4.4.1 and size of pipes shall be as per provisions of this Code or on the basis of the
hydraulic design of the system to maintain flow rate and duration of water discharge. 4.2.2 Water Sources for Fire Protection Flow rate and duration of discharging water required for interior fire extinguishment of a building shall be supplied from one or any combination of the following sources. Table 4.4.1: Fire Protection Flow Requirements* Building Type** Sprinkler System (litre/min.) Standpipe and Hose System (litre/min.) Duration in Minutes for Building Heights Up to 51 m 51 m to 102 m Above 102 m Light hazard- I Light hazard- II Ordinary hazard- I Ordinary hazard-II Ordinary hazard-III
Notes:
- See also Sec 4.2.2.3. ** Values will be for one riser serving floor area of 1000 m2. Light hazard-I : Occupancy groups, A1, A2, A3, E1 Light hazard-II : Occupancy groups, A4, A5, B, C, D,E2, E3, I2, I4, F1 Ordinary hazard-I : Occupancy groups, I1, I3, I5, F2, F3, G1 Ordinary hazard- II : Occupancy groups, G2 , H1 Ordinary hazard- III : Occupancy groups, H2 Extra hazard : Occupancy group J-pressure and flow requirement for
4.2.2.1 Direct connection to water main
For continuous water supply (public water supply system or private system) with sufficient quantity and pressure to feed and discharge firefighting equipment during peak demand period, direct connection of firefighting system to the water main may be adopted, Figure 4.4.1. In this case guidelines specified in NFPA 22 are to be followed. Connection Water Supply Line Check Valve Siamese Stand pipe Basement To Sprinkler System (optional) Hose station Figure 4.4.1 Typical diagram for standpipe and hose system connected directly to the water main4.2.2.2 Roof gravity tanks
Any elevated structure holding a water reservoir or water tank or in any level within a building and having downward supply pipelines shall be termed as gravity tank only when a water reservoir located on a roof of a building shall be termed as roof gravity tank. For water supply system with inadequate quantity or pressure during peak demand period but with sufficient pressure to feed roof tank, a roof gravity tank may be provided. In that case any one of the following steps shall be followed. (a) If only the static height of the roof gravity tank is used to feed and discharge the firefighting equipment, the height of the roof gravity tank from the top floor must be sufficient to create minimum required pressure at the top floor hydrant point. The minimum pressure at hose outlet for standpipes supplying a 50 mm or larger hose shall be at least 300 kPa. This minimum pressure for standpipe system supplying first aid hose (38 mm nominal) shall be at least 200 kPa. This minimum pressure for combination of sprinkler and hose pipe system shall be 600 kPa. To maintain the above required pressure the vertical distance of the roof gravity tank from the top floor hydrant point shall be at 31 m, 20.5 m and 62 m respectively, Figure 4.4.2. (b) If the vertical distance between the roof gravity tank and the top floor hydrant point cannot be maintained for gaining required pressure and discharge, fire pump of required size and number shall be installed with standard manufacturer recommended suction and delivery connections, Figures 4.4.3 and 4.4.4. Figure 4.4.2 Typical diagram showing required static head of gravity roof tank with adequate domestic and fire reserve4.2.2.3 Storage tank
In absence of public water supply system, the building premises shall have individual water sources specified in Part 8. For water supply system, to feed and discharge by firefighting equipment, the building premises may have deep tube well with required flow, water wells, natural water sources or a ground (or underground) tank, roof top tank, swimming pools etc. The capacity of these facilities shall be sufficient to satisfy the flow requirement as specify in Table 4.4.1.4.2.2.4 Water supply test
After installation of the hydrant system, a flow test shall be conducted to verify the capacity of the discharge system such that the installation can fulfill the minimum capacity (flow and time) as specified in Table 4.4.1. This system shall be periodically inspected, maintained and tested in accordance with NFPA 25.4.2.2.5 Fire pump
