3.5 net
C Institutional 12 gross D Health Care: In patient areas Out-patient areas 15 gross 10 gross I Assembly: with fixed seats with movable seats standing space only with table and chairs Passengers that can be unloaded simultaneously to a terminal or a platform Number of seats designed.0.93 net
0.37 net
1.5 net
0.15 net
E Business: Office Space 3 gross Occupancy Unit of Floor Area in m2 per Occupant* F Mercantile: Retail sales Area, Ground floor or Basement All other floor2.3 net
4.6 net
G Industrial 10 gross H Storage 20 net K Garages and open parking structures 23 net L Utility Actual occupant load M Miscellaneous Building Actual occupant load- As per Sec 3.5.1(b) of this Chapter, design occupant load shall be calculated and any fraction shall be rounded to next higher integer value. Width of all components of egress system shall satisfy requirements of specified in the Table 4.3.2 3.5.2 Fixed Seats The occupant load for an assembly or educational area having fixed seats shall be determined by the seating capacity of the area. For fixed seats without dividing arms, the capacity shall be taken as one person for every 500 mm of seat. 3.5.3 Maximum Occupant Load The design occupant load, need not to be calculated more than one person per 0.3 m2 of usable floor space. 3.5.4 Mezzanine Floors The occupants of a mezzanine floor evacuating through other floors the occupant load shall be added to the receiving floors. 3.5.5 Roofs A Roof, an open air space used as assembly or refuge area, educational or other types of human occupancy shall be provided with exit facilities as per provisions of this Code. 3.6 Capacity of Exit Components 3.6.1 The capacity of egress components shall be complied with the occupant load of the area served. The required width of each component shall be computed on the basis of the allotted width per occupant prescribed in Table 4.3.2, subject to the minimum widths
3.7.4
All exit corridors or passages shall have a fire resistance rating of 1 hour or
more as per provisions of this Code.
3.7.5
Protective opening leads to an exit shall be fire doors or fire windows or a fire
assembly having a fire resistance rating of at least 20 minutes or more as per provisions
of this Code.
(a)
Certified Fire resistance rating of Doors shall be in accordance with ASTM
E152 without the hose stream test.
(b)
Fire resistance rating of the fire door assembly has to perform as required 20,
30, 60, 90, 180 minutes or more shall be leveled A, B, C, D, E and F
respectively.
(c)
Fire door assembly of any approved materials shall qualify through ASTM
E152 without the hose stream test.
3.8
Assembly Seating and Waiting
(a)
Assembly buildings primarily meant for theatrical, operatic performances or
cinematic projection shall have the seats securely fastened to the floor with
exceptions as permitted in this Code. All seats in balconies and galleries shall
be securely fastened to the floor except boxes with level floor and less than
14 seats.
(b)
Seats not fixed to the floor shall be permitted in restaurants and such other
places provided that 1.25 m2 of floor space is allotted for every seat
excluding dancing floor and stage. Adequate aisles shall be maintained at all
times to reach exits without obstruction when such occupancies are in use.
3.8.1
Assembly buildings which contain seats, tables, equipment or exhibitions or
displays shall be provided with aisles, free of obstructions, leading to the exit.
3.8.2
Minimum clear widths of steeped aisles and other means of egress serving
assembly seating shall be calculated on the basis of number of seats and in accordance
with Table 4.3.3. Interpolation shall be permitted between the specific values shown
thereof. The minimum clear width of steeped aisles as found by above calculation shall
be modified in accordance with the conditions stated below:
(i)
If risers exceed 178 mm in height for steeped aisles the width of the steeped
aisles as shown in the table shall be multiplied by factor a,
Where, = 1 +
ℎ
(4.3.1)
(ii)
In the Table 4.3.3 values of steeped aisles not having a handrail within a
760 mm horizontal distance shall be 25 percent wider.
(iii)
In Table 4.3.3 values of width of ramps used for ascending and steeper than
1 in 10 slope shall be increased by 10 percent.
Table 4.3.3: Capacity Factors for Assembly Seating
Number of seats within a
single assembly space.
