7.1.1 Scope
This Chapter of the Code covers the design, construction and quality control of masonry structures.7.1.2 Definitions
For the purpose of this Chapter, the following definitions shall be applicable. ACTUAL DIMENSIONS The measured dimensions of a designated item; such as a designated masonry unit or wall used in the structures. The actual dimension shall not vary from the specified dimension by more than the amount allowed in the appropriate standard mentioned in Sec 2.2.4 Chapter 2 Part 5. BED BLOCK A block bedded on a wall, column or pier to disperse a concentrated load on a masonry element. BED JOINT A horizontal mortar joint upon which masonry units are placed. BOND Arrangement of masonry units in successive courses to tie the masonry together both longitudinally and transversely; the arrangement is usually worked out to ensure that no vertical joint of one course is exactly over the one in the next course above or below it and there is maximum possible amount of lap. BOND BEAM A horizontal grouted element within masonry in which reinforcement is embedded. BUTTRESS A pier of masonry built as an integral part of wall and projecting from either or both surfaces, decreasing in cross-sectional area from base to top and conforming to the requirement of Sec 4.3.3(c) (ii). CAVITY WALL A wall comprising two limbs each built-up as single or multi-wythe units and separated by a 50-115 mm wide cavity. The limbs are tied together by metal ties or bonding units for structural integrity. CELL A void space having a gross cross-sectional area greater than 1000 mm2. COLLAR JOINT The vertical, longitudinal, mortar or grouted joints. COLUMN An isolated vertical load bearing member the width of which does not exceed three times the thickness. CROSS JOINT A vertical joint normal to the face of the wall. CROSS- SECTIONAL AREA OF MASONRY UNIT Net cross-sectional area of masonry unit is the gross cross-sectional area minus the area of cellular space. CURTAIN WALL A non-load bearing self-supporting wall subject to transverse lateral loads, and laterally supported by vertical or horizontal structural member where necessary. FACED WALL A wall in which facing and backing of two different materials are bonded together to ensure common action under load. GROUT A mixture of cementitious materials and aggregate to which water is added such that the mixture will flow without segregation of the constituents. GROUTED HOLLOW-UNIT MASONRY That form of grouted masonry construction in which certain designated cells of hollow units are continuously filled with grout. GROUTED MULTI-WYTHE MASONRY That form of grouted masonry construction in which the space between the wythes is solidly or periodically filled with grout. HOLLOW UNIT A masonry unit of which net cross-sectional area in any plane parallel to the bearing surface is less than 75 percent of its gross cross-sectional area measured in the same plane. JAMB Side of an opening in wall. HEAD JOINT The mortar joint having a vertical transverse plane. LATERAL SUPPORT A support which enables a masonry element to resist lateral load and/or restrains lateral deflection of a masonry element at the point of support. LIMB Inner or outer portion of a cavity wall. LOAD BEARING WALL A wall designed to carry an imposed vertical load in addition to its own weight, together with any lateral load. MASONRY An assemblage of masonry units properly bonded together with mortar. MASONRY UNIT Individual units, such as brick, tile, stone or concrete block, which are bonded together with mortar to form a masonry element such as walls, columns, piers, buttress, etc. NOMINAL DIMENSIONS Specified dimensions plus the thickness of the joint with which the unit is laid. PANEL WALL An exterior non-load bearing wall in framed structure, supported at each storey but subject to lateral loads. PARTITION WALL An interior non-load bearing wall, one storey or part storey in height. PIER A projection from either or both sides of a wall forming an integral part of the wall and conforming to the requirement of Sec 7.4.3.3 of this Chapter. PILASTER A thickened section forming integral part of a wall placed at intervals along the wall, to increase the stiffness of the wall or to carry a vertical concentrated load. Thickness of a pier is the overall thickness including the thickness of the wall or, when bounded into a limb of cavity wall, the thickness obtained by treating that limb as an independent wall. PRISM An assemblage of masonry units bonded by mortar with or without grout used as a test specimen for determining properties of masonry. REINFORCED MASONRY The masonry construction, in which reinforcement acting in conjunction with the masonry is used to resist forces and is designed in accordance with Sec 7.6 of this Chapter. SHEAR WALL A load bearing wall designed to carry horizontal forces acting in its own plane with or without vertical imposed loads. SOLID UNIT A masonry unit whose net cross-sectional area in any plane parallel to the bearing surface is 75 percent or more of the gross cross-sectional area in the same plane. SPECIFIED DIMENSIONS The dimensions specified for the manufacture or construction of masonry, masonry units, joints or any other components of a structure. Unless otherwise stated, all calculations shall be made using or based on specified dimensions. STACK BOND A bond in bearing and nonbearing walls, except veneered walls, in which less than 75 percent of the units in any transverse vertical plane lap the ends of the units below a distance less than one-half the height of the unit, or less than one-fourth the length of the unit. VENEERED WALL A wall in which the facing is attached to the backing but not so bonded as to result in a common action under load. WALL JOINT A vertical joint parallel to the face of the wall. WALL TIE A metal fastener which connects wythes of masonry to each other or to other materials. WYTHE Portion of a wall which is one masonry unit in thickness.7.1.3 Symbols and Notation
The following units shall be generally implicit in this Chapter for the corresponding quantities: Lengths mm Areas mm2 Moment of inertia mm4 Force N Moment, torsion N mm Stress, strengthN/mm2 -1
Cross-sectional area of anchor bolt -!
Effective area of masonry -U
Gross area of wall -fM
Net area of masonry section bounded by wall thickness and length of section in the direction of shear force considered -\
Area of tension (pullout) cone of an embedded anchor bolt projected into the surface of masonry -
Effective cross-sectional area of reinforcement in a flexural member -M
Area of steel required for shear reinforcement perpendicular to the longitudinal reinforcement-r
Effective cross-sectional area of compression reinforcement in a flexural member ,
Allowable tension force on anchor bolt ,M
Computed shear force on anchor bolt w
Masonry shear strength coefficient f
Modulus of elasticity of masonry
Modulus of elasticity of steel ƒ
Loads due to weight and pressure of fluids or related moments and forces ƒ{
Allowable average axial compressive stress for centroidally applied axial load only ƒ1
Allowable flexural compressive stress if members were carrying bending load only ƒ1
Allowable bearing stress ƒ
Allowable stress in reinforcement ƒ
Allowable compressive stress in column reinforcement ƒ
Allowable flexural tensile stress in masonry ƒM
Allowable shear stress in masonry
= Shear modulus of masonry …
Actual height between lateral supports …r
Height of opening •
Moment of inertia about the neutral axis of the cross-sectional area •U, •
Gross, cracked moment of inertia of the wall cross-section ‹
Actual length of wall p
Design moment p
Moment capacity of the compression steel in a flexural member about the centroid of the tensile force p
Cracking moment strength of the masonry wall pf
The moment of the compressive force in the masonry about the centroid of the tensile force in the reinforcementph
Nominal moment strength of the masonry wall p
The moment of the tensile force in the reinforcement about the centroid of the compressive force in the masonry p!
Service moment at the mid-height of the panel, including P-Delta effects pk
Factored moment Ž
Design axial load Ž{
Allowable centroidal axial load for reinforced masonry columns Ž1
Nominal balanced design axial strength Ž`
Load from tributary floor or roof area Žo
Nominal axial load strength with bending Žk
Factored axial load Žk`
Factored load from tributary floor or roof loads Žk^
Factored weight of the wall tributary to the section under consideration Ž^
Weight of the wall tributary to the section under consideration .
Section modulus ্থ
Total design shear force ্থভ
Nominal shear strength provided by masonry ্থয
Nominal shear strength ্থ
Nominal shear strength provided by shear reinforcement
Depth of equivalent rectangular stress block for strength design y
Effective width of rectangular member or width of flange for T and I section y
Computed tension force on anchor bolt yM
Allowable shear force on anchor bolt y^
Width of web in T and I member $
Distance from the neutral axis to extreme fibre
Distance from the compression face of a flexural member to the centroid of longitudinal tensile reinforcement= Diameter of the reinforcing bar, diameter of bolt •
Eccentricity of Žk •fk
Maximum usable compressive strain of masonry {
Computed axial compressive stress due to design axial load 1
Computed flexural stress in the extreme fibre due to design bending load only fw
Computed compressive stress in masonry due to dead load only
Modulus of rupture
Computed stress in reinforcement due to design load
Tensile yield stress of reinforcement M
Computed shear stress due to design load fr
Specified compressive strength of masonry at the age of 28 days ℎ
Height of wall between points of support ℎr
Effective height of a wall or column /
Ratio or distance between centroid of flexural compressive force and centroid of tensile forces to depth, 0 *
Ratio of depth of the compression zone in flexural member to depth, d; stiffening coefficient ে
Length of a wall or segment ‡1
Embedment depth of anchor bolt ১ে!