The firefighting equipment shall be directly feed by automatic main fire pump. Centrifugal pump, turbine-type pump (submerged or with vertical shaft) or positive displacement pumps with adequate supply pressure and flow capacity shall be used for water supply during demand. Centrifugal pumps shall not be used where a static suction lift is required. Once the pump starts, it shall run continuously until stopped manually. The pump shall be fully operational within 30 seconds after starting. There shall be provision for manual starting where priming is necessary. Automatic priming equipment is necessary to ensure priming at all times. The fire pump shall not be used for other purpose. Fire pumps shall have the rated capacities as shown in Table 4.4.2. The pump shall be rated at net pressure of 272 kPa or more as per requirement of the firefighting system demand. For pump installation procedure and fittings NFPA 20 shall be followed. The pump shall be housed in a readily accessible position in a building of non- combustible construction. The pump shall be adequately protected against mechanical damage. There shall be a provision for secondary fire pump which can be operated by a dedicated diesel engine or by an alternate power supply source with adequate control system and incompliance with safety operation during fire. Quality of the pump assembly shall comply with the specification of International Association of Fire. (The fire pump is on the roof) Figure 4.4.3 Typical diagram for gravity roof tank with adequate domestic and fire reserve. 4.2.3 Design Considerations for Standpipe and Hose System4.2.3.1 The fire protection system shall be designed for their effective use either by
amateur or trained firefighting personnel or both.4.2.3.2 All standpipes in standpipe system shall be sized so that they will provide a
minimum flow specified in Table 4.4.1. In standpipe system with more than one standpipe, the supply piping shall be sized for the minimum flow specified in Table4.4.1 for the first standpipe plus 1000 litre per minute for each additional standpipe.
The total number of such additional standpipes shall not be more than 8. All standpipe risers shall be interconnected through check valves of equivalent size to prevent recirculation. (The fire pump at the ground level) Figure 4.4.4 Typical diagram for gravity roof tank with adequate domestic and fire reserve.4.2.3.3 The minimum pressure for standpipes supplying a 50 mm or larger diameter
hose shall be at least 300 kPa. For standpipe supplying first aid hose (38 mm nominal diameter) may have a minimum pressure of 200 kPa. The maximum pressure at any point of the system shall not exceed 2434 kPa, if the hose connection at 40 mm diameter outlet exceeds 700 kPa approved pressure regulating device shall be installed to maintain the above maximum limits.4.2.3.4 Diameter of the standpipe termed as size shall comply with flow and capacity
requirement of the pump shown in Table 4.4.2 or hydraulically design to provide required flow and pressure at the topmost hydrant point. Table 4.4.2: Fire Pump Data Pump Rating Minimum Pipe Sizes (Nominal) litre/min (gpm) Discharge, mm (inch) 946 (250) 75 (3) 1136 (300) 100 (4) 1514 (400) 100 (4) 1703 (450) 125 (5) 1892 (500) 125 (5) 2839 (750) 150 (6) 3785 (1000) 150 (6) 4731 (1250) 200 (8) 5677 (1500) 200 (8)4.2.3.5 The water supply required for combined system (for partial automatic sprinkler
and Fire Department hose) shall be calculated in accordance with Table 4.4.1 plus an amount equal to the hydraulically calculated sprinkler demand.4.2.3.6 The system for firefighting purpose may be designed with automatic fire pump
with water tank at the ground as shown in Figure 4.4.5.4.2.3.7 The water stored in storage tank for firefighting operation shall not be used for
other purposes. Accordingly, separate water connections should be provided as shown in Figure 4.4.6. Water Supply Line Siamese Check Valve Connection To Sprinkler System (optional) Hose station Non-Return Valve
Figure 4.4.5 Typical diagram for fire protection with ground tank and automatic fire pump
Figure 4.4.6 Typical diagram for storage tank (ground or overhead) with domestic and fire
reserve.
4.2.3.8
The ground storage tank shall be easily accessible to fire engine of Fire
Department. In absence of space available for fire engine, the cover slab of ground
storage tank shall be designed to withstand a vehicular load of local fire engine.
4.2.3.9
The standpipe shall be located such as intermediate stair landing, vestibules or
nearby in noncombustible enclosure such that it will be able to provide hose stream to the
most remote area of the floor served.