Clear Width per Seat Served
Steeped aisles (mm)
Passageways, Ramps
and Doorways(mm)
≤ 2,000
7.6 a
5.6 5,0005.1 a
3.8 10,0003.3 a
2.5 15,0002.4 a
1.8 20,0001.9 a
1.4 ≥25,0001.5 a
1.1 3.8.3 The minimum width of level or ramped aisles shall be as specified below: Seats on both sides of the aisle1.0 m
Seats on one side of the aisle0.9 m
3.8.4 The minimum width of stepped aisles shall be as specified below: Seats on both sides of the aisle1.2 m
Seats on one side of the aisle1.0 m
3.8.5 The minimum clear gap between rows, measured as the clear horizontal distance between the back of the row ahead and the nearest projection of the row behind shall be 300 mm. For chairs having automatic or self-rising seats, the measurement shall be made with the seats in the raised position, for non-automatic seats the measurement shall be taken with the seats in the down position. 3.8.6 For rows of seating served by an aisle or doorway at only one end of the row, the path of travel shall not exceed 10 m from any seat to the aisle or doorway. The minimum clear gap between rows shall be increased beyond 300 mm specified in Sec3.8.6 by 15 mm for each seat in excess of 7, but the clear gap need not exceed 550 mm.
3.8.7 In any assembly occupancy spectators are allowed to wait in the lobby or similar space within the building until seats are available. Exits shall be provided for the waiting spaces on the basis of 0.28 m2 areas per person waiting space and one wheel chair space
for every 100 occupant. Such waiting occupant load shall be added with main assembly
load for calculating exit size for the assembly as per provisions of this Code.
3.9
Doorways
One surface of a door leaf which is exposed to a fire incident is the terminal point of exit
access and other surface of that said door which is unexposed to that fire incident is the
starting point of an exit. A door or an opening protective assembly is an obstruction for
occupants to pass through from exit accesses to exits until and unless it is installed as per
provisions of this Code.
3.9.1
Each occupant of a room or space shall have access to at least one exit door or
exit access assembly. The occupant load per exit door and the travel distance up to that
door shall not exceed the values specified in Table 4.3.4.
3.9.2
Where either the occupant load or the travel distance exceeds the values
specified in Table 4.3.4 shall have multiple exit doors to comply the both.
3.9.3
The width of a door shall not be less than 1 m and the height shall be not less
than 2 m. Exit doors shall be side swing or pivoted of side hinge type.
3.9.4
No sliding or hanging door shall be used as a means of exit. In pressurized areas
and when occupant load is less than 10, restriction of Sec 3.9.3 may be exempted.
3.9.5
All exit access doors shall be of a side-swinging type. When the occupant load
exceeds 50 or in a hazardous occupancy, the doors shall swing outward from the room or
towards the direction of travel. Swinging of the door shall not constrict the width of the
corridor narrower than 0.9 m measured at the most critical position.
3.9.6
Exit doorways shall not open directly on a flight of stairway. A clear area which
more than the width of the door leaf as specified in the above Sec 3.9.5 shall be
maintained immediately outside the doorway. The floor levels shall be same in the
direction of travel as per provisions of this Code.
Table 4.3.4: Maximum Occupant Load and Travel Distance for Spaces with One
Exit Door
Occupancy
Maximum Design
Occupant Load
Maximum Travel
Distance (m)
A
Residential
C
Institutional
D
Health Care
B
Educational
I
Assembly
E Business
F Mercantile
G
Industrial
H
Storage
J
Hazardous
3.9.7
Revolving doors shall not be used as a means of exit in assembly, educational or
institutional buildings or in spaces with an occupant load of 200 or more. In all other
cases revolving doors shall not constitute more than half of the total required exit door
width and each revolving door with least diameter of 2.7 m shall be credited not more
than 50 persons. Exit doors shall be installed in the same wall within proximity of 3m of
Revolving doors and shall comply with the following:
3.9.7.1 Revolving doors shall be positioned with a dispersal area at a distance of 3m or
more from the foot or top of stairway or escalators or moving walks or lift lobbies.3.9.7.2 Revolving doors shall stop rotating and stand still in a book-fold position at a
force not more than 800 N or when a force is applied not more than 578 N to a wing within 760 mm of outer edge or due to sudden power failure catch automatically released and ready to manual revaluation and that provide a path which shall have aggregate width minimum 910 mm.3.9.7.3 A manual control switch shall be installed in an approved location.