Anchor bolt edge distance, the least length measured from the edge of masonry to the surface of the anchor bolt ‡w
Required development length of reinforcement •
Modular ratio = f ⁄ দ্১
Ratio of the area of bars cut off to the total area of bars at the section= Spacing of stirrups or bent bars in a direction parallel to that of the main reinforcement ›
Effective thickness of a wythe, wall or column¬
Bond stress per unit of surface area of bar ∆k
Horizontal deflection at mid-height under factored load; P-Delta effects shall be included in deflection calculation Σo
Sum of the perimeters of all the longitudinal reinforcement = Steel ratio = - y0 ⁄h
Ratio of distributed shear reinforcement on a plane perpendicular to the plane of -fM •
Strength reduction factor. 7.2 Materials 7.2.1 General All materials used in masonry construction shall conform to the requirements specified in Part 5 of this Code. If no requirements are specified for a material, quality shall be based on generally accepted good practice, subject to the approval of the building official. 7.2.2 Masonry Units The following types of masonry units which conform to the standards mentioned in Sec 2.2.4 of Part 5 may be used in masonry construction: (a) Common building clay bricks (b) Burnt clay hollow bricks (c) Burnt clay facing bricks (d) Hollow concrete blocks Other types of masonry units conforming to Sec 2.2.4 of Part 5 may also be used. 7.2.3 Mortar and Grout Mortar and grout for masonry construction shall conform to the requirements specified in Part 5 of this Code. Mix proportions and compressive strength of some commonly used mortars are given in Table 6.7.1. 7.3 Allowable Stresses 7.3.1 General Stresses in masonry shall not exceed the values given in this Section. All allowable stresses for working stress design may be increased one third when considering wind or earthquake forces either acting alone or combined with vertical loads. No increase shall be allowed for vertical loads acting alone. 7.3.2 Specified Compressive Strength of Masonry, 1 r The allowable stresses for masonry construction shall be based on the value of fr as determined by Sec 7.3.3 below. Table 6.7.1: Mix Proportion and Strength of Commonly used Mortars Grade of Mortar Mix Proportion by Volume 1, 2 Minimum Compressive Strength at 28 days, N/mm2 Cement Sand M1 M2 M3 M4 M5 M6 7.5 Sand and cement shall be measured in loose volume and sand shall be well graded with a minimum F.M. of 1.20 Lime to a maximum of one fourth (1/4) part by volume of cement may be used to increase workability. 7.3.3 Compliance with 1 r Compliance with the requirements for the specified compressive strength of masonry, fr shall be in accordance with the following:7.3.3.1 Masonry Prism Testing: The compressive strength of masonry based on
tests at 28 days in accordance with “Standard Test Method for Compressive Strength of Masonry Prisms”, (ASTM E447) for each set of prisms shall equal or exceed fr . Verification by masonry prism testing shall meet the following : (a) Testing Prior to Construction: A set of five masonry prisms shall be built and tested in accordance with ASTM E447 prior to the start of construction. Materials used for prisms shall be same as used in the project. Prisms shall be constructed under the observation of the engineer or an approved agency and tested by an approved agency. (b) Testing During Construction: When full allowable stresses are used in design, a set of three prisms shall be built and tested during construction in accordance with (ASTM E447) for each 500 square meters of wall area, but not less than one set of three masonry prisms for any project. No testing during construction shall be required when 50% of the allowable stresses are used in design. 7.3.4 Quality Control Quality control shall include, but not be limited to assure that: (a) Masonry units, reinforcement, cement, lime, aggregate and all other materials meet the requirements of the applicable standard of quality and that they are properly stored and prepared for use. (b) Mortar and grout are properly mixed using specified proportions of ingredients. The method of measuring materials for mortar and grout shall be such that proportions of materials are controlled. (c) Construction details, procedures and workmanship are in accordance with the plans and specification. (d) Placement, splices and bar diameters are in accordance with the provisions of this Chapter and the plans and specifications. 7.3.5 Allowable Stresses in Masonry When the quality control provisions specified in Sec 7.3.4 above do not include requirements for special inspection, the allowable design stresses in this Section shall be reduced by 50 percent. (a) Axial Compressive Stress (i) Unreinforced masonry walls, columns and reinforced masonry wall ƒ{ =×Å ¾1 −¸ ZÅ îq¼ ½ ¿ (6.7.1) (ii) Reinforced masonry columns ƒ{ = Ì ×Å
+
ß&
.ßÁ ƒÓ ¾1 −¸
ZÅ
îq¼
½
¿
(6.7.2)
(b) Compressive Stress in Flexural
ƒ1 = 0.33fr ≤ 10 N/mmq
(6.7.3)
(c) Tensile Stress of Walls in Flexure
The allowable tensile stress for walls in flexure of masonry structures
without tensile reinforcement using mortar Type M1 or M2 shall not exceed
the values specified in Tables 6.7.2 and 6.7.3. For Types M3 and M4 mortar,
the values shall be reduced by 25 percent.
No tension is allowed across head joints in stack bond masonry. Values for
tension normal to head joints are for running bond. These values shall not
be used for horizontal flexural members such as beams, girders or lintels.
Table 6.7.2: Flexural Tension, Ft
Masonry
Normal to Bed Joints
N/mm2
Normal to Head Joints
N/mm2
Solid Units
0.20
0.40
Hollow Units
0.12
0.25
Table 6.7.3: Tension Normal to Head Joints, Ft
Masonry
Clay Units
N/mm2
Concrete Units
N/mm2
Solid Units
0.35
0.40
Hollow Units
0.22
0.25
(d) Reinforcing Bond Stress, u
Plain Bars:
0.30 N/mm2
Deformed Bars: 1.0 N/mm2 (e) Shear Stress for Flexural Members, ƒM (i) When no shear reinforcement is used ƒM = 0.083fr ≤0.25 N/mm2 (6.7.4) (ii) When shear reinforcement is designed to take entire shear force ƒM = 0.25fr ≤0.75 N/mm2 (6.7.5) (f) Shear Stress for Shear Walls, ƒM (i) Unreinforced masonry For clay units: ƒM = 0.025fr ≤0.40 N/mm2 (6.7.6) For concrete units: M1 or M2 Mortar:0.20 N/mm2
M3 Mortar:0.12 N/mm2
(ii) The allowable shear stress for reinforced masonry shear walls shall be according to Table 6.7.4. Table 6.7.4: Allowable Shear Stress for Reinforced Masonry Shear Walls, 4 Masonry Wall M/Vd Fv, N/mm2 Maximum Allowable N/mm2 Masonry taking all shear « 1 36 Ì4 −p ্থ০” ভৎ Ì0.4 −0.2 p ্থ০” ≥ 1 0.083fr 0.17 Reinforcement taking all shear « 1 24 Ì4 −p ্থ০” ভৎ Ì0.6 −0.2 M VdÓ ≥ 1 0.125fr 0.37 7.3.6 Allowable Stresses in Reinforcement (a) Tensile Stress (i) Deformed bars, ƒ = 0.5 ≤165 N/mm2 (6.7.7) (ii) Ties, anchors and plain bars, ƒ = 0.4 ≤135 N/mm2 (6.7.8) (b) Compressive Stress (i) Deformed bars in columns and shear walls, ƒ = 0.4 ≤165 N/mm2 (6.7.9) (ii) Deformed bars in flexural members ƒ = 0.5 ≤165 N/mm2 (6.7.10) 7.3.7 Combined Compressive Stress Members subject to combined axial and flexural stresses shall be designed in accordance with accepted principles of mechanics or in accordance with the following formula:» 5» +
5 ≤1
(6.7.11)
7.3.8
Modulus of Elasticity
The modulus of elasticity of masonry shall be determined by the secant method.
The slope of the line connecting the points 0.05fr and 0.33fr on the stress-
strain curve shall be taken as the modulus of elasticity of masonry. If required,
actual values shall be established by tests. These values are not to be reduced
by 50 per cent as specified in Sec 7.3.5(a).
(a) Modulus of Elasticity for Masonry
f = 750fr ≤15,000 N/mm2
(6.7.12)
(b) Modulus of Elasticity for Steel
= 2,00,000 N/mm2
(6.7.13)
(c) Shear Modulus of Masonry
- = 0.4f N/mm2 (6.7.14) 7.3.9 Shear and Tension on Embedded Anchor Bolts
7.3.9.1 Allowable loads and placement requirements for anchor bolts shall be
in accordance with the following: (a) Bent bar anchor bolts shall have a hook with a 90o bend with an inside diameter of 301 plus an extension of 1.501 at the free end. (b) Headed anchor bolts shall have a standard bolt head. (c) Plate anchor bolts shall have a plate welded to the shank to provide anchorage equivalent to headed anchor bolts. ৭.৩.৯.২ ঞযব বভভবপঃরাব বসনবফসবহঃ ষবহমঃয, ১ে ভড়ৎ নবহঃ নধৎ ধহপযড়ৎং ংযধষষ নব:যব length of embedment measured perpendicular from the surface of the masonry to the bearing surface of the bent end minus one anchor bolt diameter. For plate ড়ৎ যবধফবফ ধহপযড়ৎ নড়ষঃং ১ে ংযধষষ নব:যব ষবহমঃয ড়ভ বসনবফসবহঃ সবধংঁৎবফ perpendicular from the surface of the masonry to the bearing surface of the plate or head of the anchorage. All bolts shall be grouted in place with at least 25 mm of grout between the bolt and the masonry except that 6 mm diameter bolts may be placed in bed joints which are at least twice as thick as the diameter of the bolt. 7.3.9.3 Allowable shear force Allowable loads in shear shall be according to Table 6.7.5 or lesser of the value obtained from the following formulae: ,M = 1070(fr -1)/î (6.7.15) ,M = 0.12-1 (6.7.16) ডযবহ:যব ফরংঃধহপব ে নব রং ষবংং:যধহ ১২ফন,:যব াধষঁব ড়ভ,গ রহ ঊয়. ৬.৭.১৫ ংযধষষ নব ৎবফঁপবফ:ড় ুবৎড় ধঃ ধ ফরংঃধহপব ১ে! বয়ঁধষ:ড় ৪০ সস. ডযবৎব ধফলধপবহঃ ধহপযড়ৎং ধৎব spaced closer than 801, the allowable shear of the adjacent anchors determined by Eq. 6.7.15 shall be reduced by interpolation to 0.75 times the allowable shear value at a centre to centre spacing of 401. 7.3.9.4 Allowable tension Allowable tension shall be the lesser value selected from Table 6.7.6 and Table6.7.7 or shall be determined from lesser of the values obtained from the
following formulae: , = 0.04-\fr (6.7.17) , = 0.2-1 (6.7.18) The area -\ shall be the lesser of the area obtained from Equations 6.7.17 and6.7.18 and where the projected areas of adjacent anchor bolts overlap, -\ of
each anchor bolt shall be reduced by 50 percent of the overlapping area. -\ = 6‡1 q (6.7.19) -= ৬১ে! q (6.7.20) Table 6.7.5: Allowable Shear, Bv for Embedded Anchor Bolts for Masonry, kN* Bent Bar Anchor Bolt Diameter, mm 1 r N/mm2 2.0 3.7 5.9 7.9 8.5 9.1 9.6 2.0 3.7 5.9 8.2 8.3 9.5 10.1 2.0 3.7 5.9 8.5 9.2 9.8 10.4 2.0 3.7 5.9 8.5 9.7 10.3 11.0 2.0 3.7 5.9 8.5 10.1 10.8 11.5 2.0 3.7 5.9 8.5 10.9 11.6 12.3- Values are for bolts of at least ASTM A307 quality. Bolts shall be those specified in Sec 4.3.9.1.
