1.1 Scope

This Part of the Code prescribes regulations for safeguarding life and property in the use or occupancy of buildings or premises from the hazards of smoke and fire, and explosions. The provisions of this Part include general requirements of fire protection, precautionary requirements, means of egress, equipment and in-built facilities standard installations required for firefighting, and firefighting arrangements required for all occupancy groups.

1.2 Terminology

This Section provides an alphabetical list of the terms used in and applicable to this Part of the Code. In case of any conflict or contradiction between a definition given in this Section and that in Part 1, the meaning specified in this Part shall govern for interpretation of the provisions of this Part. ALARM It consists of a circuit, controls, relays, switches and associated CONTROL UNIT system which receive signals from alarm initiating devices and transmit to alarm signaling devices. ALARM An equipment operated manually or automatically which, when INITIATING activated, initiates an alarm through an alarm signaling device. DEVICE ALARM SIGNAL Signals of audible or visual in nature, indicating the existence of a fire and/or smoke condition. Audible devices may be bells, horns, chimes, speakers or similar devices. Visual Alarms is a strobe light emitting bright white light with approved insanity. ALARM SIGNAL The equipment that produces the alarm signal. DEVICE ALARM SYSTEM It is a combination of compatible devices, which when activated with necessary electrical energy can produce an alarm in the event of fire. ALARM ZONE It describes a defined area of the building or buildings for alarm initiating locations.

1.3 General Requirements

The provisions of this Section shall specify the general requirements in respect of height and area limitations, open space requirements and access facilities for the fire service, which are to be provided for a building to protect it from potential fire hazards.

1.3.1 Height and Area Limitations

The height and area limitations of all buildings and structures shall be governed by the occupancy group classification, floor area ratio and type of construction, which are specified in Part 3 of this Code.

1.3.2 Open Space or Fire Separation Requirement

For the purpose of applying the provisions of open space or fire separation requirements of a building at its side, rear and frontages in Part 3 of this Code shall be followed.

1.3.3 Access Facilities for Fire Service

The access facilities for fire service vehicles and engines shall meet provisions provided in Part 3 of this Code.

1.4 Fire Drill

Fire drills based on fire order shall be arranged to train the occupants of a building in first-aid firefighting, relocation and orderly evacuation. The occupants shall be made thoroughly conversant with fire order, firefighting, and relocation and evacuation procedures in the event of an emergency. The guidelines of fire drill, relocation and evacuation procedure are given in Appendix A.

1.5 Fire Tests and Fire Resistance Rating

The fire resistance rating of individual building construction components shall be determined by standard materials testing procedure as detailed below.
  • (a) The fire resistance ratings of building assemblies and structural elements shall be determined in accordance with ASCE 29 or ASTM E 119.
  • (b) The construction materials which are intended to be classified as noncombustible shall be tested in accordance with ASTM E 136.
  • (c) Flame resistance rating of all materials used for interior finish and trim shall be tested in accordance with ASTM E 84.
  • (d) The fire door assemblies shall conform to the test requirements of ASTM E 152.
  • (e) The fire windows and fire shutters shall meet the test requirements of ASTM E 163.
  • (f) The fire resistances rating of structural elements are provided in Table 4.1.1. For details refer to ASCE 29.
Table 4.1.1: Fire Resistance of Structures Minimum Equivalent Thickness of Concrete Walls, Floors, and Roofs for Fire Resistance Rating Minimum Column Dimension for Fire Resistance Rating Minimum Required Equivalent Thickness of Masonry for Fire Resistance Rating Appendix A Fire Drill and Evacuation Procedure