3.9.7.4 Speed of revolving door shall not exceed the revolution per minute shown
below: Speed of Revolving Door Inside Diameter (m) Manual-mode Speed limit (rpm) Power-mode Speed limit (rpm) 2.1 2.3 2.4 2.6 2.7 2.93.9.7.5 All exit doors shall be operable without the using a detachable key from the side
they serve to evacuate. 3.10 Stairways Change in level in elevations achieved by steps combination of identical risers and treads as per provisions of this Code shall be termed as Stairway irrespective of their locations. Stairways within an envelope shall be termed as Staircase. Exception: stepped aisles with in an assembly. Width of Stairways shall be a length perpendicular to the direction of travel, a clear distance measured between inner edges of handrails or a clear distance between inner edges of a handrail of exposed side to its opposite and parallel surface measured at a height of inner edge of cross section of that handrail. In case of variation in width measurement the smallest value shall represent the width of a stairway. Required combination of dimensions for risers and treads given in Table 4.3.5. Required guards and handrails shall continue for the full length of each flight of stairways. Inner turns of handrail of flights shall be at the landings and grasp ability of handrails shall be smooth and continuous, Handrail Brackets or balusters attached to the bottom surface of handrail shall not be considered to be obstructions to grasp ability. Gap between any surface and handrail shall be not less than 63.5 mm. Stairways serving more than three storey building having capacity more than 10 occupants shall have visual enclosures to avoid any impediments to stair use by persons having fear of height, any arrangement intended to meet this requirement shall be at least 1070 mm in height. 3.10.1 The required width of exit stairways shall be computed in accordance with the provisions of Sec 3.6, but it shall not be less than the minimum widths specified in Tables4.3.6 and 4.3.7
3.10.2 The least dimension of landings or platforms in exit stairways shall not be less than the required width of stairway and shall be leveled, except that the landing between two stair flights in a straight run shall not be required to be wider than 1.2 m in the direction of travel. When two stair flights are not straight or nonparallel to each other, a turning in the path of travel direction occurred which is other than U turn. Landing width shall be the required width of stairway and length of the common landing between such flights shall be one tread depth more lengthen when measured from both edges of stairway from both the flights. Table 4.3.5: Combination of Risers and Treads Gradients Step Dimensions Available Headroom Clearance of Flight Handrail or Guard Height Maximum Number of Flights Grade Angle of Flight Tread Depths Risers (%) Deg (mins) (mm) (mm) (mm) (mm) 31.25 33.87 37.28 41.07 44.44 Unlimited 48.07 53.06 57.44 63.63 69.04 81.57 88.88 97.05 103.02 107.07 112.5
Note: Allowable length of nosing at the outer edge of tread shall not be included in the
tread depth measurement. The maximum rise of a single flight between landings
shall not be exceeded 3658 mm and in case of large assembly maximum rise of
a single flight between landings shall not be exceeded 2438 mm.
Table 4.3.6: Minimum Width of Stairways in Egress System
Occupancy
Minimum Width of Each
Stairway (mm)
A
Residential: A1, A2
A3, A4, A5
As per Table 4.3.6
B
Educational
Occupant load up to 130
Occupant load more than 130 but not more 250
D
Hospital
Patient area
Staff area
I
Assembly: I1, I2, I3, I4, I5
As per provisions of this Code.
All others
As per provisions of this Code.
Note: The required number of stairways shall be determined by dividing the calculated
total widths of stairways as per sections 3.5, 3.6 and Table 4.3.2 of this Chapter
by applicable minimum stair width as specified in this table and any fractions
thereof shall be rounded up with the next higher integer. Unit width of stair and
multiple even numbers shall be maintained as per provisions this Code.