7.3.10 Load Test
For load test, the member shall be subject to a superimposed load equal to twice the design live load plus one-half of the dead load. This load shall be maintained for a period of 24 hours. If, during the test or upon removal of the load, the member shows evidence of failure, such changes or modifications as are necessary to make the structure adequate for the rated capacity shall be made; or where possible, a lower rating shall be established. A flexural member shall be considered to have passed the test if the maximum deflection at the end of ঃযব ২৪ যড়ঁৎ ঢ়বৎরড়ফ হবরঃযবৎ বীপববফং ০.০০৫ে হড়ৎ ০.০০০২৫ য়ে/ন্ ধহফ:যব নবধস ধহফ slabs show a recovery of at least 75 percent of the observed deflection within 24 hours after removal of the load.7.3.11 Reuse of Masonry Units
Masonry units may be reused when clean, unbroken and conforms to the requirements of Part 5. All structural properties of masonry of reclaimed units, especially adhesion bond, shall be determined by approved test. The allowable working stress shall not exceed 50 percent of that permitted for new masonry units of the same properties. 7.4 Basic Design Requirements 7.4.1 General Masonry structures shall be designed according to the provisions of this Section. The required design strengths of masonry materials and any special requirements shall be specified in the plan submitted for approval. 7.4.2 Design Considerations7.4.2.1 Masonry structures shall be designed based on working stress and
linear stress-strain distribution. Requirements for working stress design of unreinforced and reinforced masonry structures are provided in Sections 4.5 and 4.6 respectively. In lieu of the working stress design method, slender walls and shear walls may be designed by the strength design method specified in Sec 7.7. The structure shall be proportioned such that eccentricity of loading on the members is as small as possible. Eccentric loading shall preferably be avoided by providing: (a) adequate bearing of floor/roof on the walls (b) adequate stiffness in slabs, and (c) fixity at the supports. 7.4.2.2 Effective height (a) Wall: The effective height of a wall shall be taken as the clear height between the lateral supports at top and bottom in a direction normal to the axis considered. For members not supported at the top normal to the axis considered, the effective height is twice the height of the member above the support. Effective height less than the clear height may be used if justified. (b) Column: Effective height of the column shall be taken as actual height for the direction it is laterally supported and twice the actual height for the direction it is not laterally supported at the top normal to the axis considered. (c) Opening in Wall: When openings occur in a wall such that masonry between the openings is by definition a column, effective height of masonry between the openings shall be obtained as follows: (i) When wall has full restraint at the top, effective height for the direction perpendicular to the plane of wall equals 0.75… plus 0.25…r, where … is the distance between supports and …r is the height of the taller opening; and effective height for the direction parallel to the wall equals …. (ii) When wall has partial restraint at the top and bottom, effective height for the direction perpendicular to the plane of wall equals … when height of neither opening exceeds 0.5… and it is equal to 2… when height of any opening exceeds0.5…; and effective height for the direction parallel to the plane of the wall equals 2…. 7.4.2.3 Effective length Effective length of a wall for different support conditions shall be as given in Table 6.7.8. 7.4.2.4 Effective thickness The effective thickness of walls and columns for use in the calculation of slenderness ratio, shall be defined as follows: (a) Solid Walls: The effective thickness of solid walls, faced walls or grouted walls shall be the specified thickness of the wall. (b) Solid Walls with Raked Mortar Joints: The effective thickness of solid walls with raked mortar joints shall be the minimum thickness measured at the joint. (c) Cavity Walls: When both limbs of a cavity wall are axially loaded, each limb shall be considered independently and the effective thickness of each limb shall be determined as in (a) or (b) above. If one of the limbs is axially loaded, the effective thickness of the cavity wall shall be taken as the square root of the sum of the squares of the effective thicknesses of the limbs. (d) Walls Stiffened by Pilasters: When solid or cavity walls are stiffened by pilasters at intervals, the effective thickness to be used for the calculation of ℎr/› ratio shall be determined as follows: (i) Solid Walls: For stiffened solid walls the effective thickness shall be the specified thickness multiplied by the stiffening coefficient, k, values of which are given below: :/ö: Stiffening Coefficient, k* :/ö = ! :/ö = :/ö = 1.0 1.4 2.0 1.0 1.3 1.7 1.0 1.2 1.4 1.0 1.1 1.2 20 or more 1.0 1.0 1.0- Linear interpolation is permitted for obtaining intermediate values of k
Table 6.7.8: Effective Length of Walls
Support Condition
Effective Length
Where a wall is continuous and is supported by cross wall and there is no
opening within a distance of H/8 from the face of cross wall. OR,
Where a wall is continuous and is supported by pier/buttresses
conforming to Sec 7.4.3.3 (c).
0.8‹
Where a wall is supported by cross wall at one end and continuous with
cross wall at other end. OR,
Where a wall is supported by pier/buttresses at one end and continuous
with pier/buttresses at other end conforming to Sec 7.4.3.3 (c).
0.9‹
Where a wall is supported at each end by cross wall. OR,
Where a wall is supported at each end by pier/buttresses conforming to
Sec 7.4.3.3 (c).
1.0‹
Where a wall is free at one end and continuous with a cross wall at the
other end. OR,
Where a wall is free at one end and continuous with a pier/buttresses at
the other end conforming to Sec 7.4.3.3 (c).
1.5‹
Where a wall is free at one end and supported at the other end by a cross
wall. OR,
Where a wall is free at one end and supported at the other end by a
pier/buttresses conforming to Sec 7.4.3.3 (c).
2.0‹
7.4.2.5
Slenderness ratio
(a) Walls: For a wall, slenderness ratio shall be the ratio of effective
height to effective thickness or effective length to effective thickness
whichever less is. In case of a load bearing wall, slenderness ratio
shall not exceed 20.
(b) Column: For a column, slenderness ratio shall be taken to be the
greater of the ratio of effective heights to the respective effective
thickness in the two principal directions. Slenderness ratio for a load
bearing column shall not exceed 12.
7.4.2.6
Effective area
The effective cross-sectional area shall be based on the minimum bedded area of
the hollow units, or the gross area of solid units plus any grouted area. If hollow
units are used perpendicular to the direction of stress, the effective area shall be
lesser of the minimum bedded area or the minimum cross-sectional area. If bed
joints are raked, the effective area shall be correspondingly reduced. Effective
areas for cavity walls shall be that of the loaded wythes.
7.4.2.7
Flexural resistance of cavity walls
For computing the flexural resistance, lateral loads perpendicular to the plane of
the wall shall be distributed to the wythes according to their respective flexural
rigidities.
7.4.2.8
Effective width of intersecting walls
Where a shear wall is anchored to an intersecting wall or walls, the width of the
overhanging flange formed by the intersected walls on either side of the shear
wall shall not exceed 6 times the thickness of the intersected wall. Limits of the
effective flange may be waived if justified. Only the effective area of the wall
parallel to the shear forces may be assumed to carry horizontal shear.
7.4.3
Supports
7.4.3.1
Vertical support
Structural members providing vertical support of masonry shall provide a
bearing surface on which the initial bed joint shall not be less than 6 mm or
more than 25 mm and shall be of noncombustible materials, except where
masonry is a nonstructural decorative feature or wearing surface.
