 3.2.5) Z Zoo structures M ** The occupancy classification for any project, not included in this list, shall be determined through the following process: i. The functional requirements of the unidentified occupancy shall be compared with the Occupancy use type, classification, sub-classification categories and descriptions to match with the given occupancies to find the most similar Occupancy, ii. If process (i) fails to determine the Occupancy, the project will be referred to the Board of Appeal constituted as per directives of Part 2 Chapter 2. The Board of Appeal shall determine the Occupancy, and iii. The decision of Board of Appeal shall be considered as an explanatory material of this Code and shall be added as addendum to this Code. For any future projects of similar nature this addendum will suffice and need not be referred to the Board of Appeal again.