Table 4.3.7: Fire Escape Stairs
Element
Serving More than 10
Occupants
Serving 10 or Fewer
Occupants
Clear widths
560 mm between handrails
Minimum horizontal
dimension of any
landing or platform
560 mm
Maximum riser height
230 mm
Element
Serving More than 10
Occupants
Serving 10 or Fewer
Occupants
Minimum tread,
exclusive of nosing
250 mm
Tread construction
Solid, 13 mm diameter perforation permitted
Winders
Not permitted
permitted subject to Sec 3.10.7
Spiral
Not permitted
permitted subject to Sec 3.10.7
Maximum height
between landings
3.70 m
Headroom, minimum2.00 m
Access to protected openings Door or casement windows, 600 mm x 2000 mm or double-hung windows 70 mm x 900 mm clear opening Window providing a clear opening of at least 500 mm in width, 600 mm in height, and 0.53 m2 in area Level of access openings Not over 300 mm above floor; steps if higher Discharge to ground Swinging stair section permitted if approved by authority having jurisdiction Capacity, number of person 13 mm per person if access by door; 25 mm per person if access by climbing over window sill Note: The maximum design occupant load for a Fire escape stair shall not be exceeded 50 occupants from any floor level. 3.10.3 The rise and tread dimensions in a stairway shall be identical and the headroom requirements shall conform to the provisions of this Code. 3.10.4 Handrails height on stair shall be not less than 860 mm and not more than 960 mm above the surface of the tread, measured vertically from the top of the rail to the outer edge of the tread. Peripheral diameter of circular cross section of a handrail shall not be less than 32 mm and not more than 50 mm. Any other shape with perimeter dimension of not less than 100 mm, but not more than 160 mm and with the largest cross- sectional dimension not more than 55 mm shall be permitted provided that all edges are rounded to provide a radius of not less than 3 mm. Handrails shall be graspable along their entire length. Additional handrails that are lower or higher than main shall be permitted.
3.10.5
The height of guards shall not be less than 105 mm measured vertically from the
top of the guards from the surface of adjacent area to be served by them. When blasters
are used in the guards rail shall be used to create a pattern as such size that a sphere 100
mm in diameter shall not pass through any opening up to a height of 860 mm. Riser, tread
and the bottom rail of guards formed a triangular opening shall not be of such size that a
sphere 150 mm in diameter shall not pass through.
3.10.6
There shall be no variation in excess of 5 mm in depth of adjacent treads or in
the height of adjacent risers, and the tolerance between the largest and smallest tread or
between the largest and smallest riser is 10 mm in any flight.
3.10.7
Monumental stairs, Circular stairs, Curved stairs, Spirals and winders, stepped
and rung ladders, alternate tread devices shall be permitted as per provisions of this Code.
3.10.7.1 When the width of stairways exceeded 4475 mm termed as Monumental or
Grand Stairway shall be permitted as per provisions of this Code.3.10.7.2 Curved stairs or circular stairs shall be permitted as a component of means of
egress as per provisions of this Code provided that the depth of tread is not less than 280 mm at a point 300 mm from the narrower end of the tread and the smallest radius is not less than twice of stair widths and shall comply with the provisions of this Code.3.10.7.3 Spiral stairways shall be permitted where occupant load shall not more than
five. For spiral stairways the following conditions shall be applicable: (a) The clear width of the stairs shall not be less than 660 mm. (b) The height of risers shall not exceed 240 mm. (c) Headroom shall be not less than 1980 mm. (d) Treads shall have a depth not less than 190 mm at a point 300 mm from the narrower edge. (e) All treads shall be identical.3.10.7.4 Winders shall be permitted in stairs where occupant load shall not be more than
three. (a) Winders shall have a tread depth not less than 150 mm and a tread depth not less than 280 mm at a point 300 mm from the narrowest edge. (b) The clear width of the stairs shall not be less than 660 mm.3.10.7.5 Stepped ladders and Rung ladders shall be installed with pitch that exceeds 75
degrees as per standards of ANSI A14.3. The lowest rung of any ladder shall not be more than 300 mm above the level of the surface beneath it. (a) From towers and elevated platforms around machinery or similar spaces subject to occupancy load not to exceed three persons. (b) Open structure, observation towers or railroad signals that are designed for occupancy not more than three persons.3.10.7.6 Alternate tread device