7.4.3.2 Vertical deflection
Elements supporting masonry shall be designed so that their vertical deflection does not exceed 1/600 of the clear span under total loads. Lintels shall be supported on each end such that allowable stresses in the supporting masonry are not exceeded. The minimum bearing length shall be 100 mm. 7.4.3.3 Lateral support (a) Lateral support of masonry may be provided by cross walls, columns, piers, counter forts or buttresses when spanning horizontally or by floors, beams or roofs when spanning vertically. (b) Lateral supports for a masonry element such as load bearing wall or column shall be provided to (i) limit the slenderness of a masonry element so as to prevent or reduce possibility of buckling of the member due to vertical loads; and (ii) resist the horizontal components of forces so as to ensure stability of a structure against overturning. (c) From consideration of slenderness (i.e. requirement b(i) above), masonry elements may be considered to be laterally supported if (i) in case of a wall, where slenderness ratio is based on effective height, floor/roof slab (or beams and slab) irrespective of the direction of span, bears on the supported wall as well as cross walls, to the extent of at least 100 mm; (ii) in case of a wall, when slenderness ratio is based on its effective length, a cross wall/pier/buttress of thickness equal to or more than half the thickness of the supported wall or 125 mm, whichever is more and average length equal to or more than one-fifth of the height of the wall, is built at right angle to the wall and properly bonded; (iii) in case of a column, an RC or timber beam/RS joist/roof truss, is supported on the column. In this case, the column will not be considered to be laterally supported in the direction at right angle to it; and (iv) in case of a column, an RC beam forming a part of beam and slab construction, is supported on the column, and the slab adequately bears on stiffening walls. This construction will provide lateral support to the column, in the direction of both horizontal axes. 7.4.4 Stability A wall or column subject to vertical and lateral loads may be considered to provide adequate lateral support from consideration of stability, if the construction providing the support is capable of resisting the following forces: (a) Simple static reactions at the point of lateral support to all the lateral loads; plus (b) A lateral load equal to 2.5% of the total vertical load that the wall or column is designated to carry at the point of lateral support.7.4.4.1 In case of load bearing buildings up to five storeys, stability
requirements may be considered to have been satisfied if the following conditions are met. (a) Height to width ratio of building does not exceed 2. (b) Cross walls acting as stiffening walls continuous from outer wall to outer wall or outer wall to a load bearing inner wall, and of thickness and spacing as given in Table 6.7.9 are provided. If stiffening wall or walls that are in a line, are interrupted by openings, length of solid wall or walls in the zone of the wall that is to be stiffened shall be at least one-fifth of the height of the opening. (c) Floors and roof either bear on cross walls or are properly anchored to those walls such that all lateral loads are safely transmitted to those walls and through them to the foundation. (d) Cross walls are built jointly with the bearing walls and jointly mortared, or interconnected by toothing. Cross walls may be anchored to walls to be supported by ties of noncorrosive metal of minimum section 6 x 35 mm and length 60 mm with ends bent at least 50 mm, maximum vertical spacing of ties being 1.2 m.Table 6.7.9: Thickness and Spacing of Stiffening Walls Thickness of Load Bearing Wall to be Stiffened (mm) Height of Storey not to Exceed (m) Stiffening Wall * Thickness not less than Maximum spacing (m) 1 to 3 storeys (mm) 4 and 5 storeys (mm) above 300 3.2 3.2 3.4 5.0
4.5 6.0 8.0 8.0- Storey height and maximum spacing as given are centre to centre dimensions.
7.4.4.2 In case of walls exceeding 8 m in length, safety and adequacy of lateral
supports shall always be checked by structural analysis.7.4.4.3 A trussed roofing may not provide lateral support unless special
measures are adopted to brace and anchor the roofing. However, in case of residential and similar buildings of conventional design with trussed roofing having cross walls, it may be assumed that stability requirements are met by the cross walls and structural analysis for stability may be dispensed with.7.4.4.4 In case of walls exceeding 8 m in length, safety and adequacy of lateral
supports shall always be checked by structural analysis.7.4.4.5 A trussed roofing may not provide lateral support unless special
measures are adopted to brace and anchor the roofing. However, in case of residential and similar buildings of conventional design with trussed roofing having cross walls, it may be assumed that stability requirements are met by the cross walls and structural analysis for stability may be dispensed with.7.4.4.6 In case of external walls of basement and plinth, stability requirements
of Sec 7.4.4 may be considered to be satisfied if : (a) Bricks used in basement and plinth have a minimum crushing strength of 5 N/mm2 and mortar used in masonry is of Type M3 or better, (b) Clear height of ceiling in basement does not exceed 2.6 m, (c) In the zone of action of soil pressure on basement walls, traffic load excluding any surcharge due to adjoining buildings does not exceed 5 kN/m2, (d) Minimum thickness of basement walls is in accordance with Table 6.7.10. In case there is surcharge on basement walls from adjoining buildings, thickness of basement walls shall be based on structural analysis.
Table 6.7.10: Minimum Thickness of Basement Wall
Minimum Nominal
Thickness of Basement Wall
(mm)
Height of the Ground above Basement
Floor Level
Wall Loading (Permanent Load)
Less than 50 kN/m
More than 50 kN/m
2.0 m
1.4 m
2.5 m
1.8 m
7.4.4.7 Free standing wall Free standing walls, subject to wind pressure or seismic forces shall be designed on the basis of permissible tensile stress in masonry or stability consideration. However in Seismic Zones 1 and 2, free standing walls may be proportioned without making any design calculations with the help of Table 6.7.11 provided the mortar used is of type not leaner than M3. For parapet wall see Sec 7.4.9.4. 7.4.5 Structural Continuity Intersecting structural elements intended to act as a unit shall be anchored together to resist the design forces. Walls shall be anchored together to all floors, roofs or other elements which provide lateral support for the wall. Where floors or roofs are designed to transmit horizontal forces to walls, the anchorages to the walls shall be designed to resist the horizontal forces. Table 6.7.11: Height to Thickness Ratio of Free Standing Wall Design Wind Pressure, N/m2 Height to Thickness Ratio Up to 300 Note: Height is to be taken from 150 mm below ground level or top of footing/ foundation block, whichever is higher, and up to the top edge of the wall.
7.4.5.1
Multi-wythe Walls
All wythes shall be bonded by grout or tied together by corrosion resistant wall
ties or joint reinforcement as follows:
(a) Wall Ties in Cavity Wall Construction: Wall ties shall be of sufficient
length to engage all wythes. The portion of the wall ties within the
wythe shall be completely embedded in mortar or grout. The ends of
the wall ties shall be bent to 90 degree angles with an extension not
less than 50 mm long. Wall ties not completely embedded in mortar
or grout between wythes shall be a single piece with each end
engaged in each wythe.
There shall be at least one 6 mm diameter wall tie for each 0.45 m2 of
wall area. For cavity walls in which the width of the cavity is greater
than 75 mm, but not more than 115 mm, at least one 6 mm diameter
wall tie for each 0.3 m2 of wall area shall be provided.
Ties in alternate courses shall be staggered. The vertical distance
between ties shall not exceed 600 mm. The horizontal distance
between ties shall not exceed 900 mm. Additional ties spaced not
more than 900 mm apart shall be provided around and within 300
mm of the opening. Wall ties of different size and spacing may be
used if they provide equivalent strength between wythes.
(b) Wall Ties for Grouted Multi-wythe Construction: The two wythes
shall be bonded together with at least 6 mm diameter steel wall ties
for each 0.20 m2 of area. Wall ties of different size and spacing may be
used if they provide equivalent strength between wythes.
(c) Joint Reinforcement: Prefabricated joint reinforcement for masonry
walls shall have a minimum of one cross wire of at least 3 mm
diameter steel for each 0.2 m2 of wall area. The vertical spacing of the
joint reinforcement shall not exceed 400 mm. The longitudinal wires
shall be thoroughly embedded in the bed joint mortar. The joint
reinforcement shall engage all wythes.
Where the space between tied wythes is filled with grout or mortar,
the allowable stresses and other provisions for masonry bonded
walls shall apply. Where the space is not filled, tied walls shall
conform to the allowable stress, lateral support, thickness (excluding
cavity), height and tie requirements of cavity walls.
7.4.6
Joint Reinforcement and Protection of Ties
The minimum mortar cover between ties or joint reinforcement and any
exposed face shall be 15 mm. The thickness of grout or mortar between
masonry units and joint reinforcement shall not be less than 6 mm, except that
smaller diameter reinforcement or bolts may be placed in bed joints which are
at least twice as thick as the diameter of the reinforcement.
7.4.7
Pipes and Conduits
Pipe or conduit shall not be embedded in any masonry so as to reduce the
capacity to less than that necessary for required stability or required fire
protection, except the following:
(a) Rigid electrical conduit may be embedded in structural masonry
when their location has been detailed on the approved plan.
(b) Any pipe or conduit may pass vertically or horizontally through any
masonry by means of a sleeve at least large enough to pass any hub
or coupling on the pipeline. Such sleeves shall not be placed closer
than three diameters, centre to centre, nor shall they unduly impair
the strength of construction.
(c) Placement of pipes or conduits in unfilled cores of hollow unit
masonry shall not be considered as embedment.