4.2.3.10 The hose shall be connected to the standpipe within a height not more than 1.5
m from the finished floor level. The hose stations shall be easily accessible for inspection and testing.4.2.3.11 The hose connection to a standpipe for large stream shall be at least 100 mm
nominal and that of small stream may be 63 mm or 50 mm on each point. The size of first aid hose shall be 38 mm nominal. The hose length shall not be more than 30 m.4.2.3.12 Different piping materials and fittings for standpipe system presented in Tables
4.4.3 and 4.4.4 shall conform to the standard or one of the standards cited against them.
The standard requirements for other materials not provided in these tables shall be subject to the approval of the Authority. Table 4.4.3: Piping for Standpipe System Material Standard Copper Tube Copper and Copper-Alloy Tube Steel Pipe Wrought Steel or Iron ASTM B75, ASTM B88 ASTM B251 ASTM A55, ASTM A120, ASTM A135 ANSI B36.10 Table 4.4.4: Standpipe Fittings Material Standard Cast Iron Copper Malleable Iron Steel ANSI 616.1, ANSI B16.4 ANSI B16.18, ANSI B16.22 ANSI B16.3 ANSI B16.5, ANSI B16.9, ANSI B16.11, ANSI B16.25, ASTM A2344.2.3.13 The standpipe riser shall be supported at the top and at the lowest level. The
riser shall also be provided with support at the alternate level in between top and bottom level of the standpipe riser. The support shall be of adequate strength to support the water-filled pipe load and an additional load of 110 kg.4.2.3.14 The horizontal standpipe shall have hangers with a spacing not more than
5 m. The hanger shall be able to carry a load of five times the weight of the water-filled pipe and an additional load of 110 kg.4.2.3.15 There shall be Siamese connection also termed as firemen connection to the
standpipe or to the delivery pipe of the gravity roof storage tank. The location of Siamese connection shall be easily accessible from the street or means of access.4.2.3.16 The system shall be provided with adequate drainage piping to discharge under
pressure. The drain pipe shall not discharge into sanitary sewer.4.2.3.17 All control valves shall be designed to withstand the pressure specified
in Sec 4.2.3.3 4.2.4 Wet Riser A wet riser is a vertical pipe of not less than 100 mm internal diameter, kept permanently charged with water which is then immediately available for use on any floor in the building at which a hydrant or landing valve is provided. The riser is connected to a booster pump or town main of suitable capacity so that they are capable to supply four 13 mm jet at 2.5 bars at the highest outlets. 4.2.5 Down Comer A similar function to that of wet riser is performed by down comer which like a wet riser is constructed of vertical piping, with outlets at different levels, but is supplied with water from a tank in the roof through terrace pump, gate valve and non-return valve. It is also fitted with inlet connections at ground level and air release valve at roof level for being capable of charged with water by pumping from fire engines. 4.2.6 High Velocity Water Spraying Projector System This system applies water in the form of conical spray consisting of droplets of water traveling at high velocity. The three principles of extinguishments are employed, namely emulsification, cooling and dilution. While the water droplets are passing through the flame zone, some of the water is turned into steam, diluting the oxygen feeding the fire. Addition of water to the burning oil also cools it and reduces the rate of vaporization. In addition to this droplets of water traveling at high velocity bombard the surface of the oil to form an emulsion of oil and water that will not support combustion. 4.2.7 Water Mist Technology Fine water spray suppression system can extinguish fires using water and nitrogen from air. Nozzle is used to atomize water by nitrogen or other suitable media to generate mist or fog of finely controlled water droplets. The system operates at low pressure and produces droplets in a range of 80 to 200 microns. These droplets extinguish fire rapidly and efficiently even those involving highly volatile hydrocarbons. This system is an alternative to Halon and other gaseous system in many applications. 4.2.8 Drenchers Drenchers are used for the external protection of the building against exposure hazard, or radiant heat. Drencher heads are similar to sprinkler heads and may be sealed or unsealed. Drenchers are of three types, roof drenchers, wall drenchers, window drenchers. 4.2.9 Dry Riser System Dry riser stand pipe system shall be an equivalent alternative of wet riser stand pipe system. The water supply for an automatic or semi-automatic standpipe system shall be designed such that the system must be capable of supply the system during peak demand hour. 4.2.10 Design Consideration of Sprinkler System4.2.10.1 A system of water pipes fitted with sprinkler heads as per manufacturers