The occupant load shall not exceed three and shall comply with the followings: (a) Handrail shall be provided on both sides of alternate tread device having clear width not less than 430 mm and not more than 610 mm (c) Headroom shall not less than 2000 mm and angle of the device shall be between 50 degrees and 68 degrees to horizontal. (c) The initial tread of the device shall begin at the same elevation as the platform, landing, or floor surfaces and the alternating treads shall not be laterally separated by a distance more than 50 mm. (d) Treads shall have projected depth not less than 150 mm and each tread providing 240 mm of depth, including overlapping of treads. (e) The height of the risers shall not exceed 240 mm. 3.10.8 Stairways shall have continuous guards on both side along the direction of travel and a continuous handrail shall be provided with inner edge guard. A stair of width more than 1120 mm but not more than 2235 mm shall have guards and handrails on both of the edges. Inner edge handrails shall be continuous and outer edge handrails shall be along the flights extended up to one tread depth on both the landings. A stair the width exceeds 2235 mm; intermediate handrails shall be installed with similar length of outer edge handrail. Single traffic lane shall be calculated 560 mm in the stairway and two traffic lanes shall be 1120 mm. Widths of stairs shall be multiple of two traffic lane other than width specified in the Table 4.3.6. 3.10.9 All exit stairways shall be constructed by materials that conform to the fire resistance requirements of the type of construction of the building, except that solid wooden handrails shall be permitted for all types of construction.3.10.10 An exit stairway shall not be built around a lift shaft unless both of them are
located in a smoke proof enclosure and made of a material with fire resistance rating required for the type of construction of smoke proof enclosure.3.10.11 Exterior stairways used as fire stair shall not be considered as a component of
means of egress, unless they lead directly to the ground or a refuge area, are separated from the building interior by fire resistive assemblies or walls and are constructed by noncombustible materials and free from smoke accumulation. 3.11 Ramps 3.11.1 Ramp is a sloping surface steeper than 1 in 20 but not steeper than 1 in 8 used by walkers only. Slope of ramps to comply with accessibility requirement shall not be steeper than 1 in 12. 3.11.2 The minimum width of exit ramps shall not be less than that width required for corridors or passages. 3.11.3 The slope of an exit ramp shall not exceed 1 in 8, but for slopes steeper than 1 in 10 the ramp shall be surfaced with approved non-slip material or finished such as to effectively prevent slipping. 3.11.4 Guards and handrails shall be provided on both sides of ramps having slope steeper than 1 in 15. 3.11.5 Ramps shall be straight, in case of changes in the travel direction that shall be made at the level platforms or at the landings except that ramps having a slope steeper than 1 in 12 may be curved at any place. 3.11.6 Length of the sloping portion of ramps shall be at least 915 mm but not more than 9150 mm long between level platforms or landings. 3.11.7 Level platforms or landings shall be at least as wide as the ramps and shall be placed at the bottom, at intermediate levels where required, and at the top of all ramps. Level platform shall be provided on each side of openings into or from ramps having minimum length of 915 mm in the direction of travel and when a door swings on the minimum length of platform or landing shall be 1525 mm. 3.11.8 Doors on ramps shall not be opened on sloping surface shall be complied with the requirements of 3.9 of this Chapter. 3.11.9 Sloping or ramp driveway approaching basements or any parking structures shall not be credited as an exit ramp when slope is steeper than 1 in 8 and not complied with Sec 3.11 of this Chapter. Exits requirement of such basements shall be achieved by stairways or fire lifts within smoke proof enclosure approached by a two doors smoke lock vestibule. 3.12 Horizontal Exits 3.12.1 The connection between two separated areas of a building or connection between buildings at same level which the horizontal exit serves shall be provided with at least 2 hour fire resistance rated walls, or by an open air balcony or a bridge having protected openings. 3.12.2 The horizontal exits shall be protected from the area of incidence by self-closing fire door. 3.12.3 The width of a horizontal exit access door shall not be less than 1 m. 3.12.4 Changes in level in the elevation along the direction of the horizontal exit shall not be achieved by single step but by ramps which is not stepper than 1 in 12. 