7.4.8
Loads and Load Combination
7.4.8.1 Design loads
All design loads and other forces to be taken for the design of masonry structures shall conform to Chapter 2, Loads. 7.4.8.2 Load dispersion The angle of dispersion of vertical load on walls shall be taken as not more than 30o from the vertical. 7.4.8.3 Distribution of concentrated vertical loads in walls The length of wall, laid up in running bond, which may be considered capable of working at the maximum allowable compressive stresses to resist vertical concentrated loads, shall not exceed the centre to centre distance between such loads, nor the width of bearing area plus four times the wall thickness. Concentrated vertical loads shall not be assumed distributed across continuous vertical mortar or control joints unless elements designed to distribute the concentrated vertical loads are employed. 7.4.8.4 Loads on non-bearing wall Masonry walls used as interior partition or as exterior surfaces of building which do not carry vertical loads imposed by other elements of the building shall be designed to carry their own weight plus any superimposed finish and lateral forces. Bonding or anchorage of nonbearing walls shall be adequate to support the walls and to transfer lateral forces to the supporting structures. 7.4.8.5 Load combinations Load combination for design of masonry structures shall conform to requirements of Sec 2.7 Chapter 2 Part 6. 7.4.9 Minimum Design Dimensions 7.4.9.1 Minimum thickness of load bearing walls The nominal thickness of masonry bearing walls in building shall not be less than 250 mm. Exception: Stiffened solid masonry bearing walls in one-storey buildings may have a minimum effective thickness of 165 mm when not over 3 m in height, provided that when gable construction is used an additional 1.5 m height may be permitted at the peak of the gable. 7.4.9.2 Variation in thickness When a change in thickness due to minimum thickness requirements occurs between floor levels, the greater thickness shall be carried up to the higher floor level. 7.4.9.3 Decrease in thickness When walls of masonry of hollow units or masonry bonded hollow walls are decreased in thickness, a course or courses of solid masonry shall be constructed between the walls below and the thinner wall above, or special units or construction shall be used to transmit the loads from wythes to the walls below. 7.4.9.4 Parapet wall Parapet walls shall be at least 200 mm thick and height shall not exceed 4 times the thickness. The parapet wall shall not be thinner than the wall below. 7.5 Design of Unreinforced Masonry 7.5.1 General The requirements of this Section are applicable to unreinforced masonry in addition to the requirements of Sec 7.4. 7.5.2 Design of Members Subjected to Axial Compression The stresses due to compressive forces applied at the centroid of any load bearing wall, column and pilaster may be computed by Eq. 6.7.22 below assuming uniform distribution over the effective area. e a A P f (6.7.22) 7.5.3 Design of Members Subjected to Combined Bending and Axial Compression (a) Compressive stresses due to combined bending and axial load shall satisfy the requirements of Sec 7.3.5. (b) Resultant tensile stress due to combined bending and axial load shall not exceed the allowable flexural tensile stress, ƒ as specified in Sec 7.3. 7.5.4 Design of Members Subjected to Flexure Stresses due to flexure calculated by Eq. 6.7.23 below shall not exceed the values given in Sec 7.3.5. I Mc fb (6.7.23) 7.5.5 Design of Members Subjected to Shear Shear calculations in flexural members and shear walls shall be based on Eq.6.7.24 below.
M = s ßì (6.7.24) 7.5.6 Design of Arches Geometrical form and the cross-sectional dimensions of masonry arch shall be selected such that the line of thrust at any section of the arch is kept within the middle third of the section of the arch rib. The elastic theory of arches shall be permitted for the analysis of unreinforced masonry arches. All supports of arches shall be capable of developing the required horizontal thrust without suffering unacceptable displacements. Every arch must be designed to resist the stresses due to the following loads: (a) Gravity loads : (i) Dead loads shall be placed in conformity with their actual distribution. (ii) Live loads shall be positioned to cover entire span or part of the span as necessary to produce the maximum stresses at the crown, springing and all other sections of the arch rib. (b) Loads due to temperature change. (c) Shrinkage load due to setting and hardening. (d) Shortening of arch rib under thrust caused by loads. 7.5.7 Footings and Corbels The slope of footing and corbelling (measured from the horizontal to the face of the corbelled surface) shall not be less than 60 degrees. The maximum horizontal projection of corbelling from the plane of the wall shall be such that stress at any section does not exceed the allowable value. 7.6 Design of Reinforced Masonry 7.6.1 General The requirements of this Section are in addition to those specified in Sec 7.4 and are applicable to reinforced masonry. Plain bars larger than 6 mm in diameter shall not be used. 7.6.1.1 Assumptions The following assumptions shall be applicable for this Section. (a) Masonry carries no tensile stress. (b) Reinforcement is completely surrounded by and bonded to masonry material so that they work together as a homogeneous material within the range of working stresses. 7.6.2 Design of Members Subjected to Axial Compression Stresses due to compressive forces applied at the centroid of load bearing wall, column and pilaster may be computed assuming uniform distribution over the effective area. Stress shall be calculated from Eq. 6.7.25 below: e a A p f (6.7.25) 7.6.3 Design of Members Subjected to Combined Bending and Axial Compression Stress due to combined bending and axial loads shall satisfy the requirements of Sec 7.3.5. Columns and walls subjected to bending with or without axial loads shall meet all applicable requirements for flexural design. The design of walls with an (h//t) ratio larger than 30 shall be based on forces and moments determined from analysis of structure. Such analysis shall take into account influence of axial loads and variable moment of inertia on member stiffness and fixed end moments, effect of deflections on moments and forces, and the effects of duration of loads. 7.6.4 Design of Members Subjected to Shear Force Shearing stresses in flexural members and shear walls shall be computed by bjd V νf (6.7.26) When the computed shear stress exceeds the allowable value, web reinforcement shall be provided and designed to carry the total shear force. Both vertical and horizontal shear stresses shall be considered. The area required for shear reinforcement placed perpendicular to the longitudinal reinforcement shall be computed by Eq. 6.7.27 below: d F sV A s ν (6.7.27) Spacing of vertical shear reinforcement shall not exceed d/2, nor 600 mm. Inclined shear reinforcement shall have a maximum spacing of 0.3750(1 + $›u), but not greater than 600 mm, where α is the acute angle between inclined bar and the horizontal. 7.6.5 Design of Members Subjected to Flexural Stress 7.6.5.1 Rectangular elements Rectangular flexural elements shall be designed in accordance with the following equations or other methods based on the simplified assumptions. (a) Compressive stress in the masonry: jk f b bd M (6.7.28) (b) Tensile stress in the longitudinal reinforcement: d f j A M s s (6.7.29) (c) Design coefficients :- = [(ঙ্চ্)য় + ২ঙ্চ্]/য় −ঙ্চ্ (6.7.30)
- =
- Žk ! q + ÕŽk^ + Žk`Ù∆k (6.7.37) Where,
Ï'ªà Ï
and
= depth of stress block due to factored loads.
=
ß&Ï'ªà ².Í×Å 1
The strength reduction factor • for flexure shall be 0.80.
(d) Design Assumptions: The following are the design assumptions for
calculation of nominal strength.
(i)
Nominal strength of singly reinforced masonry wall cross-
sections subject to combined flexure and axial load shall be
based on applicable conditions of equilibrium and compatibility
of strains.
(ii) Strain in reinforcement and masonry walls shall be assumed
directly proportional to the distance from the neutral axis.
(iii) Maximum usable strain at extreme masonry compression fibre
shall be assumed equal to 0.003.
(iv) Stress in reinforcement below specified yield strength shall
be taken as times steel strain. For strains greater than that
corresponding to stress in reinforcement shall be considered
independent of strain and equal to.
(v) Tensile strength of masonry walls shall be neglected in flexural
calculations of strength, except for deflection calculation.
(vi) Relationship between masonry compressive stress and masonry
strain may be assumed to be rectangular as defined by the
following:
Masonry stress of 0.85fr shall be assumed uniformly
distributed over an equivalent compression zone bounded by
edges of the cross-section and a straight line located parallel to
the neutral axis at a distance a = 0.85c from the fibre of
maximum compressive strain.
Distance c from fibre of maximum strain to the neutral axis shall
be measured in a direction perpendicular to that axis.
7.7.1.3
Deflection calculation
The mid-height deflection, ∆ under service lateral and vertical loads (without
load factors) shall be limited to:
∆= 0.007ℎ
(6.7.39)
The mid-height deflection shall be computed by:
When, p! ≤p
∆=
¹&Zë
îÍ”×ÀÁ
(6.7.40)
When, p « p! « ph
∆=
¹±ºZë
îÍ”×ÀÁ + 5
(¹&ìºØ¹±º)Zë
îÍ”×À±º
(6.7.41)
The cracking moment strength of the wall p shall be determined by:
p = .
(6.7.42)
The modulus of rupture, shall be determined form Table 6.7.13.
Table 6.7.13: Values of the Modulus of Rupture,
Type of Masonry
Fully Grouted
Partially Grouted
Solid Masonry
0.17fr ≤0.65 N/mmq
Not allowed
Hollow Unit Masonry
0.33fr ≤1.2 N/mmq
0.21fr ≤0.65 N/mmq
7.7.2
Design of Shear Walls
Based on ultimate strength design, the procedures described below may be used
as an alternative to the procedure specified in Sec 7.6 for the design of
reinforced hollow unit masonry shear walls. Provisions for quality control
during construction of the shear wall are specified in Sec 7.3.4
7.7.2.1
Required strength
The required strength to resist different combinations of loads shall be
determined in accordance with Sec 2.7.3.1 Chapter 2 of this Part.
7.7.2.2
Design strength
Shear walls shall be proportioned such that the design strength exceeds the
required strength. Design strength in terms of axial force, shear force and
moment provided by the shear wall shall be computed as the nominal strength
multiplied by the strength reduction factor •.
Strength reduction factor •
shall be as follows:
(a) For axial load and axial load with flexure • = 0.65
(b) For members with less than 410 N/mm2 and with symmetrical
reinforcement, • may be increased linearly to 0.85 as •Žh decreases
from 0.10fr -! or 0.25Ž1 to zero.
For solid grouted walls Ž1 may be calculated using:
Ž1 = 0.85fr y21
(6.7.43a)
Where,
2y = 0.85 •>¬/ ¸•>¬ + /
¼ 0
(6.7.43b)
(c) For shear • = 0.60. The shear strength reduction factor may be
increased to 0.80 for any shear wall when its nominal shear strength
exceeds the shear corresponding to development of its nominal flexural
strength for the factored load combination.
7.7.2.3
Design Assumptions for Nominal Strength
(a) Nominal strength of shear wall cross-sections shall be based on
assumptions specified in Sec 7.7.1.2(d).
(b) The maximum usable strain •fk, at the extreme masonry
compression fibre shall not exceed 0.003.