specification may be installed actuate automatically, control and extinguish a fire by the discharge of water.4.2.10.2 The pipe schedule sizing to supply different number of sprinklers for their
different uses may be in accordance with Tables 4.4.5 and 4.4.64.2.10.3 Each sprinkler shall serve a maximum ceiling area specified in Table 4.4.7 for
different types of building according to their uses.4.2.10.4 Water supply piping and fittings for sprinkler system shall conform to the
standard or one of the standards cited against them in accordance with Tables 4.4.4 and 4.4.8. The standard requirements for other pipe materials not provided in these tables shall be subject to the approval of the Authority.4.2.10.5 The sprinkler system shall be provided with adequate support or made flexible
to prevent pipe breakage during earthquake.4.2.10.6 The hanger in sprinkler system shall be designed to carry a load equal to five
times the weight of the water-filled pipe plus an addition load of 110 kg. The support shall be designed to support a load equal to the weight-filled pipe plus and additional load of 110 kg. 4.2.11 Connection4.2.11.1 There shall be Siamese connection to the sprinkler system located outside the
building and accessible to the fire department connection.4.2.11.2 All risers shall be connected through a gate valve with a main of size equal to
that largest riser.4.2.11.3 The sprinkler system shall be provided with adequate drainage arrangement.
The drain pipe shall not discharge into sanitary sewer.4.2.11.4 All control valves and fittings shall be able to withstand the pressure specified
in Sec 4.2.3.3. 4.2.12 Inspection, Testing and Maintenance4.2.12.1 Inspection
All piping and equipment shall be inspected for satisfactory supports in accordance with Sec 6.15 in Part 8 of this Code and protection from damage and corrosion. All outlets shall be free from obstruction.Table 4.4.5: Size of Water Supply Steel Pipe to Sprinklers Pipe Size mm (inch) nominal No. of Sprinkler for Light Hazard* No. of Sprinkler for Ordinary Hazard * No. of Sprinkler for Ordinary Extra Hazard * 25(1) 32(1 ) 38(1 ) 50(2) 63(1 ) 75(3) 88(3 ) 100(4) NL** 125(5)
150(6)
200(8)
400*** 225***- Definitions of these terms are given in Table 4.4.1. ** No limit. *** One sprinkler system riser or combined system riser shall serve the floor area not more than 4850 m2 for light and ordinary hazardous occupancy and 2325 m2 for extra hazardous occupancy Table 4.4.6: Size of Water Supply Copper Pipe to Sprinklers Pipe Size mm (inch) nominal No. of Sprinkler Connection for Light Hazard* No. of Sprinkler Connection Ordinary Hazard * No. of Sprinkler Connection Ordinary Extra Hazard * 25(1) 32(1 ) 38(1 ) 50(2) 63(1 ) 75(3) 88(3 ) 100(4) NL** 125(5)
150(6)
200(8)
-
- The definitions of these terms are given in Table 4.4.1. ** * Storage facilities which permit closely piled materials over 4.5 m or materials on rack over 3.6 m. Table 4.4.8: Piping for Sprinkler System Material Standard Copper and Copper-Alloy
4.2.12.2 Testing
Fire protection plumbing system or part thereof shall be tested and approved after installation by the Authority. (a) Testing of Standpipe System: The hydrant pipes shall be hydraulically tested to a pressure 1400 kPa or 150% of working pressure whichever is the higher for 2 hours without any leakage at any points. The system shall be able to maintain
above test pressures. The system shall also be tested for the required flow at the
highest outlet.
(b)
Testing of Sprinkler System: This system shall be tested for at least 2 hours for a
pressure of 1000 kPa or at 350 kPa in excess of normal working pressure when
normal working pressure will be more than 650 kPa. The system shall be able to
maintain above test pressures. The system shall also be tested for the required flow
at the highest outlet.
(c)
Testing of Sprinkler System Pump: The pump used for sprinkler system
firefighting purpose shall be tested by approved authority for their performance
characteristics and this test report must be submitted at the time of supply of pump.
The pump shall be retested or repaired to its original condition if their performance
characteristics fall below more than 10 percent of the supplier’s test characteristic
curve or as specified for the fire protection water supply system.