3.12.5 Where the horizontal exit serves for only one side, fire door shall swing in along the direction of travel. When horizontal exit serves both the side of separated area, the doors shall have two leaves and each leave dedicated to satisfy direction of travel from assigned area, or there shall be two independent doors assigned for two areas each of them serves only one area. When the building is occupied the doors installed in horizontal exit shall be operable at all times without the use of a detachable key. 3.12.6 Horizontal exit relocates occupants to an area which is either a public space or a space used by other occupants and shall be termed as a refuge area. The capacity of the refuge area shall be computed on the basis of net floor area excluding stairways, shafts and spaces allotted to occupants of the receiving end. The required capacity of a refuge area shall be 0.28 m2 per healthy occupant and 0.3 m2 per wheelchair or 2.8 m2 per patients retained in bed for delayed egress or an area equivalent to a passage or a corridor having width to comply the capacity of evacuees and connected with the components of exits up to exit discharge. 3.13 Smoke Proof Enclosure Any compartment or a room or a control area surrounded by barrier walls within a building structure shall be protected from smoke penetration during a fire incident occurred elsewhere in the building shall be termed as smoke proof enclosure. A stairway with in an envelope shall be termed as Interior stairway or staircase. Any exterior side having opening of 50 percent or more in such a way that there shall be no smoke accumulation shall be termed as open stair. 3.13.1 An interior stairway conforming to Sec 3.10 and having entry from an exterior balcony or through a ventilated vestibule conform a smoke proof enclosure provided no direct opening or any aperture allowed on the walls of the stair from the building side. 3.13.2 All exit stairways mentioned above shall be protected by a smoke proof enclosure when serving occupants are located in a high rise building. 3.13.3 There shall be provision to access enclosed stairways through vestibule or an open balcony. The minimum width of a vestibule shall be equal to width of connected passages or corridors specified in section 3.7 in this Chapter and the minimum length of a vestibule in the direction of travel shall be 1.8 m. 3.13.4 The minimum fire resistance rating of the walls forming a smoke proof enclosure around stairway including the vestibule thereof shall be 4 hours and separated from the area of incidence having no openings other than a fire door for the entry to the vestibule. For fire rating of the door see Chapter 1 Part 3. 3.13.5 All doors in smoke proof enclosure and the vestibule shall be self-closing type or they shall be fitted with automatic closing devices actuated by the fire detection system. 3.13.6 The vestibule shall have adequate natural ventilation. Each vestibule shall have a minimum area of openings of 2 m2 divided into two in an exterior wall facing a courtyard, street or public way wider than 6 m. The location of one opening measuring1.5 m2 shall be as high as possible and another shall be 0.5 m2 as low as possible.
3.13.7 If the enclosed staircase is windowless, mechanical ventilation shall be installed. If the vestibule is windowless, mechanical ventilation shall also be installed. In addition to ventilation a positive pressure of 50 Pa shall be maintained in the vestibule. This positive pressure must be developed within 30 seconds of the incident of fire. When the staircase and the vestibule are windowless emergency illumination shall be provided. 3.14 Number of Exits 3.14.1 The number of exits shall be determined as per provisions of Sec 3.6, Tables 4.3.1, 4.3.2 and 4.3.8 of this Chapter and complying with maximum dead end passage or corridors and maximum travel distance. 3.14.2 Total required widths of exits shall be calculated as per provisions of the Tables4.3.2 and 4.3.8 shall be divided and distributed at a distance not less than one-third of
diagonal distance of space and the travel distance and the width of each exit shall comply with the provisions of this Code. The required number of exits in a space as specified below: Occupant load less than 50 Minimum 1 exit Occupant load 50 to 500 Minimum 2 exits Occupant load 501 to 1000 Minimum 3 exits Occupant load more than 1000 Minimum 4 exits 3.14.3 High rise buildings having a floor area larger than 500 m2 on each floor used as educational, institutional, assembly, industrial, storage or a mixed occupancy involving any of these or hazardous occupancy, shall have a minimum of two staircases. These staircases shall comply with the requirements as specified in Sec 3.13 of this Chapter. 3.14.4 Where two accessible means of egress are required, the exits serving such means of egress shall be located at a distance from one another not less than one-half the length of the maximum overall diagonal dimension of the building or area to be served. 3.15 Travel Path 3.15.1 Travel path shall be measured along the center line of a natural and unobstructed path up to center of an exit access door opening. In case of a stairway exist in the travel path shall be measured along an inclined straight line through the center of outer edge of each tread of a stairway. 