(c) fr shall not be less than 7 N/mm2 or greater than 20 N/mm2.
7.7.2.4
Axial Strength
The nominal axial strength of shear walls supporting axial loads only shall be
calculated by Eq 6.7.44.
Žo = 0.85fr (-! −-) + -
(6.7.44)
The shear wall shall be designed for the axial strength Pu, such that
Žk ≤∅(0.80)޲
(6.7.45)
7.7.2.5
Shear strength
(a) The nominal shear strength shall be determined by the provisions as
specified in (b) or (c) below. The maximum nominal shear strength
values are given in Table 6.7.14.
Table 6.7.14: Maximum Nominal Shear Strength Values
@∗
ô
ô
81
r
≤ 0.25
≥1.00
72.0
48.0
- M is the maximum bending moment that occurs simultaneously with the shear load V at the section under consideration. Interpolation may be by straight line for M/Vd values between 0.25 and 1.00.
7.8.5.1 for all seismic areas using this method of analysis.
(b) When the shear wall failure mode is in flexure, the nominal flexural strength of the shear wall shall be at least 1.8 times the cracking moment strength of a fully grouted wall or 3.0 times the cracking moment strength of a partially grouted wall as obtained from Eq. 6.7.42. (c) All continuous reinforcement shall be anchored or spliced in accordance with Sec 7.6.6.4 with = 0.5. (d) Vertical reinforcement shall not be less than 50 percent of the horizontal reinforcement. (e) Spacing of horizontal reinforcement within the region defined in Sec 7.7.2.5(c) shall not exceed three times the nominal wall thickness or 600 mm, whichever is smaller. 7.7.2.7 Boundary member Boundary members shall be as follows: (a) The need for boundary members at boundaries of shear wall shall be determined using the provisions set forth in (b) or (c) below. (b) Boundary members shall be provided when the failure mode is flexure and the maximum extreme fibre stress exceeds 0.2fr . The boundary members may be discontinued where the calculated compressive stresses are less than 0.15fr . Stresses may be calculated for the factored forces using a linearly elastic model and gross section properties. (c) When the failure mode is flexure, boundary member shall be provided to confine all vertical reinforcement whose corresponding masonry compressive stress exceeds 0.4fr . The minimum length of the boundary member shall be 3 times the thickness of the wall. (d) Boundary members shall be confined with minimum of 10 mm diameter bars at a maximum of 200 mm spacing or equivalent within the grouted core and within the region defined by the base of the shear wall and a plane at a distance ‹^ above the base of the shear wall. 7.8 Earthquake Resistant Design 7.8.1 General All masonry structures constructed in the Seismic Zones 2, 3 and 4 shown in Figure 6.2.13 shall be designed in accordance with the provisions of this Section. 7.8.2 Loads Seismic forces on masonry structures shall be determined in accordance with the provisions of Sec 2.5 Chapter 2 of this Part. 7.8.3 Materials (a) Well burnt clay bricks and concrete hollow blocks having a crushing strength not less than 12 N/mm2 shall be used. (b) Mortar not leaner than p½ shall be used for masonry constructions. 7.8.4 Provisions for Seismic Zone 2 and 3 7.8.4.1 Wall Reinforcement Vertical reinforcement of at least 12 mm diameter shall be provided continuously from support to support at each corner, at each side of each opening, at the ends of walls and at a maximum spacing of 1.2 m horizontally throughout the wall. Horizontal reinforcement not less than 12 mm diameter shall be provided: (a) at the bottom and top of wall openings and shall extend at least 40 bar diameters, with a minimum of 600 mm, past the opening, (b) continuously at structurally connected roof and floor levels and at the top of walls, (c) at the bottom of the wall or in the top of the foundations when dowelled to the wall, (d) at maximum spacing of 3.0 m unless uniformly distributed joint reinforcement is provided. Reinforcement at the top and bottom of openings when continuous in the wall may be used in determining the maximum spacing specified in item (a) above. 7.8.4.2 Stack bond Where stack bond is used, the minimum horizontal reinforcement ratio shall be 0.0007y›. This ratio shall be satisfied by uniformly distributed joint reinforcement or by horizontal reinforcement spaced not more than 1.2 m and fully embedded in grout or mortar. 7.8.4.3 Columns Columns shall be reinforced as specified in Sec 7.6.6.1. 7.8.5 Provisions for Seismic Zone 4 All masonry structures built in Seismic Zone 4 shall be designed and constructed in accordance with requirements for Seismic Zone 2 and with the following additional requirements and limitations. Reinforced hollow unit stack bond construction which is part of the seismic resisting system shall use open-end units so that all head joints are made solid, shall use bond beam units to facilitate the flow of grout and shall be grouted solid. 7.8.5.1 Wall reinforcement Reinforced masonry walls shall be reinforced with both vertical and horizontal reinforcement. The sum of the areas of horizontal and vertical reinforcement shall be at least 0.002 times the gross cross-sectional area of the wall and the area of reinforcement in either direction shall not be less than 0.0007 times the gross cross-sectional area of the wall. The spacing of reinforcement shall not exceed 1.20 m. The diameter of reinforcing bar shall not be less than 10 mm except that joint reinforcement may be considered as part of all of the requirements for minimum reinforcement. Reinforcement shall be continuous around wall corners and through intersections. Only reinforcement which is continuous in the wall or element shall be considered in computing the minimum area of reinforcement. Reinforcement with splices conforming to Sec7.6.6.7 shall be considered as continuous reinforcement.
7.8.5.2 Column reinforcement The spacing of column ties shall be not more than 225 mm for the full height of columns stressed by tensile or compressive axial overturning forces due to the seismic loads, and 225 mm for the tops and bottoms of all other columns for a distance of one sixth of the clear column height, but not less than 450 mm or maximum column dimension. Tie spacing for the remaining column height shall be not more than 16 bar diameters, 48 tie diameters or the least column dimension, but not more than 450 mm. 7.8.5.3 Stack bond Where stack bond is used, the minimum horizontal reinforcement ratio shall be 0.0015y›. If open-end units are used and grouted solid, the minimum horizontal reinforcement ratio shall be 0.0007y›. 7.8.5.4 Minimum dimension (a) Bearing Walls: The nominal thickness of reinforced masonry bearing walls shall be not less than 150 mm except that nominal 100 mm thick load bearing reinforced hollow clay unit masonry walls may be used, provided net area unit strength exceeds 55 N/mm2, units are laid in running bond, bar sizes do not exceed 12 mm with no more than two bars or one splice in a cell, and joints are flush cut, concave or a protruding V section. (b) Columns: The least nominal dimension of a reinforced masonry column shall be 375 mm except that if the allowable stresses are reduced to 50 percent of the values given in Sec 7.3, the minimum nominal dimension shall be 250 mm. 7.8.5.5 Shear wall (a) When calculating shear or diagonal tension stresses, shear walls which resist seismic forces shall be designed to resist 1.5 times the forces specified in Chapter 2, Loads. (b) The portion of the reinforcement required to resist shear shall be uniformly distributed and shall be joint reinforcing, deformed bars, or a combination thereof. The maximum spacing of reinforcement in each direction shall be not less than the smaller of one-half the length or height of the element or more than 1.20 m. Joint reinforcement used in exterior walls and considered in the determination of the shear strength of the member shall conform to the requirement “Joint Reinforcement for Masonry” (UBC Standard No. 24-15) or “Standard Specification for Steel Wire, Plain, for Concrete Reinforcement”, (ASTM, A82). Reinforcement required to resist in-plane shear shall be terminated with a standard hook or with an extension of proper embedment length beyond the reinforcing at the end of the wall section. The hook or extension may be turned up, down or horizontally. Provisions shall be made not to obstruct grout placement. Wall reinforcement terminating in columns or beams shall be fully anchored into these elements. (c) Multi-wythe grouted masonry shear walls shall be designed with consideration of the adhesion bond strength between the grout and masonry units. When bond strengths are not known from previous tests, the bond strength shall be determined by test. 7.8.5.6 Hook The standard hook for tie anchorage shall have a minimum turn of 135 degrees plus an extension of at least 6 bar diameters, but not less than 100 mm at the free end of the bar. Where the ties are placed in the horizontal bed joints, the hook shall consist of a 90 degree bend having a radius of not less than 4 tie diameters plus an extension of 32 tie diameters. 7.8.5.7 Mortar joints between masonry and concrete Concrete abutting structural masonry such as at starter courses or at wall intersections not designed as true separation joints shall be roughened to a full amplitude of` 1.5 mm and shall be bonded to the masonry as per the requirements of this Section as if it were masonry. 7.8.6 Additional Requirements 7.8.6.1 Opening in bearing walls (a) Tops of all openings in a storey shall preferably be at the same level so that a continuous band could be provided over them, including the lintels throughout the building. (b) The total width of the openings shall not be more than half of the length of the walls between the adjacent cross walls, except as provided in (f) below. (c) The opening shall preferably be located away from the corner by a clear distance of at least one-eighth of the height of the opening for Seismic Zones 2 and 3, and one-fourth of the height for Seismic Zone 4. (d) The horizontal distance between two openings shall not be less than one-fourth of the height of the shorter opening for Seismic Zones 2 and 3, and one-half of the height for Seismic Zone 4. (e) The vertical distance between openings one above the other shall be not less than 600 mm. (f) Where openings do not comply with the requirements of (b) and (c) above, they shall be strengthened in accordance with Sec 7.8.6.5. (g) If a window or ventilator is to be projected out, the projection shall be in reinforced masonry or concrete and well anchored. (h) If the height of an opening is approximately full height of a wall, dividing the wall into two portions, these portions of the wall shall be reinforced with horizontal reinforcement of 6 mm diameter bars at not more than 600 mm intervals, one on inner and one on outer face, properly tied to vertical steel at jambs and corners or junctions of walls where used. (i) The use of arches to span over the openings is a source of weakness and shall be avoided unless steel ties are provided. 7.8.6.2 Strengthening arrangements All masonry buildings shall be strengthened by the methods specified in Table 6.7.15. Table 6.7.15: Strengthening of Masonry Buildings for Earthquake Seismic Zones No. of Storey Strengthening Arrangements to be Provided. Up to 4 a) Masonry mortar shall not be leaner than p½ 2, 3 Up to 2 with pitched roof a) Masonry mortar shall not be leaner than p½ b) By lintel and roof band (Sec 7.8.6.3) c) By vertical reinforcement at corners and junctions of walls (Sec 7.8.6.4) d) Bracing in plan at tie level for pitched roof* 3 to 4 a) Masonry mortar shall not be leaner than p½ b) By lintel and roof band (Sec 7.8.6.3) c) By vertical reinforcement at corners and junctions of walls (Sec 7.8.6.4) d) Vertical reinforcement at jambs of openings (Sec 7.8.6.5) e) Bracing in plan at tie level for pitched roof* Seismic Zones No. of Storey Strengthening Arrangements to be Provided. Up to 4 a) Masonry mortar shall not be leaner than p½ b) By lintel and roof band (Sec 7.8.6.3) c) By vertical reinforcement at corners and junctions of walls (Sec 7.8.6.4) d) Vertical reinforcement at jambs of openings (Sec 7.8.6.5) e) Bracing in plan at tie level for pitched roof* At tie level all the trusses and the gable end shall be provided with diagonal bracing in plan so as to transmit the lateral shear due to earthquake force to the gable walls acting as shear walls at the ends. 7.8.6.3 Bands Roof band need not be provided underneath reinforced concrete or brickwork slabs resting on bearing walls, provided that the slabs are continuous over parts between crumple sections, if any, and cover the width of end walls fully. The band shall be made of reinforced concrete with r not less than 20 N/mm2 or reinforced brickwork in cement mortar not leaner than 1: 4. The bands shall be to the full width of the wall and not less than 75 mm in depth and shall be reinforced as indicated in Table 6.7.16. In case of reinforced brickwork, the thickness of joints containing steel bars shall be increased so as to have a minimum mortar cover of 6 mm around the bar. In bands of reinforced brickwork, the area of steel provided shall be equal to that specified above for reinforced concrete bands. Table 6.7.16: Band Reinforcement Seismic Zones Plain Mild Steel Bars High Strength Deformed Bars Links 2, 3 2 - 12 mm dia, one on each face of the wall with suitable cover 2 - 10 mm dia, one on each face of the wall with suitable cover 6 mm dia, 150 mm c/c 2 - 16 mm dia, one on each face of the wall with suitable cover 2 - 12 mm dia, one on each face of the wall with suitable cover 6 mm dia, 150 mm c/c7.8.6.4 Strengthening of corner and junctions Vertical steel at corners and junctions of walls which are up to one and a half bricks thick shall be provided either with mild steel or high strength deformed bars as specified in Table 6.7.17. For thicker walls, reinforcement shall be increased proportionately. The reinforcement shall be properly embedded in the plinth masonry of foundations and roof slab or roof band so as to develop its tensile strength in bond and passing through the lintel bands in all storeys. Bars in different storeys may be welded or suitably lapped. (a) Typical details of vertical steel in brickwork and hollow block at corners, T-junctions and jambs of opening are shown in Figures 6.7.1 and 6.7.2. (b) Details of vertical reinforcement given in Table 6.7.17 are applicable to brick masonry and hollow block masonry. 7.8.6.5 Strengthening of jambs of openings Openings in bearing walls shall be strengthened, where necessary, by providing reinforced concrete members or reinforcing the brickwork around them as shown in Figure 6.7.3. 7.8.6.6 Walls adjoining structural framing Where walls are dependent on the structural frame for lateral support they shall be anchored to the structural members with metal ties or keyed to the structural members. Horizontal ties shall consist of 6 mm diameter U-bars spaced at a maximum of 450 mm on centre and embedded at least 250 mm into the masonry and properly tied to the vertical steel of the same member. Table 6.7.17: Vertical Reinforcement for Brick and Hollow Block Masonry No. of Storeys Storeys Diameter of Single Bar or Equivalent Area of Plain Mild Steel Bar to be Provided (mm) Diameter of Single Bar or Equivalent Area of High Strength Deformed Bar to be Provided (mm) Zone 2 and 3 Zone 4 Zone 2 and 3 Zone 4
nil nil Top Bottom nil nil nil nil Top Middle Bottom Top Third Second Bottom
Figure 6.7.1 Typical details of vertical reinforcement in brick masonry
Figure 6.7.2 Typical details of vertical reinforcement in hollow block masonry
Figure 6.7.3 Minimum reinforcement in walls and around openings in Seismic Zones 2, 3 and 4
7.9
Provisions For High Wind Regions
7.9.1
General
The provisions of this Section shall apply to masonry structures located at
regions where the basic wind speed is greater than 200 km/h.
7.9.2
Materials
Materials for masonry structures shall generally comply with the provisions of
Part 5; however, there are some special requirements for masonry construction
in high wind regions, which are given below:
(a) Burnt clay bricks shall have a compressive strength not less than 15
N/mm2,
(b) Grout shall have a minimum compressive strength of 12.5 N/mm2,
(c) Mortar for exterior walls and interior shear walls shall be type M1 or M2,
(d) Unburnt clay masonry units shall not be used.
7.9.3
Construction Requirements
Masonry construction shall comply with the provisions of Sec 7.10.
7.9.4
Foundation
Footings shall have a thickness of not less than 375 mm and shall be extended
450 mm below the undisturbed ground surface. Foundation stem wall shall
have the same width and reinforcement as the wall it supports.
7.9.5
Drainage
Walls retaining more than 1 m of earth and enclosing interior spaces or floors
below grade shall have minimum 100 mm diameter footing drain. A slope of
1:50 away from the building shall be provided around the building.
7.9.6
Wall Construction
7.9.6.1 Minimum thickness of different types of wall shall be as given in Table
6.7.18.7.9.6.2 All walls shall be laterally supported at the top and bottom. The
maximum unsupported height of bearing walls or other masonry walls shall be3.5 m. Gable end walls may be 4.5 m high at their peak.
7.9.6.3 The span of lintels over openings shall not exceed 3.5 m. All lintels shall
be reinforced and the reinforcement bars shall extend not less than 600 mm beyond the edge of opening and into lintel supports. 7.9.6.4 Walls shall be adequately reinforced.7.9.6.5 Anchors between walls and floors or roofs shall be embedded in
grouted cells or cavities and shall conform to Sec 7.9.7 below. Table 6.7.18: Minimum thickness of Walls in High Wind Region Type of Wall Minimum Thickness (mm) Unreinforced grouted brick wall Reinforced exterior bearing wall Unreinforced hollow and solid masonry wall Interior nonbearing wall 7.9.7 Floor and Roof Systems Floors and roofs of all masonry structures shall be adequately anchored with the wall it supports to resist lateral and uplift forces due to wind specified in Sec2.4 of this Part.