3.15.2 Occupant load and components of exits shall be arranged in such a manner that the travel path from any point in the area served shall not be exceeded as listed in the Table 4.3.8. 3.15.3 Unit width shall be 560 mm and fraction of unit width less than 280 mm shall not be credited. Where calculation of total required width give fractional result, next larger integral number of exit units or integral number plus one-half shall be used. Where changes in elevation exist, one-half or less unit of width shall not be permitted. 3.15.4 Capacity of exits shall be measured in unit of width of 560 mm and the number of occupants per unit width shall be determined by the occupancy group and type of exits as listed in Table 4.3.8. 3.15.5 Wherever more than one exit required in a room or in any floor they shall be placed as remote as possible from each other. As far as practicable, exits shall be arranged in such a manner to provide a refuge area or an exit discharge to the occupants irrespective of the direction of travel from any point in an area served. 3.16 Means of Exit Signs and Illumination 3.16.1 All required means of exit or exit access in buildings or areas requiring more than one exit shall be signposted. The signs shall be clearly visible at all times, where necessary supplemented by directional signs. All exit doors shall be clearly marked for easy identification. Exceptions: Building Occupancy type A.3.16.1.1 Location: Exit signs shall be installed at stair enclosure doors, horizontal exits
and other required exits from the storey. When two or more exits are required from a room or area, exit signs shall be installed to clearly indicate the direction of egress. Exceptions: (i) Main exterior exit doors which obviously and clearly are identifiable as exits need not be signed when approved by the Building Official. (ii) Exit signs are not required for buildings of occupancies A1, A2 and individual units of A3. (iii) No sign is needed for exits from rooms or areas with an occupant load of less than 50 for Occupancy type C. Table 4.3.8: Determination of Exit and Access Requirements. Occupancy Group/ Classification Maximum Travel Path (meter) Capacity Number of Occupancy per unit width of the component Ramp, Passage , Corridors Unsprinklered Full fire resistive or sprinklered Door openings Stairs, Escalators Ramp, Corridors, Exit passageways, Horizontal exit Minimum width (mm) Maximum Dead End (mm) To outdoors at Grade All other Exit and corridor doors A1, A2 Residential N.R. N.R. N.R. N.R. N.R. N.R. N.R. N.R. A3, A4,A5 B Educational
C1, C2
Institutional
C3, C4, C5
D
Health
E
Business
F
Mercantile
G1
Industrial
G2
H1
Storage
H2
I
Assembly
J
High Hazard
N.P.
Notes:
1.
In Hazardous occupancy (occupancy J) Travel Path should be performance
based but shall not exceed 15240 mm.
2.
N.P. = Not permitted
3.
N.R. = No requirement, (except as provided in Table 4.3.5b)
3.16.1.2 Graphics: The color and design of lettering, arrows and other symbols on exit
signs shall be in high contrast with their background as per NFPA 170. Words on the signs shall be at least 150 mm high with a stroke of not less than 20 mm. For vernacular alphabet and numeric height shall be at least 150 mm with stroke not less than 20 mm.3.16.1.3 Illumination: Signs shall be internally or externally illuminated by two electric
lamps or shall be of self-luminous type. When the luminance on the face of an exit sign is from an external source, it shall have an intensity of not less than 53.8 lux from either lamp. Internally illuminated signs shall provide equivalent luminance.3.16.1.4 Source of Power: Supply of power to one of the lamps for exit signs shall be
provided by the premises wiring system. Power to the other lamp shall be from an on-site generator set which shall be installed in accordance with the provisions of this Code.3.16.1.5 Floor-level Exit Signs: For floor-level exit signs additional approved low-level
exit signs which are externally or internally illuminated, or self-luminous, shall be provided in all interior exit corridors serving guest rooms of hotels in Occupancy A5. The bottom of the sign shall be 150 mm to 200 mm above the floor level. For exit doors, the
sign shall be on the door or adjacent to the door with the closest edge of the sign within
100 mm of the door frame.
3.16.2
Amusement Building Exit Marking: Approved exit direction marking and exit
signs shall be provided. Approved low-level exit signs and directional marking shall be
located not more than 200 mm above parallel the walking surface and at the exit path.
3.16.3
All exit signs shall be illuminated while in use at night, or during dark periods
within the area served, in accordance with the provisions of this Code.
3.16.4
The means of exit and exit access in buildings requiring more than one exit shall
be equipped with artificial lighting. The lighting facilities shall satisfy the provisions of
this Code.