7.9.8 Lateral Force Resistance7.9.8.1 Strapping, approved framing anchors and mechanical fasteners, bond
beams and vertical reinforcement shall be installed to provide a continuous tie from the roof to foundation system as shown in Figure 6.7.4. In addition, roof and floor systems, masonry shear walls, or masonry or wood cross walls shall be provided for lateral stability.7.9.8.2 Floor and roof diaphragms shall be properly connected to masonry
walls. Gable and sloped roof members not supported at the ridge shall be tied by the ceiling joist or equivalent lateral ties located as close to where the roof members bear on the wall as practically possible and not at more than 1.2 m on centers. Collar ties shall not be used for these lateral ties.7.9.8.3 Masonry walls shall be provided around all sides of floor and roof
systems in accordance with Figure 6.7.5. The cumulative length of exterior masonry walls along each side of the floor or roof systems shall be at least 20 percent of the parallel dimension. Required elements shall be without openings and shall not be less that 1.25 m in width. Interior cross walls at right angles to bearing walls shall be provided when the length of the building perpendicular to the span of the floor of roof framing exceeds twice the distance between shear walls or 10 m, whichever is greater.7.9.8.4 When required interior cross wall shall be at least 1.8 m long and
reinforced with 2 mm wire joint reinforcement spaced not more than 400 mm on centre. Figure 6.7.4 Continuous tie from roof to foundation of masonry structure Figure 6.7.5 Masonry walls required in high wind regions 7.10 Construction7.10.1 General
Masonry shall be constructed according to the provisions of this Section.7.10.2 Storage and Preparation of Construction Materials
Storage, handling and preparation at the site shall conform to the following: (a) Masonry materials shall be stored in such a way that at the time of use the materials are clean and structurally suitable for the intended use. (b) All metal reinforcement shall be free from loose rust and other coatings that inhibit reinforcing bond. (c) Burnt clay units shall have a rate of absorption per minute not exceeding 1 litre/m2 at the time of lying. In the absorption test the surface of the unit shall be held 3 mm below the surface of the water. (d) Burnt clay units shall be thoroughly wetted before placing. Concrete masonry units shall not be wetted unless otherwise approved. (e) Materials shall be stored in such a manner that deterioration or intrusion of foreign materials is prevented and at the time of mixing the material conforms to the applicable requirements. (f) The method of measuring materials for mortar and grout shall be such that proportions of the materials can be easily controlled. (g) Mortar or grout mixed at the job site shall be mixed for a period of time not less than 3 minutes or more than 10 minutes in a mechanical mixer with the amount of water required to provide the desired workability. Hand mixing of small amounts of mortar is permitted. Mortar may be retempered. Mortar or grout which has hardened or stiffened due to hydration of the cement shall not be used, but under no case shall mortar be used two and one-half hours, nor grout used one and one-half hours, after the initial mixing water has been added to the dry ingredients at the job site.7.10.3 Placing Masonry Units
(a) The mortar shall be sufficiently plastic and units shall be placed with sufficient pressure to extrude mortar from the joint and produce a tight joint. Deep furrowing which produces voids shall not be used. The initial bed joint thickness shall not be less than 5 mm or more than 25 mm; subsequent bed joints shall be not less than 5 mm or more than 15 mm in thickness. (b) All surfaces in contact with mortar or grout shall be clean and free of deleterious materials. (c) Solid masonry units shall have full head and bed joints. (d) All head and bed joints shall be filled solidly with mortar for a distance from the face of the unit not less than the thickness of the shell. Head joints of open-end units with beveled ends need not be mortared. The beveled ends shall form a grout key which permits grout within 16 mm of the face of the unit. The units shall be tightly butted to prevent leakage of grout.7.10.4 Verticality and Alignment
All masonry shall be built true and plumb within the tolerances prescribed below. Care shall be taken to keep the perpends properly aligned. (a) Deviation from vertical within a storey shall not exceed 6 mm per 3m height. (b) Deviation in verticality in total height of any wall of a building more than one storey in height shall not exceed 12 mm. (c) Deviation from position shown on plan of any brickwork shall not exceed 12 mm. (d) Relative displacement between load bearing walls in adjacent storeys intended to be in vertical alignment shall not exceed 6 mm. (e) Deviation of bed joint from horizontal in a length of 12 m shall not exceed 6 mm subject to a maximum deviation of 12 mm. (f) Deviation from the specified thickness of bed joints, cross joints and perpends shall not exceed one-fifth of the specified thickness.7.10.5 Reinforcement Placing
Reinforcing details shall conform to the requirements of Sec 7.6.6. Metal reinforcement shall be located in accordance with the plans and specifications. Reinforcement shall be secured against displacement prior to grouting by wire positioners or other suitable devices at intervals not exceeding 20 bar diameters. Tolerances for the placement of steel in walls and flexural elements shall be ±12 mm for 0 ≤200 mm, ±25 mm for 200 mm ≤0 ≤600 mm and ± 30 mm for 0 > 600 mm. Tolerance for longitudinal location of reinforcement shall be ± 50 mm.7.10.6 Grouted Masonry
Grouted masonry shall be constructed in such a manner that all elements act together as a structural element. Space to be filled with grout shall be clean and shall not contain any foreign materials. Grout materials and water content shall be controlled to provide adequate workability and shall be mixed thoroughly. The grouting of any section of wall shall be completed in one day with no interruptions greater than one hour. Size and height limitations of the grout space or cell shall not be less than those shown in Table 6.7.19. Higher grout pours or smaller cavity widths or cell size than shown in Table 6.7.19 may be used when approved, if it can be demonstrated that grout spaces are properly filled. Cleanouts are required for all grout pours over 1.5 m in height. When required, cleanouts shall be provided in the bottom course at every vertical bar but shall not be spaced more than 800 mm on centre for solidly grouted masonry. When cleanouts are required, they shall be sealed after inspection and before grouting. When cleanouts are not provided, special provisions must be made to keep the bottom and sides of the grout spaces, as well as the minimum total clear area as required by Table 6.7.19, clean and clear prior to grouting. Table 6.7.19: Grouting Limitations Grout Type Grout pour Maximum Height (m) Minimum Dimensions of the Total Clear Areas within Grout Spaces and Cells Multi-wythe Masonry (mm) Hollow Unit Masonry (mm ) Fine 0.30 1.50 2.40 3.65 7.30 4050 4050 4075 4575 7575 Coarse 0.30 1.50 2.40 3.65 7.30 4075 6075 7575 7575 751007.10.7 Chases, Recesses and Holes
(a) Chases, recesses and holes may be permitted in masonry provided either they are considered in the structural design or they are not cut into walls made of hollow or perforated units, or vertical chases are planned instead of horizontal chases. (b) Depth of vertical and horizontal chases in load bearing walls shall not exceed one-third and one-sixth of the wall thickness respectively. (c) Vertical chases shall not be closer than 2 m in any stretch of wall and shall not be located within 350 mm of an opening or within 230 mm of a cross wall that serves as stiffening wall for stability. Width of a vertical chase shall not exceed the thickness of wall in which it occurs. (d) Horizontal chases shall be located in the upper or lower middle third height of wall at a distance not less than 600 mm from lateral support. No horizontal chase shall exceed one metre in length and there shall not be more than 2 chases in any one wall. Horizontal chases shall have minimum mutual separation distance of 500 mm. Sum of lengths of all chases and recesses in any horizontal plane shall not exceed one-fourth the length of the wall. (e) Lintel shall not be used to support masonry directly above a recess or a hole wider than 300 mm. No lintel however, is necessary in case of a circular recess or hole exceeding 300 mm in diameter provided upper half of the recess or hole is built as a semi-circular arch of adequate thickness and there is adequate length of masonry on the sides of openings to resist the horizontal thrust. (f) Recesses and holes in masonry shall be kept at the time of construction so as to avoid subsequent cutting. If cutting is necessary, it shall be done using sharp tools without causing heavy impact and damage to the surrounding areas. (g) No chase, recess or hole shall be provided in half-brick load bearing wall, excepting the minimum number of holes needed for scaffolding.7.11 Confined Masonry
7.11.1 General
Confined masonry construction consists of masonry walls (made either of clay brick or concrete block units) and horizontal and vertical RC confining members built on all four sides of a masonry wall panel. Vertical members, called tie- columns or practical columns, resemble columns in RC frame construction except that they tend to be of far smaller cross-section. Horizontal elements, called tie-beams, resemble beams in RC frame construction. To emphasize that confining elements are not beams and columns, alternative terms horizontal ties and vertical ties could be used instead of tie-beams and tie-columns. The confining members are effective in (a) Enhancing the stability and integrity of masonry walls for in-plane and out-of-plane earthquake loads (confining members can effectively contain damaged masonry walls), (b) Enhancing the strength (resistance) of masonry walls under lateral earthquake loads, and (c) Reducing the brittleness of masonry walls under earthquake loads and hence improving their earthquake performance. The structural components of a confined masonry building are (see Figure 6.7.6): (a) Masonry walls – transmit the gravity load from the slab(s) above down to the foundation. The walls act as bracing panels, which resist horizontal earthquake forces. The walls must be confined by concrete tie-beams and tie-columns to ensure satisfactory earthquake performance. (b) Confining elements (tie-columns and tie-beams) - provide restraint to masonry walls and protect them from complete disintegration even in major earthquakes. These elements resist gravity loads and have important role in ensuring vertical stability of a building in an earthquake. (a) Floor and roof slabs - transmit both gravity and lateral loads to the walls. In an earthquake, slabs behave like horizontal beams and are called diaphragms. (b) Plinth band - transmits the load from the walls down to the foundation. It also protects the ground floor walls from excessive settlement in soft soil conditions. (c) Foundation - transmits the loads from the structure to the ground. The design of confined masonry members shall be based on similar assumptions to those set out for unreinforced and for reinforced masonry members. Confined masonry shall be constructed according to the provisions of this Section. Figure 6.7.6 Typical confined masonry building7.11.2 Difference of Confined Masonry from RC Frame Construction
The appearance of a finished confined masonry construction and a RC frame construction with masonry in fills may look alike, however these two construction systems are substantially different. The main differences are related to the construction sequence, as well as to the manner in which these structures resist gravity and lateral loads. These differences are summarized in Table 6.7.20 and are illustrated by diagrams in Figure 6.7.7. In confined masonry construction, confining elements are not designed to act as a moment-resisting frame; as a result, detailing of reinforcement is simple. In general, confining elements have smaller cross-sectional dimensions than the corresponding beams and columns in a RC frame building. It should be noted that the most important difference between the confined masonry walls and infill walls is that infill walls are not load-bearing walls, while the walls in a confined masonry building are. A transition from RC frame to confined masonry construction in most cases leads to savings related to concrete cost, since confining elements are smaller in size than the corresponding RC frame members. Table 6.7.20: Comparison between confined masonry and RC frame construction Component Confined masonry construction RC frame construction Gravity and lateral load- resisting system Masonry walls are the main load bearing elements and are expected to resist both gravity and lateral loads. Confining elements (tie- beams and tie-columns) are significantly smaller in size than RC beams and columns. RC frames resist both gravity and lateral loads through their relatively large beams, columns, and their connections. Masonry in fills are not load-bearing walls. Foundation construction Strip footing beneath the wall and the RC plinth band Isolated footing beneath each column Superstructure construction sequence- Masonry walls are constructed first.
- Subsequently, tie-columns are cast in place.
- Finally, tie-beams are constructed on top of the walls, simultaneously with the floor/roof slab construction.
- The frame is constructed first.
- Masonry walls are constructed at a later stage and are not bonded to the frame members; these walls are nonstructural, that is, non-load bearing walls.